NOTE: 

The terminals on the TSF units are labeled 

Ground  / Earth 1,2 (unprotected side) and 7,8 

(protected side), Neutral 3,4 (unprotected side) and 

9,10 (protected side), and Line 5,6 (unprotected side) 

and 11,12 (protected side). 

For installations in accordance with the National 

Electrical Code (NEC) and UL

®

1449, use the fuse 

specified in column A.  For installations in accordance 

with the International Electrotechnical Commission 

(IEC) 60364 and 61643, use the circuit breaker 

specified in column B.   

Figure 1:  Wiring Diagram

Table 2:  Fuse Rating and Wire Size

5.  Mounting

TSF's are designed to clip onto 35mm DIN rails 

(standard EN50022). Unless otherwise mechanically 

restrained, use horizontal DIN rails with the snap fit 

design of the TSF to mount the unit with the label text 

in the correct orientation.

NOTE: 

TSF's must be installed in an enclosure or panel 

which:

• prevents the TSF unit ambient temperature from 

exceeding 104°F (40°C). 

• provides adequate electrical and safety protection

• prevents the ingress of moisture and water

• allows the plug-in module visual indication flag to be 

inspected

6.  Ground Fault Circuit Interruption (GFCI)

Where GFCI protectors (RCD's/ELCB's) are used, it 

is preferable that the TSF modules be installed prior 

to these devices (i.e. upstream). If this is not done, 

nuisance tripping of the GFCIs may occur during 

transient activity.

7.  Conductor Termination

Each TSF terminal is designed to accept wire sizes 

from 14 AWG to 10 AWG (2.5mm

²

 - 6mm

²

) solid or 

stranded conductors. The wire insulation should be 

stripped back .28-.31 in. (7-8mm) before terminating 

into the tunnel terminal. 

NOTE: 

Do not use greater than 7 in-lb (1.0 Nm) of torque 

when tightening the terminals.

8.  FUSING AND ISOLATION

Overcurrent protection must be installed in the 

upstream circuit of every TSF to provide protection to 

the unit itself, the load and the wiring in case of fault 

situations. The overcurrent protection device and the 

wire size used should be determined according to 

table 2.    

9.  Status Indication

TSF modules have a visual indicator flag on the plug-

in module. Should the plug-in module reach end-of-

life the visual indicator flag provides user-feedback. 

Refer to figure 2 for visual flag indicator. The TSF 

module should be replaced, as optimum protection is 

no longer provided. Refer to Table 1 for replacement 

module part number information.

10.  Maintenance & Testing

The convenient plug-in module and separate base 

design facilitates replacement of a failed plug-in surge 

module without needing to undo installation wiring. In 

the event you are removing the TSF module, ensure 

that the power has been removed from the TSF 

module before removing a TSF module from service. 

Replacement of a TSF module should only be 

undertaken by qualified personnel.

NOTE:

 TSF units should be inspected periodically, and also 

following any periods of lightning or transient voltage 

activity. Check the visual indicator flag and replace the 

plug-in module if the flag has been activated as in Section 9 

Status Indication.

11.  Remote Alarm Contact

The TSF has a form C alarm contact for remote 

indication of protection status. Refer to figure 3 for 

remote alarm plug-in information. The alarm contacts 

are rated at 3A @ 125VAC.  Use 16 AWG wires to 

connect to the M2 contact screws. 

Figure 2:  Visual Indicator       Figure 3: Remote Alarm Contacts

Transient Surge Filter

ERICO CRITEC TSF Series

(1&2) Bussmann FNQR7-1/2 and Mersen ATMR25 are required for UL 1449 certification.

(3&4) Clipsal 4CB106/10 and Clipsal 4CB116/10 were used for IEC 61643-11 testing

TECHNICAL SUPPORT

www.erico.pentair.com

IP8276_E

2 OF 2