P78 Series Controls for Dual Pressure Applications Installation Instructions

4

P78 controls for dual pressure applications are available with a Single-Pole, Double-Throw (SPDT) switch. Check 
the label inside the control cover for the model number, switch action, and electrical rating. Check the wiring 
terminal designations on the control switch block, and see the following wiring diagram when wiring the control. 
(See Figure 3 and Table 2). Also see 

Technical Specifications

.

   

Refrigerant Connections        

IMPORTANT:

Use terminal screws furnished in the switch block. Using other terminal screws will void the 

warranty and may damage the switch.

Table 2:  P78 Switch Wiring (SPDT)

LP/HP Description

LP

A-C opens on pressure decrease
A-B closes simultaneously

HP

A-C opens on pressure increase
A-D closes simultaneously

Risk of Environmental and Property Damage.

Avoid sharp bends in the capillary tubes. Sharp bends can weaken or kink capillary tubes, which may result in 
refrigerant leaks or restrictions of flow.

Risque de dommages environnementaux et dégâts matériels.

Éviter de former des coudes serrés avec les tubes capillaires. Les coudes serrés peuvent affaiblir les tubes 
capillaires ou engendrer des pliures, ce qui risque de provoquer des fuites de réfrigérant ou d'en gêner 
l'écoulement.

Figure 3:  P78 Switch Wiring (SPDT)

Содержание P78 Series

Страница 1: ...ol only as an operating control Where failure or malfunction of the control could lead to personal injury or property damage to the controlled equipment or other property additional precautions must b...

Страница 2: ...structions and guidelines included with the control These instructions and guidelines are intended to reduce the risk of malfunction of the control and resulting property damage Failure to follow thes...

Страница 3: ...ket Part Number 271 51 sold separately Risk of Electric Shock Disconnect or isolate all power supplies before making electrical connections More than one disconnection or isolation may be required to...

Страница 4: ...Using other terminal screws will void the warranty and may damage the switch Table 2 P78 Switch Wiring SPDT LP HP Description LP A C opens on pressure decrease A B closes simultaneously HP A C opens...

Страница 5: ...ovoquer des dommages environnementaux ou des d g ts mat riels IMPORTANT If the control is installed on equipment that contains hazardous or regulated materials such as certain refrigerants or lubrican...

Страница 6: ...set Lockout have a scaleplate that displays the low side Cut in Differential and high side Cut out setpoints Item 6 Figure 4 1 Set the low side Cut in setpoint by adjusting the range screw 2 Turn the...

Страница 7: ...eration of the controlled equipment see Item 5 Figure 4 Technical Specifications Callout Description 1 Low Side Range and Differential Scales 2 High Side Range Scale 3 Low Side Range Screw 4 Low Side...

Страница 8: ...5 in 101 x 89 x 64 mm Approximate Shipping Weight Individual Pack Type 1 Enclosure 1 55 lbs 0 7 kg Bulk Pack Type 1 Enclosure in multiples of 35 controls 40 lbs 18 1 kg Compliance cULus Listed UL 6073...

Отзывы: