ACCESSORY
Difference in the cone surface pressure and fan inlet pressure (∆p) canbe correlated to the volumetric air flow rate (Q) with which
fan is moving, using equattion shown below and can be analysed to read out the real time fan performance accurate to
To complete the installation of the transducer, follow the installation instructions located at 5%
Q = K * √(∆p)
Q = Volumetric flow rate (CFM)
∆p = Differential Pressure (inWC)
K = Fan constant, as noted in table:
Fan Size
K
122
2512
135
3336
150
4286
165
5236
182
6313
200
7453
222
8847
245
10304
270
11887
300
13787
330
15688
365
17905
402
20248
445
22972
490
25823
542
29117
600
32791
HIGH-PRESSURE
SIDE
LOW-PRESSURE
SIDE
TUBE
TO DIFFERENTIAL
PRESSURE TRANSUDER
HIGH-PRESSURE
SIDE HOLE
ON INLET CONE
LOW-PRESSURE
SIDE HOLE
ON INLET CONE