Installing the float switch set
GL-Base load | Alarm | SL-Peak load
NOTICE!
Do not alter the length of the cables that run from the
float switch to the retaining plate. The lengths have already
been adjusted.
Push the ready-to-install float switch set onto the centre of
the T-piece. Secure the pump cables and float switch cables
adequately in the tank, so that the float switches can float up
unhindered. Feed the float switch cables up through the venti
-
lation pipe (in the same way as the pump cables) to the T-piece
provided by the customer, then through the closing plug to the
control unit, ensuring that the seal is odour-tight.
Installation of floor drain
1. Take out the screws of the cover plate and remove it.
2. Take the plug out of the cover connection piece with a
screwdriver.
3.
Screw the siphon with the union nut, the packing and the
expanding ring on the connection piece.
4. The outlet of the siphon must not be positioned directly
above the pumps.
5.
Grease the screws, ensure the correct position of the pro-
filed seal and screw down the cover plate again.
Accessory alarm device (only single unit)
The alarm device signals an excessive high water level. It can
be installed subsequently. The float switch is fixed to the
pump handle (see the drawing at the front). The cable is pulled
through the vent pipe and sealed in the same way as the pump
cable. The alarm unit should be connected to a separate elec-
tric circuit, to ensure the operation in case of a pump fault. Al-
ternatively it can be equiped with our 9V-rechargeable battery
for off the line operation.
Accessory special ventilation
If the ventilation over the roof level is not possible, alternatively
the special ventilation consisting of a ventilation screen and 3
activated carbon filters can be installed above the T-piece for
the cable in the ventilation pipe. An assembly instruction ac-
companies the special ventilation.
Accessory guide rail system
For the pumps is as an accessory guide rail system available
that can be mounted in the Baufix. A simple pull out and lower
-
ing the pump is possible.
Accessory: sump extension
With the sump extension, the installation depth of the Baufix
200-50 can be increased by between 165 and 265 mm. Howev
-
er, the pumps must still remain accessible for installation and
maintenance works (arm length).
Accessory: tileable cover plate
A stainless-steel cover plate for tiling is available for the Baufix
200-32. The cover plate has an integrated base drain.
MAINTENANCE
The tank, the float switches and the foot strainer of the pump
should be inspected regularly and cleaned if necessary.
To service the pump, please refer to the separate operating
instruction.
NOTICE!
Always grease the screws before using them to close
the cover plate and ensure the correct position of the profiled
seal.