GENESIS™

Air Conditioner

All Models

INSTRUCTION MANUAL

Содержание Genesis

Страница 1: ... 2013 Pentair Equipment Protection 89104462 Rev B P N 89104462 GENESIS Air Conditioner All Models INSTRUCTION MANUAL ...

Страница 2: ... 15 M33 Design Data 16 M33 Dimensional Drawing 16 M33 Mounting Gasket and Cutout Dimensions 17 M33 Components List 18 M33 Wire Diagram and Schematic 115 V 4000 BTU 19 Wire Diagram 230 V 4000 BTU 19 M36 Design Data 20 M36 Dimensional Drawing 20 M36 Mounting Gasket and Cutout Dimensions 21 M36 Components List 22 M36 Schematic and Wire Diagram 115 230 Volt 6000 BTU 22 M52 Design Data 23 M52 Dimension...

Страница 3: ...ITY BEFORE MOUNTING THE AIR CONDITIONER TO THE ENCLOSURE Refer to the nameplate for proper electrical current requirements and then connect the power cord to a properly grounded power supply Minimum circuit ampacity should be at least 125 of the amperage shown in the design data section for the appropriate model No other equipment should be connected to this circuit to prevent overloading Operate ...

Страница 4: ...vided install gaskets to air conditioner See gasket kit illustration in this manual for proper location 4 Mount air conditioner on enclosure using mounting bolts and screws provided EZ mount tabs can be used to hold unit on enclosure while mounting in place Allow unit to remain upright for a minimum of five 5 minutes before starting Caution Air conditioner must be in upright position during operat...

Страница 5: ...1 800 1000 125 52 48 22 M13 0126 G1008 Stock 230 50 60 2 2 2 1 1 800 1000 125 52 48 22 M13 0126 G1XXX 230 50 60 2 2 2 1 1 800 1000 125 52 48 22 XXX will be replaced with a three digit number designating all desired options Consult the factory for specific model numbers M13 DIMENSIONAL DRAWING M13 MOUNTING GASKET AND CUTOUT DIMENSIONS Mounting gasket kit 17 1000 50 included Apply gasket to the back...

Страница 6: ...bly Narrow N S 10 1106 100 10 1106 100 Filter Air Reusable Narrow N S 10 1000 57 10 1000 57 Filter Dryer 7 52 6028 00 52 6028 00 Grille Front Narrow N S 10 1130 01 10 1130 01 Pan Condensate 9 10 1130 12 10 1130 12 Pan Evaporator 10 10 1130 13 10 1130 13 Relay Compressor Start 11 10 1028 05 10 1028 07 Service Cord 12 52 6035 138 52 6035 139 Terminal Block 13 10 1003 03 10 1003 03 Thermal Overload C...

Страница 7: ... 2013 Pentair Equipment Protection 89104462 7 M13 SCHEMATIC AND WIRE DIAGRAM 115 230 VOLT 1000 BTU ...

Страница 8: ... 1500 1800 125 52 56 25 M17 0226 G004 Stock 220 230 50 60 4 2 3 7 1 1500 1800 125 52 56 25 M17 0226 GXXX 220 230 50 60 4 2 3 7 1 1500 1800 125 52 56 25 XXX will be replaced with a three digit number designating all desired options Consult the factory for specific model numbers M17 DIMENSIONAL DRAWING M17 MOUNTING GASKET AND CUTOUT DIMENSIONS Mounting gasket kit 17 1000 50 included Apply gasket to ...

Страница 9: ...74 Control Panel Assembly Narrow N S 10 1106 100 10 1106 100 Filter Air Reusable Narrow N S 10 1000 57 10 1000 57 Filter Dryer 7 52 6028 03 52 6028 03 Grille Front Narrow N S 10 1130 01 10 1130 01 Pan Condensate 9 10 1130 14 10 1130 14 Pan Evaporator 10 10 1130 18 10 1130 18 Relay Compressor Start 11 10 1028 05 10 1028 07 Service Cord 12 52 6035 138 52 6035 139 Terminal Block 13 10 1003 03 10 1003...

Страница 10: ... 2013 Pentair Equipment Protection 89104462 10 M17 SCHEMATIC AND WIRE DIAGRAM 115 VOLT 1800 BTU M17 SCHEMATIC AND WIRE DIAGRAM 230 VOLT 1800 BTU ...

Страница 11: ...98 45 M28 0226 GXXX 230 50 60 5 0 4 5 1 2200 2200 125 52 98 45 M28 0416 G007 STOCK 115 50 60 14 6 14 0 1 3800 4000 125 52 116 53 M28 0416 GXXX 115 50 60 14 6 14 0 1 3800 4000 125 52 116 53 M28 0426 G032 STOCK 230 50 60 7 4 6 9 1 3800 4000 125 52 116 53 M28 0426 GXXX 230 50 60 7 4 6 9 1 3800 4000 125 52 116 53 M28 0616 GXXX 115 50 60 16 4 17 2 1 5400 6000 125 52 120 55 M28 0626 GXXX 230 50 60 8 0 1...

Страница 12: ...gasket kit 28 1000 50 included Apply gasket to the back of the air conditioner before mounting to enclosure 1 Dashed lines represent air conditioner 2 Cutout dimensions are for standard unit 3 Hole may be deleted if service cord is routed through 3 00 x 13 50 cutout except on units with electric heat ...

Страница 13: ...50 Thermostat SPST 55 100F 15 10 1061 16 10 1061 16 10 1061 16 Transformer 10 VAC Secondary 16 10 1006 114 10 1006 114 10 1006 114 Part Description Item Number Part Number 230 Volt 2200 BTU 4000 BTU 6000 BTU Blower Condenser 1 30 4019 02M 30 4019 02M 38 2020 04 Blower Evaporator 2 28 1064 05M 28 1064 05M 28 1064 05M Capacitor Compressor Start Run 3 10 1032 09 10 1032 14 10 1032 18 Coil Condenser 4...

Страница 14: ... 2013 Pentair Equipment Protection 89104462 14 M28 SCHEMATIC AND WIRE DIAGRAM 115 VOLT 2200 BTU AND 230 VOLT 6000 BTU M28 SCHEMATIC AND WIRE DIAGRAM 230 VOLT 2200 BTU ...

Страница 15: ... 2013 Pentair Equipment Protection 89104462 15 M28 SCHEMATIC AND WIRE DIAGRAM 115 230 VOLT 4000 BTU 230 VOLT 6000 BTU M28 SCHEMATIC AND WIRE DIAGRAM 115 VOLT 6000 BTU ...

Страница 16: ...M33 0416 G010 Stock 115 50 60 11 6 10 8 1 3700 4000 131 55 105 48 M33 0416 GXXX 115 50 60 11 6 10 8 1 3700 4000 131 55 105 48 M33 0426 G009 Stock 230 50 60 4 4 4 7 1 3700 4000 131 55 105 48 M33 0426 GXXX 230 50 60 4 4 4 7 1 3700 4000 131 55 105 48 XXX will be replaced with a three digit number designating all desired options Consult the factory for specific model numbers M33 DIMENSIONAL DRAWING ...

Страница 17: ...t kit 33 1000 50 included Apply gasket to the back of the air conditioner before mounting to enclosure 1 Dashed lines represent aire conditioner 2 Cutout dimensions for standard unit 3 Service cord to be routed through 2 00 x 11 12 cutout 4 Bottom cutout will accomodate air conditioner or heat exchanger ...

Страница 18: ...02 Control Panel Assembly Narrow N S 10 1106 100 10 1106 100 Filter Air Reusable Narrow N S 10 1000 57 10 1000 57 Compressor AK 7 89100365 89104088 Grille Front Narrow N S 10 1130 01 10 1130 01 Filter Dryer 8 52 6028 00 52 6028 00 Hot Gas By Pass Valve 9 52 6027 16 52 6027 16 Pan Condensate 10 10 1130 17 10 1130 17 Pan Evaporator 11 10 1130 16 10 1130 16 Relay Compressor Start 12 N A 89100495 Serv...

Страница 19: ... 2013 Pentair Equipment Protection 89104462 19 M33 WIRE DIAGRAM AND SCHEMATIC 115 V 4000 BTU 89100994 WIRE DIAGRAM 230 V 4000 BTU ...

Страница 20: ... Weight lb kg M36 0616 G307 Stock 115 50 60 10 0 10 0 1 5000 6000 105 48 M36 0616 GXXX 115 50 60 10 0 10 0 1 5000 6000 105 48 M36 0626 G306 Stock 230 50 60 5 0 5 0 1 5000 6000 105 48 M36 0626 GXXX 230 50 60 5 0 5 0 1 5000 6000 105 48 XXX will be replaced with a three digit number designating all desired options Consult the factory for specific model numbers M36 DIMENSIONAL DRAWING ...

Страница 21: ... CUTOUT DIMENSIONS Mounting gasket kit 36 1000 50 included Apply gasket to the back of the air conditioner before mounting to enclosure 1 Dashed lines represent aire conditioner 2 Cutout dimensions for standard unit 3 Service cord to be routed through 3 00 x 14 00 cutout ...

Страница 22: ...Air Reusable Wide N S 10 1000 56 10 1000 56 Filter Dryer 7 52 6028 00 52 6028 00 Grille Front Wide N S 10 1130 00 10 1130 00 Pan Condensate 9 10 1130 17 10 1130 17 Pan Evaporator 10 10 1130 19 10 1130 19 Relay Compressor optional N S 10 1042 06 10 1042 13 Start Capacitor Compressor optional N S 10 1032 08 10 1032 08 Time Delay Relay optional N S 10 1005 71 N A Contactor optional N S 10 1005 41 N A...

Страница 23: ...2 160 73 M52 1016 038 Stock 110 115 50 60 18 9 19 5 1 8300 10000 125 52 165 75 M52 1016 XXX 110 115 50 60 18 9 19 5 1 8300 10000 125 52 165 75 M52 1026 021 Stock 220 230 50 60 9 5 9 8 1 8300 10000 125 52 165 75 M52 1026 XXX 220 230 50 60 9 5 9 8 1 8300 10000 125 52 165 75 M52 1216 017 Stock 110 115 50 60 24 0 23 0 1 10000 12000 125 52 175 79 M52 1216 XXX 110 115 50 60 24 0 23 0 1 10000 12000 125 5...

Страница 24: ... gasket kit 52 1000 50 included Apply gasket to the back of the air conditioner before mounting to enclosure 1 Dashed lines represent air conditioner 2 Cutout dimensions for standard unit 3 Hole may be deleted if service cord is routed through 4 50 x 15 63 cutout except on units with electric heat ...

Страница 25: ... 04 10 1007 05 10 1007 05 Thermostat SPST 55 100F 15 10 1061 16 10 1061 16 10 1061 16 10 1061 16 Transformer 10 VAC Secondary 16 10 1006 114 10 1006 114 10 1006 114 10 1006 114 Part Description Item Number Part Number 230 Volt 6000 BTU 8000 BTU 10000 BTU 12000 BTU Blower Condenser 1 52 6025 10 52 6025 10 52 6025 10 52 6025 10 Blower Evaporator 2 52 6076 00 52 6076 00 52 6076 00 52 6025 10 Capacito...

Страница 26: ... 2013 Pentair Equipment Protection 89104462 26 M52 SCHEMATIC AND WIRE DIAGRAM 115 VOLT 10000 AND 12000 BTU M52 SCHEMATIC AND WIRE DIAGRAM 115 230 VOLT 6000 8000 BTU AND 230 VOLT 10000 12000 BTU ...

Страница 27: ...306 STOCK 230 50 60 5 5 4 6 1 2200 2200 125 52 90 41 MHB11 0226 G3XX 230 50 60 5 5 4 6 1 2200 2200 125 52 90 41 MHB11 0416 G307 STOCK 110 115 50 60 14 7 13 6 1 3300 4000 125 52 108 49 MHB11 0416 G3XX 110 115 50 60 14 7 13 6 1 3300 4000 125 52 108 49 MHB11 0426 G306 STOCK 220 230 50 60 8 0 7 5 1 3300 4000 125 52 108 49 MHB11 0426 G3XX 220 230 50 60 8 0 7 5 1 3300 4000 125 52 108 49 XXX will be repl...

