background image

Firmly insert connector into the valve body. Press locking clip 

into position. Make certain the clip is fully engaged.
To remove a clip:
1.  Turn off water and release water pressure at the valve.
2.  Push the water line connectors into the valve body. This will 

help release O-rings that may have seated in place.

3.  Remove the clip by inserting a flat blade under the top 

center of the clip and lifting (prying up) (Figure 4 Connector 

Assembly).

WARNING:

  Do not use pliers to remove a clip. It is likely 

the clip will break. 

Drain Line Flow Control

The drain line flow control (DLFC) requires assembly  

(Figures 4 and 5).

Install washer with printed 

lettering facing the valve body.

1 Inch Drain Line Flow Control

Rates 8 - 20 GPM

Figure 5 - 1" Drain Line Flow Control

Install washer with printed 

lettering facing the valve body.

3/4 Inch Drain Line Flow Control

Rates 4 - 7 GPM

Figure 6 - 3/4" Drain Line Flow Control

Note: Install DLFC washer with printed lettering facing the 

valve body. 

EQUIPMENT INSTALLATION 

continued

Drain Line Connection

NOTE: Standard commercial practices are expressed here. 

Local codes may require changes to the following 

suggestions. Check with local authorities before 

installing a system.

4.  Use appropriate fittings to connect tubing to the DLFC 

connection on valve.

5.  The drain line may be elevated up to 6 feet (1.8 m) providing 

the run does not exceed 15 feet (4.6 m) and water pressure 

at the filter is not less than 40 psi (2.76 bar). Elevation can 

increase by 2 feet (61 cm) for each additional 10 psi (.69 bar) 

of water pressure at the drain connector.

6.  Where the drain line is elevated but empties into a drain 

below the level of the control valve, form a 7 inch (18 cm) 

loop at the far end of the line so that the bottom of the loop 

is level with the drain line connection. This will provide an 

adequate siphon trap.

7.  Secure the discharge end of the drain line to prevent it from 

moving.

Right Way

Figure 7  Drain Line Connection

NOTE: 

Waste connections or drain outlet shall be designed 

and constructed to provide for connection to the 

sanitary waste system through an air gap of two 

pipe diameters or one inch (22 mm), whichever is 

larger. 

WARNING:

 Never insert drain line directly into a drain, 

sewer line, or trap (Figure 7 Drain Line 

Connection). Always allow an air gap between 

the drain line and the wastewater to prevent 

the possibility of sewage being back-siphoned 

into the filter.

Electrical Connection

WARNING:

  This valve and control are for dry location use 

only unless used with a Listed Class 2 power 

supply suitable for outdoor use.

The 363 controller operates on 12-volt alternating current 

power supply. This requires use of the an AC adapter with your 

system.
Make sure power source matches the rating printed on the AC 

adapter. 

4002493 Rev A

4002492 Rev A

Autotrol

®

 363 Demand Automatic Filter Valve • 5

Содержание AUTOTROL 363

Страница 1: ...AUTOTROL 363 DEMAND AUTOMATIC FILTER VALVE Service Manual 2014 Pentair Residential Filtration LLC www pentairaqua com pro...

Страница 2: ...ing seal Do not use pliers or pipe wrenches All plumbing must be completed according to local codes Soldering of the plumbing should be done before connecting to the valve Excessive heat will cause in...

Страница 3: ...degrade to cause system failures Temperature Extreme hot or cold temperatures may cause damage to the valve or controller Freezing temperatures will freeze the water in the valve This will cause phys...

Страница 4: ...softener should be installed downstream of this system Grounding the Plumbing It is important that the plumbing system be electrically grounded When a water treatment system is installed a nonmetallic...

Страница 5: ...to 6 feet 1 8 m providing the run does not exceed 15 feet 4 6 m and water pressure at the filter is not less than 40 psi 2 76 bar Elevation can increase by 2 feet 61 cm for each additional 10 psi 69 b...

Страница 6: ...media tank Turn on the water supply after five minutes Check for leaks The system is now fully operational INSTALLATION CHECKLIST ___ Read the owner s installation manual ___ Follow all safety guideli...

Страница 7: ...set a time duration between cleaning cycles to ensure proper function of the filter in the event of a flow sensor malfunction press and hold and for three seconds The value in days between cleaning c...

Страница 8: ...en and C 4 Repeat steps 2 and 3 to cycle through each position Quick Cycle to Service Position Simultaneously press and and hold for three seconds during any cleaning cycle step The control will skip...

Страница 9: ...PT 360 Fltr 4002469 Kit DLFC 20GPM NPT 360 Fltr 4002476 Kit DLFC 4 0GPM BSP 360 Fltr 4002477 Kit DLFC 4 5GPM BSP 360 Fltr 4002478 Kit DLFC 5 0GPM BSP 360 Fltr 4002479 Kit DLFC 6 0GPM BSP 360 Fltr 4002...

Страница 10: ...haft slots If motor continues to rotate indefinitely replace the following components in this order 1 Motor Assembly Optical Sensor 2 Control System Problem Possible Cause Solution Flowing or dripping...

Страница 11: ...kwash Media Tank Inlet Outlet 1 4 3 2 BACKWASH Drain Drain Control FAST RINSE Untreated Water Rinse Media Tank Inlet Outlet 4 3 Drain Control 1 2 Drain Valve No 1 Closed 2 Open 3 Closed 4 Closed Valve...

Страница 12: ...TA CHARTS 12 Autotrol 363 Demand Automatic Filter Valve 0 5 10 15 20 25 30 1 6 11 16 21 26 PRESSURE DROP IN PSI FLOW IN GPM Service Cv 5 43 0 5 10 15 20 25 30 35 1 6 11 16 21 PRESSURE DROP IN PSI FLOW...

Страница 13: ...egistered marks of their respective owners Because we are continuously improving our products and services Pentair reserves the right to change specifications without prior notice Pentair is an equal...

Отзывы: