Pentair 962 Series Скачать руководство пользователя страница 13

13

Press and hold the (

) and (

) arrow buttons to access Level IV.

Note:  The number of “C” values MUST equal exactly the number of stager regeneration cycles.
Example: If the parameter “Position 5 Cycle Time” is programmed then C1 through C4 must also be programmed.

Table 4 Level IV Parameters

#

Description of Parameter

Range of Values

Minimum 

Increment

Default

Notes

C1

Position 1 Cycle Time

0 min -255 min

1 min

0

Stager Cycle (P17=6 or 9)

C2

Position 2 Cycle Time

0 min -255 min

1 min

0

Stager Cycle (P17=6 or 9)

C3

Position 3 Cycle Time

0 min -255 min

1 min

0

Stager Cycle (P17=6 or 9)

C4

Position 4 Cycle Time

0 min -255 min

1 min

0

Stager Cycle (P17=6 or 9)

C5

Position 5 Cycle Time

0 min -255 min

1 min

0

Stager Cycle (P17=6 or 9)

C6

Position 6 Cycle Time

0 min -255 min

1 min

0

Stager Cycle (P17=6 or 9)

C7

Position 7 Cycle Time

0 min -255 min

1 min

0

Stager Cycle (P17=6 or 9)

C8

Position 8 Cycle Time

0 min -255 min

1 min

0

Stager Cycle (P17=6 or 9)

C9

Position 9 Cycle Time

0 min -255 min

1 min

0

Stager Cycle (P17=6 or 9)

C10

Position 10 Cycle Time

0 min -255 min

1 min

0

Stager Cycle (P17=6 or 9)

C11

Position 11 Cycle Time

0 min -255 min

1 min

0

Stager Cycle (P17=6 or 9)

C12

Position 12 Cycle Time

0 min -255 min

1 min

0

Stager Cycle (P17=6 or 9)

C13 

Position 13 Cycle Time

0 min -255 min

1 min

0

Stager Cycle (P17=6 or 9)

C14

Position 14 Cycle Time

0 min -255 min

1 min

0

Stager Cycle (P17=6 or 9)

C15

Position 15 Cycle Time

0 min -255 min

1 min

0

Stager Cycle (P17=6 or 9)

d1

Sunday

0-1

1

0

0 = no day of week regen this day

d2

Monday

0-1

1

0

0 = no day of week regen this day

d3

Tuesday

0-1

1

0

0 = no day of week regen this day

d4

Wednesday

0-1

1

0

0 = no day of week regen this day

d5

Thursday

0-1

1

0

0 = no day of week regen this day

d6

Friday

0-1

1

0

0 = no day of week regen this day

d7

Saturday

0-1

1

0

0 = no day of week regen this day

Table 5 “C” Level Program Values for Select Stager Configurations

#

48-83

51-09

51-10

51-86

58-00

58-03

58-04

58-TB

C1

BW1 Time

BW Time

BW1 Time

BW1 Time

BW1 Time

BW1 Time

BW1 Time

BW Time

C2

BW2 Time

BR/SR 

Time

FR1 Time

BW2 Time

Draw1 

Time

FR1 Time

FR1 Time

Draw Time

C3

BW3 Time

FR Time

BW2 Time

BW3 Time

SR1 Time

BW2 Time

BW2 Time

SR Time

C4

0

Refill Time

FR2 Time

BW4 Time

FR1 Time

FR2 Time

FR2 Time

FR Time

C5

0

0

0

BW5 Time

BW2 Time

BW3 Time

BW3 Time

0

C6

0

0

0

BW6 Time

Draw2 

Time

FR3 Time

FR3 Time

0

C7

0

0

0

0

Rinse2 

Time

0

BW4 Time

0

C8

0

0

0

0

FR2 Time

0

FR4 Time

0

C9

0

0

0

0

0

0

0

0

C10

0

0

0

0

0

0

0

0

C11

0

0

0

0

0

0

0

0

C12

0

0

0

0

0

0

0

0

C13

0

0

0

0

0

0

0

0

C14

0

0

0

0

0

0

0

0

C15

0

0

0

0

0

0

0

0

Содержание 962 Series

Страница 1: ...TIME OF DAY TIME OF REGEN HARDNESS CAPACITY REGEN TIME REMAINING SET REGEN SERIES 962 FLOW PM Operation Manual Series 962 Electronic Stager Control...