Страница 28: ...ssor AE AK AE AK 6 10 1016 22 10 1016 26 10 1026 74 10 1026 77 Control Panel Assembly Wide N S 10 1106 101 10 1106 101 10 1106 101 10 1106 101 Filter Air Reusable Wide N S 10 1000 56 10 1000 56 10 1000 56 10 1000 56 Filter Dryer 7 52 6028 00 52 6028 00 52 6028 00 52 6028 00 Grille Front Wide N S 10 1130 00 10 1130 00 10 1130 00 10 1130 00 Hot Gas By Pass Valve 8 52 6027 16 52 6027 16 52 6027 16 52...

Страница 29: ... 2013 Pentair Equipment Protection 89104462 29 MHB11 SCHEMATIC AND WIRE DIAGRAM 115 VOLT 2200 BTU AND 230 VOLT 6000 BTU ...

Страница 30: ... 2013 Pentair Equipment Protection 89104462 30 MHB11 SCHEMATIC AND WIRE DIAGRAM 230 VOLT 2200 BTU MHB11 SCHEMATIC AND WIRE DIAGRAM 115 230 VOLT 4000 BTU 230 VOLT 6000 BTU ...

Страница 31: ... 2013 Pentair Equipment Protection 89104462 31 NOTES ...

Страница 32: ...ed with Breaking of seals on compressor access fittings during warranty period will void warranty on hermetic system Recharging ports are provided for the ease and convenience of reputable refrigeration repair service personnel for recharging the air conditioner INLET AIR FILTER Proper maintenance of the inlet air filter located behind the front cover will assure normal operation of the air condit...

Страница 33: ...ENSER AND EVAPORATOR AIR MOVERS Blower and impeller motors require no maintenance All bearings shafts etc are lubricated during manufacturing for the life of the motor If the condenser blower motor ambient blower should fail it is not necessary to remove the air conditioner from the cabinet or enclosure to replace the blower The condenser blower is mounted on its own bulkhead and is easily accessi...

Страница 34: ...re airflow YES proceed to step 6 NO possible problem Defective thermostat Open motor winding Stuck blower motor Obstructed wheels blades Repair or Replace defective part 6 Carefully check the compressor for operation motor should cause slight vibration and the outer case of the compressor should be warm Is the compressor showing signs of this YES wait 5 minutes then proceed to step 7 NO possible p...

Страница 35: ...t won t run Low line voltage at start Should be 10 rated voltage Compressor motor stuck Bad contactor Bad overload switch Bad run start capacitor Unit blows breakers Undersized breaker fuse or not time delayed Short in system Getting water in enclosure Drain plugged Drain tube kinked Enclosure not sealed allowing humidity in For additional technical information i e amp draw pressures temperatures ...

Страница 36: ... 2013 Pentair Equipment Protection 89104462 36 NOTES ...

Страница 37: ... 2013 Pentair Equipment Protection 89104462 37 NOTES ...

Страница 38: ... than fourteen 14 days from the date when Buyer has become aware of such occurrence or where the defect is such that it may cause damage immediately such notice containing a description of how the defect manifests itself Failure to provide such prompt notice to Pentair Equipment Protection shall result in forfeiture of Buyer s rights under this warranty In the event of a warranty claim Buyer is to...

Страница 39: ...st Failure Analysis can be provided by Pentair Equipment Protection for warrantable goods at no charge Failure analysis for non warranty repairs are subject to a 100 per hour Engineering charge plus any other incurred testing costs F All returned merchandise must be sent to the following address Pentair Equipment Protection 2100 Hoffman Way Anoka MN 55303 1745 G Credit for accepted returns shall b...

Страница 40: ... 2013 Pentair Equipment Protection 89104462 Rev B P N 89104462 Pentair Equipment Protection 2100 Hoffman Way Minneapolis MN 55303 USA 1 763 422 2211 1 763 576 3200 PentairEquipmentProtection com ...