A421 Control parameter setup menus

The A421 Temperature Controls have a Basic and

Advanced setup menu. You can use these menus to

scroll through the parameter setup codes, view and

edit parameter values, and set up your control for your

application requirement. The control also has a Restricted

adjustment menu. See 

Restricting user adjustment

 for

more information.

Note: 

The A421 Control retains a copy of the saved

parameter values in memory. When you change

and save a new value, the new value immediately

overwrites the previous value and saves to memory.

In the event of a power failure, brown out, or when

you disconnect power from the control, all of the

current parameter values in memory are retained.

Reconnecting power to the control restores all of the

saved values.

Navigating the Basic and Advanced

menus

The A421 Control buttons and display operate the same

way in the Basic and Advanced menus. The parameter

code flashes on and off in any parameter code screen.
1.

To navigate through all of the parameter code

screens, press 

Down

 or 

Up

.

2.

To exit either menu and return to the Main screen,

press 

Down

 and 

Up

 simultaneously.

3.

While in any parameter value screen, the parameter

value flashes on and off.

4.

To scroll through all of the available parameter values

for the associated parameter code, press 

Down

 or

Up

.

5.

With the preferred parameter value displayed,

press 

MENU

 to save the value and go to the next

parameter code screen.

Note: 

If you do not press

 MENU

 to save a new

value, the control reverts to the last saved

value. After 30 seconds of inactivity, while in any

screen, the control reverts to the Main screen.

Basic menu

Use the Basic menu to quickly edit the On and OFF

temperature values, and the Sensor Failure Mode (SF).
See 

Parameter codes and modes of operation

 and Table 3

for more information regarding parameter codes, usable

parameter values, and default values.

Figure 6: Navigating the Basic menu

Viewing and changing values in the Basic

menu

In this task you access the Basic menu and view and

change the Basic parameter values.

1.

On the Main screen, press 

MENU

. The LCD displays

OFF, which is the first parameter code screen

displayed in the Basic menu.

2.

To scroll through all of the basic parameter codes

and display the preferred code, press 

Down

 or 

Up

.

3.

With the preferred parameter code displayed, press

MENU

 to display the current parameter value for the

code.

4.

With the current parameter value displayed, press

Down

 or 

Up

 to scroll through all of the parameter’s

usable values and display the preferred value.

5.

With the preferred parameter value displayed, press

MENU

 to save the displayed value and go to the next

parameter code.

6.

To exit the Basic menu and go to the Advanced menu,

simultaneously press and hold 

Down

 and 

Up

 for 5

seconds.

Advanced menu

The Advanced menu allows you to change the parameter

values in the Basic menu and the values for the following

advanced parameter codes:
• Temperature Units (

Un

)

• Low Temperature Stop (

LtS

)

• High Temperature Stop (

HtS

)

• Low Temperature On-Time (

Ltt

)

• Minimum Relay On-Time (

Ont

)

• Cycle Period (

cP

)

A421 Series Electronic Temperature Controls with Cycle Timer Installation Guide

7

Содержание A421 Series

Страница 1: ...ou de protection en cas de d faillance ou de dysfonctionnement du A421 Control The A421 Series Electronic Temperature Controls are single stage electronic temperature controls with a single pole doubl...

Страница 2: ...range of usable values from 40 F to 212 F or 40 C to 100 C See Wiring Technical specifications and refer to the A99B Series Temperature Sensors Product Technical Bulletin LIT 125186 for more informat...

Страница 3: ...l ratings Exceeding the electrical ratings can result in permanent damage to the control and void any warranty Important Run all low voltage wiring and cables separate from all high voltage wiring It...

Страница 4: ...re for 120 VAC supply power applications Connect the L1 supply power lead for all 208 240 VAC supply power applications 120V Line voltage 120 VAC control power hot Connect the 120 VAC supply power hot...

Страница 5: ...On temperature On Select the temperature at which the output relay energizes the LC to LNO relay contacts close cut in and the green LED lights The range of usable temperature values is 40 F to 212 F...

Страница 6: ...brightest backlight setting and the system default The selected backlight brightness level is applied to the LCD during normal operation When you enter the programming menus to set up the control or p...

Страница 7: ...ave a new value the control reverts to the last saved value After 30 seconds of inactivity while in any screen the control reverts to the Main screen Basic menu Use the Basic menu to quickly edit the...

Страница 8: ...tween the On and OFF values the following behavior is enforced The fan relay is On for at least the Minimum Relay On Time Ont during a Cycle Period cP See Figure 8 The fan relay goes Off when the sens...

Страница 9: ...Restricted mode prevents casual users from over adjusting the control in your application or from inadvertently changing the mode of operation from cooling to heating or heating to cooling by over adj...

Страница 10: ...e See Troubleshooting procedure Cycle power to reset the control SF flashing alternately with SH Shorted temperature sensor or sensor wiring Output functions according to the selected SF mode See Trou...

Страница 11: ...with Cycle Timer Type 1 NEMA IP20 standard enclosure for DIN rail and surface mount applications Rated for 120 240 VAC Includes timer for On Off duty cycle control Includes an A99BB 200C temperature s...

Страница 12: ...Specification Description Power consumption 1 8 VA maximum Supply power 110 120 or 208 230 240 VAC 50 60 Hz Table 8 A421 Series Electronic Temperature Controls Technical Specifications Specification...

Страница 13: ...00 RH condensing Shipping weight 1 4 oz 41 g for 6 1 2 ft 2 m sensor Accessories See Table 7 1 When any A99 Series Temperature Sensor is connected to a standard A421 Control model the range of display...

Страница 14: ...SON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA For more contact information refer to www johnsoncontrols com locations 2019 Johnson Controls Al...

Отзывы: