INSTALLATION INSTRUCTIONS
1. Inspect air conditioner. Verify functionality before mounting the air conditioner, see HANDLING &
TESTING THE AIR CONDITIONER on page 3.
2. Using the cutout dimensions shown in this manual or the cutout template printed on the units
shipping carton, prepare the air “IN” and air “OUT” openings, and mounting bolt hole pattern for
the enclosure.
3. Using the gasket kit provided, install gaskets to air conditioner. See Mounting Gasket on page 5
for proper location.
4. Mount air conditioner on enclosure using mounting bolts and screws provided. “EZ” mount tabs
can be used to hold unit on enclosure while mounting in place. Connect water inlet and outlet
fittings to a clean pressurized water supply. Allow unit to remain upright for a minimum of five (5)
minutes before starting. Caution: Air conditioner must be in upright position during operation.
5. Refer to top of nameplate for electrical requirements. Connect the power cord to a properly
grounded power supply. Use of an extension cord is not recommended. Electrical circuit should be
fused with slow blow or HACR circuit breaker.
TECHNICAL INFORMATION
DESIGN DATA
Model
Voltage
Hertz
Full Load
Amps
Phase
BTU/Hr.
Maximum
°F Water
Temperature
Maximum
Water
Usage
(GPM)
Shipping
(lbs/kg)
330216GWXXX
115
50/60
5.0/4.3
1
2500/2500
90
0.5
85
330226GWXXX
230
50/60
3.1/2.8
1
2500/2500
90
0.5
85
330416GWXXX
115
50/60
6.0/5.8
1
3800/4000
90
0.5
85
330426GWXXX
230
50/60
3.3/3.2
1
3800/4000
90
0.5
85
XXX will be replaced with a three-digit number designating all desired options. Consult the factory for specific model numbers
DIMENSIONAL DRAWING