Страница 2: ...2...

Страница 3: ...splay Programming the Series 962 Stager 7 Factory Default Values Program Levels Level I Programming Setting Time of Day Level II Programming Changing a Program Value Level III Programming Level IV Pro...

Страница 4: ...equipment is not supplied with built in overcurrent protection fuses or circuit breakers An external switch and or circuit breaker must be installed by a qualified electrician in accordance with all...

Страница 5: ...nal Input TB2 Terminal 17 Delayed Start Input Dry Contact TB2 Terminal 18 Delayed Start Input Dry Contact TB2 Terminal 19 Lockout Input Dry Contact TB2 Terminal 20 Lockout Input Dry Contact Outputs Te...

Страница 6: ...150 or more Capacity Setting Lockout The control can be programmed to lock the capacity so it cannot be altered after installation Selectable Reserve Options To meet the application requirements the c...

Страница 7: ...ing battery power the display will alternate between Time of Day and Capacity Remaining once power has been restored The control will remain in this display mode until the Time of Day is reset or unti...

Страница 8: ...the new entry is stored and the control automatically scrolls to the next P value If a beep sounds the new entry was not accepted Table 1 lists the range available for a specific program value Level...

Страница 9: ...regeneration This signal can also come from external equipment that can provide a dry contact closure CONNECTION MUST BE A DRY CONTACT NOTE When using the Relay Output Option the lockout feature cann...

Страница 10: ...capacity of zero gallons and override the Time of Regeneration P2 to allow for an immediate regeneration These are the preferred settings for a Twin Alternating softener system Advance Cycle Function...

Страница 11: ...6 or 9 Do not program P10 P11 Rinse time 1 19 1 4 minutes If P17 6 or 9 Do not program P11 P12 Units of measure 0 1 1 0 0 US 1 Metric P13 Clock mode 0 1 1 0 0 12 hour clock 1 24 hour clock P14 Calend...

Страница 12: ...eset L 5 0 655360 0 6553 6 Water used today in gallons M3 since time of regeneration L 6 0 655360 0 6553 6 Water used since last regeneration in gallons M3 L 7 0 655360 0 6553 6 Average water usage fo...

Страница 13: ...12 Cycle Time 0 min 255 min 1 min 0 Stager Cycle P17 6 or 9 C13 Position 13 Cycle Time 0 min 255 min 1 min 0 Stager Cycle P17 6 or 9 C14 Position 14 Cycle Time 0 min 255 min 1 min 0 Stager Cycle P17...

Страница 14: ...on 4 Cycle Time P5 Capacity of unit C5 Position 5 Cycle Time P6 Not used C6 Position 6 Cycle Time P7 Not used C7 Position 7 Cycle Time P8 Not used C8 Position 8 Cycle Time P9 Backwash time C9 Position...

Страница 15: ...controller When using a model 58 TA the Tank in Service is indicated by two NEMA 4 rated door mounted lights that are operated by the stagers second auxiliary switch When using a model 58 TA Twin Alt...

Страница 16: ...ced between terminals 1 and 3 and 2 and 4 For 230VAC jumpers are placed between terminals 2 and 3 only Figure 5 Line voltage and neutral inputs are always on terminals 1 and 4 respectively Figure 5 Fl...

Страница 17: ...ds that the remote input signal will be ignored before starting a regeneration THE CONNECTION MUST BE A NO VOLTAGE DRY CONTACT Figure 8 Remote Regeneration Start Connections Relay Output Option A sing...

Страница 18: ...18 Figure 10 E948 E951 Standard Wiring Design...

Страница 19: ...19...

Страница 20: ...2009 Pentair Residential Filtration LLC P N 1076301 Rev H FE09...

Отзывы: