Warning

The electronic parts of the F02 and all the optional 
modules can be damaged by a discharge of static 
electricity. Before you start, touch a grounded 
metal surface to discharge any static electricity.

1 General safety 
instructions

1.1 intended use

the f02 electric actuators covered in this 
instruction and operating Manual are designed 
for the operation of any kind of quarter-turn 
industrial valves (i.e., ball, butterfly, plug 
and control valves) used in a wide range of 
applications ranging from heavy industrial, 
chemical, petrochemical plants, waterworks, 
water pipelines, waste paper plants and power 
plants to food, brewing and heating, ventilation, 
air conditioning, etc.
Biffi will not be liable for any possible damage 
or physical injury resulting from use in other 
than the designated applications or by lack of 
care during installation, operation, adjustment 
and maintenance of the machine. such risks 
lie entirely with the user. Depending on 
the specific working conditions, additional 
precautions may be requested.
considering that Biffi has no direct control 
over particular applications, operation or 
maintenance conditions, it is the operator’s 
responsibility to comply with all applicable 
safety rules.
Please inform Biffi urgently if you face unsafe 
situations not described in this ioM. it is the 
sole responsibility of the operator to ensure 
that the local health and safety regulations are 
adhered to.
f02 are tested according to en 21680. noise 
level is less than 65 dB (grade a) at 1 m 
distance.

f02 electric actuators are designed in 
accordance with the applicable international 
rules and specifications, but the following 
regulations must be observed in any case:
• the general and safety regulations
• the plant specific regulations and 

requirements

• the proper use of personal and protective 

devices (glasses, clothing, gloves, etc.)

• the proper use of tools, lifting and transport 

equipment

• electrical installation, use and maintenance 

on f02 has to be carried out in accordance 
with the national legislation and statutory 
requirement related to the safe use of f02 
actuators, applicable to the site of installation

• should further information and guidance 

related to the safe use of f02 actuators is 
requested, please contact Biffi

index

1  General safety instructions ......................... 1

2  Machine description .................................... 4

3  storage end pre-installation ....................... 6

4 installation .................................................... 7

5 lubrication ................................................. 14

6  actuator setting and configuration ........... 14

7  Maintenance and trouble-shooting .......... 20

8 Decommissioning ...................................... 21

9  Parts list and drawings.............................. 21

Warning

It is assumed that the installation, configuration, 
commissioning, maintenance and repair works 
are carried out by qualified personnel and 
checked by responsible specialists.

Warning

Any repair work, other than the operations 
outlined in this manual, is strictly reserved to 
qualified Biffi personnel or to personnel directly 
authorized by the company itself.

Biffi 

f02 quarter-turn electric actuator

InstallatIon and MaIntenance InstructIons

www.pentair.com/valves

© 2015 Pentair plc. all rights reserved.

VCiOM-03859-en 15/09

Содержание Biffi F02

Страница 1: ...to F02 are tested according to EN 21680 Noise level is less than 65 dB grade A at 1 m distance F02 electric actuators are designed in accordance with the applicable international rules and specificati...

Страница 2: ...nt of Use of the actuator in contravention of local safety at work legislation Incorrect installation disregard or incorrect application of the instructions provided on the actuator nameplate and in t...

Страница 3: ...ctuator label Figure 1B 1 4 2 1 ATEX label for application in hazardous areas A Manufacturer logo B Product model C Nominal output torque value D Product code E Serial number F Stroking time range G P...

Страница 4: ...ation Control command open counter clockwise or clockwise rotation selectable on the logic board moves the valve to a completely or partially open position Control command closed clockwise or counter...

Страница 5: ...from 24 to 48 V DC V AC 2 7 Options label A label is always provided with base actuators where optional modules will have to be checked out once they are installed after delivery at local organisatio...

Страница 6: ...erproof they just prevent the entry of undesired objects during transport Biffi cannot accept responsibility for deterioration caused on site when the covers are removed 3 2 2 Storage for a brief peri...

Страница 7: ...tuator onto the valve so that the shaft output drive enters the groove of the stem extension This coupling must take place without forcing and only with the weight of the actuator When the actuator ou...

Страница 8: ...valve flange and the actuator coupling block Warning Never lift the valve actuator assembly without securing slings to both the valve and the actuator Never use the handwheel to lift the actuator Warn...

Страница 9: ...staller s responsibility to select the most appropriate electric protection Figure 7 Setting of the mechanical stop Screw 1 Screw 2 4 6 Setting of the angular stroke mechanical stops It is important f...

Страница 10: ...0 580 0 500 2000 8 53 14 50 6 80 3 200 2 520 1 150 1 000 14 00 7 00 3 220 2 530 1 120 0 980 6 100 9 50 4 60 1 900 1 550 0 760 0 670 9 30 4 50 1 920 1 540 0 720 0 620 4 180 7 00 3 40 1 550 1 240 0 600...

Страница 11: ...rd Directive and specific Rules applying to the products Figure 9 Overview of the electrical connections Earth connection X 4 9 Removal of the terminal board enclosure Using a 5 mm Allen key loosen th...

Страница 12: ...und Blinker local selector relay Output contacts Note 3 4 Optional module OM3 3 Contacts shown in intermediate position CLC1 CLC2 end of travel signaling in closing Contacts shown in intermediate posi...

Страница 13: ...to physically separate the power from the signal terminal place the power clamps protection provided with the actuator on the power terminal once you have completed the power cable connection This wi...

Страница 14: ...ortant In case the screws of the cover must be replaced SS Class A4 grade 80 screw must be used with minimum yield strength 600 N mm2 Warning Pay attention not to damage the joint surfaces of the cove...

Страница 15: ...rried out by specifically qualified personnel for operations on powered electronic cards Important The actuators are set in the workshop with the following configuration default value CL limit switch...

Страница 16: ...8 ON PUSH Opening speed 5 4 ON PUSH 6 5 6 ON PUSH 5 8 ON PUSH Closing torque 6 2 50 ON PUSH 9 6 5 75 ON PUSH 6 9 100 ON PUSH Opening torque 7 2 50 ON PUSH 9 7 5 75 ON PUSH 7 9 100 ON PUSH CW CCW 8 0...

Страница 17: ...f the above condition is not respected the setup will not be successful and stroke limit error alarm will be signalized red LED blinking The red LED will continuously flash when the actuator is in set...

Страница 18: ...et to operate with a 63 Nm or 125 Nm motor and a 250 Nm or 500 Nm motor respectively The difference is based on the technical characteristics of the electric motor itself Actuator model 063 Enter set...

Страница 19: ...ftware The relevant Instruction and Operating Manual is available with the A Manager software Warning The controls available via Bluetooth allow full actuator operability at a distance Biffi will not...

Страница 20: ...be required from Biffi please refer to the individual item number shown in Chapter 8 In case of malfunction in the mechanical electronic components in case of grease leaks through the seals or in case...

Страница 21: ...ers or waste disposal companies Batteries Yes Yes Will require special treatment before disposal use specialist recyclers or waste disposal companies 8 Decommissioning 8 1 Disposal and recycling At th...

Страница 22: ...erminal block 1 23 Worm shaft flange 1 24 Anti loosening washer UNI8842 J6 1 25 Base plate ISO 5211 F05 F07 1 26 Cover gasket 1 27 Dowel pin UNI EN 22338 1 28 Earth stud 1 29 Fixed anulus 1 30 Gasket...

Страница 23: ...2 Terminal block 1 23 Worm shaft flange 1 24 Anti loosening washer UNI 8842 J6 1 25 Base plate ISO 5211 F07 F10 1 26 Cover gasket 1 27 Dowel pin UNI EN 22338 1 28 Earth stud 1 29 Fixed anulus 1 30 Gas...

Страница 24: ...rminal block 1 24 Anti loosening washer UNI 8842 J6 2 25 Base plate ISO 5211 F07 F10 F12 1 26 Cover gasket 1 27 Dowel pin UNI EN 22338 1 28 Earth stud 1 29 Fixed anulus 1 30 Gasket 1 31 Indicator 1 32...

Страница 25: ...rive assembly 1 23 Stopper 2 24 Terminal block 1 25 Anti loosening washer UNI 8842 J6 2 26 Base plate ISO 5211 F10 F12 1 27 Cover gasket 1 28 Dowel pin UNI EN 22338 1 29 Earth stud 1 30 Fixed anulus 1...

Страница 26: ...minal block 1 23 Terminal cover gasket 2 24 Anti loosening washer UNI 8842 J6 2 25 Base plate ISO 5211 F10 F14 1 26 Cover gasket 1 27 Dowel pin UNI EN 22338 1 28 Earth stud 1 29 Fixed anulus 1 30 Hous...

Страница 27: ...10 Base housing 1 11 Base plate F12 F16 EN ISO 5211 1 12 Bearing support 1 13 Bushing 2 14 Bushing 1 15 Bushing 1 16 Bushing 1 17 Dowel pin UNI EN 22338 D 8x20 type B 4 18 Gasket 1 19 Hex head screw U...

Страница 28: ...EN 24017 M16x30 2 30 Indicator 1 31 Indicator shaft 1 32 Manual worm shaft 1 33 Motor pinion 1 34 O ring Di 13 94 W 2 62 1 35 O ring Di 25 12 W 1 78 1 36 O ring Di 6 07 W 1 78 1 37 O ring Di 82 22 W 2...

Отзывы: