2
AViD
LP R2
InstallatIon and operatIng InstructIons
3.0 FielD wiring
Attention
Before installing the conduit entry gland, please
ensure that it is the correct size and thread form.
An incorrect gland may affect the enclosure
ingress protection rating.
3.1 The terminal strip base has been
designed to offer easy access for wire
termination.
3.1a It is not necessary to remove the terminal
strip to connect the field wiring, but if
required, first remove the terminal strip
retaining screw and keep safe as this will
be required to secure the terminal strip
when complete.
3.1b Lift the terminal strip evenly off of the
two base pins and terminate the wiring
in accordance with the wiring diagram
which is located on the of the cover.
note
For special builds of the AVID LP product it may be
necessary to have an additional A4 wiring diagram
placed in the packing box.
3.1c Position the terminal strip over the
two base pins and press evenly in the
direction of the pins.
3.1d Secure with the retaining screw removed
in step 3.1a.
4.0 eAsiFix cAM setting
4.1 To set the switch or sensor cam (Fig. 3),
lift the bottom cam and turn until
switch / sensor is activated and then
release. The spring will push the cam
back onto the splined shaft.
4.2 Operate the actuator to the opposite
extreme, push down on the top cam
and turn until the upper switch / sensor
is activated.
4.3 Operate the actuator from one extreme
to the other several times to ensure that
the switches / sensors activate correctly.
5.0 coVer AsseMbly
5.1 Before assembling the cover assembly to
the AVID LP housing, check the cover seal
detail to ensure that it is not damaged
and free of debris.
5.1 Engage the shaft into the beacon bore
and rotate the cover assembly so that the
shaft drive flats fully engage.
5.2 Approximately align the cover with the
housing flange and secure using either
a 8 mm A/F spanner / socket drive or an
appropriately sized flat blade screwdriver.
5.3 Tighten the screws to a torque value of
18 to 22 Lb/Ins.
6.0 reADy For use
6.1 The AVID LP switchbox is now ready
for use.
6.2 If there are any un-used conduit entries,
please ensure that they are plugged using
correctly rated IP blanking plugs.
7.0 technicAl DAtA
Area classification - non hazardous.
Ingress protection - IP66 / 67
switch / sensor options
Mechanical Switch – SPDT Form C,
Electrical rating -
24, 48, 110 & 240 VAC / 15Amps,
24 VDC / 15 Amps
48 VDC / 2.5 Amps
Alternative inductive proximity sensors;
P&F - NJ2-V3-N, NBB3-V3-Z4, NBB2-V3-E2
IFM - IS5026, IS5001, IS0003, IS5003, NS5002
Turck - Bi2-Q10S-AP6X, Bi2-Q10S-YOX
Telemecanique - XS7-H10PA340
Terminal strip –
Weco 302 HDS, 8 points or Klippon MK3,
6 points.
Conduit options –
Up to 2 x M20 x 1.5p or ½”-14 NPT
Ambient Temperature Range –
Minus 20°C to +80°C
Figure 3
Top Cam (OPEN)
Push down, turn
and release.
Bottom Cam
(CLOSED). Lift, turn
and release.