IntelliFlo VF Pump Settings

TO CHANGE THE PUMP TYPE: Press the Right button to 

Select 

Pump Type

Press the 

Up/Down button

 and select 

Y

, then press the 

Right button

. Press the 

Up/Down button

 to change the pump type to 

VS or VF

. Press 

MENU

 to save and 

return to the selected pump’s settings.  

FILT. CIRCUIT: Press Down button, 

Choose 

FILT > CIRCUIT

. Press 

Up/Down 

button

 to select the pool filter circuit: 

NONE, SPA, POOL, AUX 1-7 (ET8), AUX 1-3 

(ET4)

 and

 FEATURE 1-8

. Press 

MENU

 to save. 

VF FLOWS: Press Down button: 

Choose 

Flows

. Press 

Right button: 

 Access the 

IntelliFlo VF flow settings.

 Press the Up/Down buttons

 to set 

GPM (15-130)

Press Right button to 

CIRCUIT

 for circuit 

1

 of 8. Assign the circuit: 

NONE, SPA, 

POOL, AUX 1-7 (ET8), AUX 1-3 (ET4), FEATURE 1-8, SOLAR 

(if enabled in the 

Solar menu)

 

or

 AUX EXTRA 

(only if Solar is not selected, see page 25 and 42),

 

HEATER, POOL HEATER, SPA HEATER, FREEZE, 

and 

HI_SPEED.

 AUX EXTRA 

is only available if the Solar output (J17) plug on the EasyTouch motherboard 

is not being used for solar equipment. After circuit selection is finished, press 

Right button: 

Press the Up arrow button and go to the next circuit page settings 

(

2

/8) and repeat GPM and CIRCUIT settings setup. Up to eight (8) circuits can be 

assigned.  

When finished , Press the 

MENU button

 to save and exit to previous menu.

Press Down/Up button to select FILTERING

PRIMING

BACKWASH

VACUUM

, or 

STATUS.

 

Press the Right button to access settings: Press the Up/Down buttons

 

to set parameters. See IntelliFlo VF parameter descriptions below: 

When finished setting up a parameter, press the 

Menu

 button to save the settings 

and to return to the IntelliFlo VF setting menu. When finished setting up all of 

the IntelliFlo VF pump parameters, press the 

Menu

 button until the main screen 

displays.

Filtering

 -Pool Size/Gallons: 0 - 255 (Kgals) - Turnovers per day: (1 - 8) 

Filtering Manual Filter GPM: (15 - 130) Default 30 GPM: Manual Filter sets the 

flow at which the pump will run if it is turned on manually. The IntelliFlo pump 

will only run in the ‘Filter’ mode during the programmed times. For example, 

if the pump is programmed (start/stop times) for the pool circuit to run from 

8:00 AM to 4:00 PM everyday. This program or programs are used by IntelliFlo 

to calculate at what speed it must run given those ‘ON’ times to achieve the 

turnover(s) for that sized pool for the basic filter mode. 

Priming

 - Max Prime Flow GPM: (30 - 130)  Default 55 GPM: Every time the pump 

starts this parameter will negotiate the maximum flow of the pump. If the flow 

is too high, equipment damage can occur. If the flow is to low the pump will not 

prime. This “flow” is system dependent and may require adjustment. The pump 

will never flow more than this parameter is set to, however, it is common for the 

pump to ramp up and down quickly while priming. Always try to keep this flow as 

low as possible for cost savings and safety.

Max Prime Time: (1 - 15 minutes) Default 15 min.: Use this parameter to set the 

time that you want IntelliFlo try and prime before it reports an error. Remember 

that the IntelliFlo will attain prime every time it starts and goes through this 

cycle. The IntelliFlo mechanical seal can withstand about 15 minutes before 

severe damage occurs. The lower the time the quicker you will get a priming 

error if the system is difficult to prime. A well plumbed pool without having the 

strainer removed should prime in less than 30 seconds. If the strainer has been 

removed for cleaning and a substantial amount of air is in the system it should 

prime in about 60 to 90 seconds on the average, however, all systems will be 

different. 

Pump Filtering         

Size     :  1500 

Turns   :  2 

Man Filt: 0

Pump Priming         

Max Flow   :  55 

Max Time   :  5 

Sys time    :  0

 

 

 Priming 

 Backwash 

 Vacuum 

 Status

 

 

 

 

 Pump Type 

 Filt. Circuit 

 Flows 

 Filtering

 

 

 

 

Pump #1         1/8 

GPM   : 30 

Circuit:  

[ AUX 1              ]

Pump #1         1/8 

GPM   : 30 

Circuit:  

[ AUX 1              ]

 

 

Programming EasyTouch: IntelliFlo

Содержание EasyTouch PNP 10

Страница 1: ...EasyTouch EasyTouch PNP 5 EasyTouch PNP 10 Pool and Spa Control Systems AQUATIC SYSTEMS...

Страница 2: ...ings and cautions in this manual DANGER Risk of Electrical Shock or Electrocution This product must be installed by a licensed electrician Installations must comply with The Wiring Rules AS NZS 3000 A...

Страница 3: ...sed to ensure that they do not play with the appliance General Installation Information 1 All work must be performed by a licensed electrician and must conform to all national state and local codes 2...

Страница 4: ...ly EasyTouch Indoor Control Panel P N 520548 4 Circuit P N 520549 8 Circuit EasyTouch Wireless Control Panel P N 520546 4 Circuit P N 520547 8 Circuit Wireless connection kit P N 520639 SpaCommand Spa...

Страница 5: ...tional 24 EasyTouch Menus 25 Programming EasyTouch Step By Step 26 Set the System Date and Time 27 Settings Menu English Metric Fahrenheit Celsius 27 Circuit Names 28 EasyTouch Circuit Names 29 Settin...

Страница 6: ...he pipe should be level and protrude beyond the finished surface of the spa It will be cut back later at installation time Reduce the pipe size down to 12mm or 20mm conduit and run it to the proposed...

Страница 7: ...ematic All equipment should be installed in an appropriate pool zone depending on IP rating as per the Wiring Rules AS NZS 3000 Recommended Hydraulic Schematic for Shared Equipment System CHLORINATOR...

Страница 8: ...wires that have to be connected to the enclosure Make sure to con sider cable lengths for the sensors to the EasyTouch load centre location The Air Temperature Sensor cable is 1m long and the Water T...

Страница 9: ...front door from the hinges 4 Remove the screws securing the high voltage cover panel Remove the cover panel from the enclosure 5 Proceed with Mounting the EasyTouch Load Centre page 10 Installing Con...

Страница 10: ...are being used support the EasyTouch load centre enclosure in position horizontally level and square against the surface and mark the bracket hole pattern on the wall 2 Secure the enclosure with three...

Страница 11: ...n be installed in various sizes of conduit To avoid obstruction into the EasyTouch load centre when using electrical conduit complete the installation of the conduit before concrete is poured Also und...

Страница 12: ...ays and Equipoten tial Bonding of Pool if appli cable Neutral Active F PUMP AUX 1 AUX 2 AUX 3 AUX 4 AUX 5 AUX 6 AUX 7 P POW1 P POW2 CNTRL Always supply A N conductors to CNTRL for power to elec tronic...

Страница 13: ...Page 13 Electrical Installation Relay Wiring Schematic...

Страница 14: ...nections to switch the filter pump heater auxil iary relays motorized valves and connections for temperature sensors EasyTouch Indoor Control Panel and iS4 Spa Side remote To access the motherboard re...

Страница 15: ...retaining screws securing from the top edge of the control panel 2 Fold down the control panel to access the rear of the motherboard for the electrical connec tions 3 Proceed with Installing the Valv...

Страница 16: ...ve A actuator cable plug into the INTAKE suction 3 pin socket and Valve B actuator cable plug into the RETURN three pin socket on the right side of the motherboard for more information see Item 2 and...

Страница 17: ...way from air conditioners During the win ter months to avoid freeze damage to pool and spa equipment mount the air sensor in a shad ed area to assure proper temperature readings The main screen displa...

Страница 18: ...relay to Solar terminal separate solar pump system Menu Settings Solar Enable Yes Menu Heat Menu Pool Temp SRC Solar or solar preferred Menu Heat Menu Spa Temp SRC Heater Gas Heater Only Connect gas...

Страница 19: ...ators and Filter Pump Use the following steps to test the valve actuators CVA24T for proper rotation To test the valve actuators and pump 1 Power up the EasyTouch load centre 2 Press the Mode button o...

Страница 20: ...Page 20 Electrical Installation EasyTouch System Wiring Diagram...

Страница 21: ...croll through the main menu items and to adjust or change settings Use these buttons after pressing the Menu button to access the main menu items While editing settings press and hold the Up or Down b...

Страница 22: ...the heater to cool down heater cool down then when you press the F button to switch off the pump only the heater will turn off then the filter pump will automatically switch off after 10 minutes to al...

Страница 23: ...circuit button will activate the corresponding circuit in either Auto or Service mode When a circuit relay is switched on manually it remains on until either you switch it off manually or the next ti...

Страница 24: ...uator to isolate spa water from pool water and switches the heater on Hi Temp EasyTouch single body system sets the high temperature settings for the spa Circuit LED Circuit name label Spa Hi Temp But...

Страница 25: ...NTROL PANEL SELF TEST STATUS TESTING FOLLOW ON SCREEN PROMPTS TO TEST LCD AND BUTTONS CODE 0 SEE TROUBLESHOOTING SECTION FOR ERROR CODES WATER TEMP FAHRENHEIT CELCIUS STATUS DISPLAY ONLY SOLAR TEMP FA...

Страница 26: ...elliFlo Pump Page 8 Configure valve actuators Page 9 Schedule on off times for automatic circuit activation Page 10 Configure Spa Side remotes Page 11 Optional Advanced set up Page MENU SETTINGS CLOCK...

Страница 27: ...month use this setting to set the number of seconds in five second increments per month to automatically adjust the clock to the correct time Up Down buttons Adjust the offset in five second increment...

Страница 28: ...18 Pool 2 18 Aux 1 7 EasyTouch PNP 10 Aux 1 3 EasyTouch PNP 5 Ft 1 10 18 Ft 8 17 18 AuxX 18 18 Aux Extra The circuit number 1 18 corresponds to its assigned circuit name This name can be changed to s...

Страница 29: ...LL WATERFALL 1 WATERFALL 2 WATERFALL 3 WHIRLPOOL WTRFL LGHT YARD LIGHT FEATURE 1 FEATURE 2 FEATURE 3 FEATURE 4 FEATURE 5 FEATURE 6 FEATURE 7 FEATURE 8 Settings Menu Custom Names There are nearly 100 c...

Страница 30: ...Func SPA Master Spa Freeze No Circuit Func AUX 1 LIGHT Freeze No Freeze Protection Freeze protection switches on a circuit if the outside air temperature sensor detects the temperature is getting clo...

Страница 31: ...the filter pump pulls the water from the pool and returns it to the spa creating a water fall effect Automatic pool cleaners are turned off when this feature is turned on Floor Cleaner This setting mo...

Страница 32: ...pump Do not activate the heater without running the pump The heater will not run if water flow is not detected SOLAR ONLY Solar heating system to be the only heat source In order to display solar opti...

Страница 33: ...HEAT PUMP Is a heat pump being used for solar heat Select Yes or No to enable solar as a heat pump Heat Pump Control instead of Solar Select YES if a heat pump is being used in place of a solar heati...

Страница 34: ...e N SELECT PUMP TYPE Up Down buttons Choose VS or VF Menu button Press the MENU button to save selection and return to the selected pump s menu settings see VS and VF pump settings descriptions below...

Страница 35: ...day 1 8 Filtering Manual Filter GPM 15 130 Default 30 GPM Manual Filter sets the flow at which the pump will run if it is turned on manually The IntelliFlo pump will only run in the Filter mode durin...

Страница 36: ...air traps become problems within the system The display will inform the user when this is engaged and when it is finished during the priming cycle at each start up cycle Backwash Clean Filter PSI 1 5...

Страница 37: ...names Press the Menu button to save the settings and to return to the Settings menu options Press the button again to return to the main menu options or press again to return to the main screen MENU...

Страница 38: ...ms Choose the type Mode of program to run After selecting New the current program number 1 1 for this circuit is displayed Right button To move to the Mode selections Up Down button Choose the program...

Страница 39: ...r Note The following example describes how to use the Schedule feature to program the spa circuit to switch the filter pump on and rotate the valves into the Spa position and switch the heater on This...

Страница 40: ...create a new program and enter the Mode settings Up Down button 1 1 indicates that this circuit has one program If there are existing programs assigned to this circuit use these buttons to view and s...

Страница 41: ...ter pump on and rotate the valves into the Spa position and switch the heater on for one time only This example can also be used if you wanted to program when to filter and heat your pool and switch l...

Страница 42: ...increase the spa water temperature Each time the spa Heat Boost button is pressed the temperature will increase about 1 C The temperature will not go beyond the 40 C limit Right button Assign the nex...

Страница 43: ...p Cntrl Quick Touch Assign 10 BtnSS Row Top Circuit 1 5 SPA IS4 10 BUTN SPA SD 10B Pump Cntrl Quick Touch To assign an iS10 and SpaCommand spa side remote buttons Up Down buttons Select the Top or Bot...

Страница 44: ...2 4 3 4 4 4 Right button Move to the circuit setting Up Down buttons To configure the first button 1 4 on the QuickTouch wireless remote Use these buttons to scroll through the circuit names and find...

Страница 45: ...es screen you can select various preset show colour lighting effects such as American mode and Sunset mode Color Swim or Color Set Using the Hold and Recall feature you can also capture and save a uni...

Страница 46: ...our for the light Right button Switch the selected coloured light ON To switch the light off go to the main Lights menu and select All Off or press the AUX button assigned to the light The AUX button...

Страница 47: ...igned to any position from 1 through 12 To ensure that the Color Swim and Color Set lighting feature colour effects are correct set the position of the light according to where it s located in the poo...

Страница 48: ...ream Right button Select MagicStream Up Down button Select the desired MagicStream laminar features Right button Use this button to activate the selected MagicStream laminar feature After the button i...

Страница 49: ...eature Circuits To switch a feature circuit ON or OFF Right button Select the feature circuit to turn ON or OFF Up Down buttons Choose assigned feature circuit FEATURE 1 8 Right button Switch the sele...

Страница 50: ...for the pool and spa circuits Select YES to use delays for valves Press the Menu button to save and to return to the Settings menu options Delay Cancel Menu Use the Delay Cancel feature for service or...

Страница 51: ...revent over chlorination of the spa the EasyTouch system will automatically drop the chlorine output levels to 1 20th of the current pool output when the spa is switched on For example if the pool out...

Страница 52: ...ble below for ideal Saturation Index levels SI The saturation Index is displayed IDEAL Optimum levels CORROSIVE pH too low SCALING Press the Menu button three times to return to the main screen Note U...

Страница 53: ...to assign to a two speed pump The generic circuits names are NONE SPA POOL AUX 1 7 EasyTouch PNP 10 AUX 1 3 EasyTouch PNP 5 FEATURE 1 8 SOLAR HEATER POOL HEATER SPA HEATER and FREEZE AUX EXTRA is dis...

Страница 54: ...SETTINGS CALIBRATION CALIBRATION Getting There Calibration Water 20 C Air 25 C Solar 45 C 10B Pump Cntrl QuickTouch Man Heat On Calibration MENU SETTINGS MAN HEAT On Off Getting There Advanced Settin...

Страница 55: ...ed and retained in Flash memory in an EEPROM located on the control panel motherboard and optional Indoor Control Panel The EasyTouch user system configuration data can be erased to restore the factor...

Страница 56: ...he front of the wireless device Note After replacing depleted batteries a check battery message is displayed on the screen Press the MENU button twice to continue 4 Press Menu button and select Settin...

Страница 57: ...control panels is initiated from the indoor or wireless control panel The following describes how to synchronize an indoor or wireless control panel Download from outdoor to indoor control panel Press...

Страница 58: ...el UOC Displays the current software revision level for the outdoor control panel Press the Menu button to return to the Settings menu options Press the button again to return to the main menu options...

Страница 59: ...ough salt in pool The water salt level has fallen below 2500 parts per million ppm IntelliChlor will not produce chlorine until additional salt is added manually HIGH CURRENT Check IntelliChlor electr...

Страница 60: ...plays the current outside air temperature Press the Menu button to return to the Settings menu options Press the button again to return to the main menu options or press again to return to the main sc...

Страница 61: ...en and Yellow Indoor Control Panel lights up but fails to operate cor rectly The unit will not turn equipment on off or may turn some items on but not off and may not LEDs near buttons on control pane...

Страница 62: ...ration or circuit to switch as signment Verify motherboard connection Maximum Programs Exceeded The Maximum Programs Exceeded message displays in the Schedules menu if you try to create a new program...

Страница 63: ...S REPLACEMENT PARTS 520946Z EASYTOUCH TRANSCEIVER CIRCUIT BOARD WITH ATTACHED ANTENNA 520658 INDOOR CONTROL PANEL WIRELESS REMOTE FEATURES LABEL Set of 10 521246 QUICKTOUCH II RECEIVER REPLC NOT SHOWN...

Страница 64: ...Phone 0800 654 112 Fax 0800 806 642 National dealer locator Phone 0800 664 269 Email nz sales pentair com Web www pentair co nz International Australia New Zealand Phone 61 3 9709 5800 Fax 61 3 9709 5...

Отзывы: