A19QSC Type Temperature Controls with NEMA 4X Raintight Enclosures Installation Instructions

6

Setup and Adjustments

Turn the knob under the temperature control cover to adjust the setpoint.

Before leaving the installation, observe at least three complete operating cycles of the controlled equipment to 
ensure that all components are functioning correctly.

Follow the guidelines in the 

Operation

 section to check for proper A19QSC temperature control operation.

For heating applications: 

1. Turn the dial clockwise to a setpoint greater than the sensed temperature. The heating system should cycle on. 

2. Turn the dial counterclockwise to a setpoint less than the sensed temperature and the heating system should 

cycle off.

For cooling or ventilating applications: 

1. Turn the dial clockwise to a setpoint greater than the sensed temperature and the ventilating or cooling system 

should cycle off. 

2. Turn the dial counterclockwise to a setpoint less than the sensed temperature and the ventilating or cooling 

system should cycle on.

If the temperature does not operate in the manner described previously, check the wiring and tightness of wiring 
connections.

Operation

When the temperature at the sensing element rises to the setpoint (dial setting), the switch between R and Y 
closes and the switch between R and B opens on SPDT models. See Figure 2, Figure 3, anFigure 4.

Repair Information

If the A19QSC type electromechanical temperature control fails to operate within its specifications, replace the unit. 
For a replacement A19QSC control, contact the nearest PENN by Johnson Controls® representative.

Technical Specifications

A19QSC Type Temperature Controls with NEMA 4X Raintight Enclosures

Switch Contact Ratings

Applied VAC

24

120

208

240

277

600

Motor, Full Load Amperes

-

16

9.2

8

-

-

Motor, Locked Rotor Amperes

-

96

55.2

48

-

-

Non-inductive, Single-Pole, Single-Throw 

(SPST) Amperes

-

22

22

22

22

-

Non-inductive, Single-Pole, Double-Throw 

(SPDT) Amperes

-

16

16

16

16

-

Pilot Duty Volt-Amperes

125

125

125

125

125

125

Ambient Operating Conditions

-26–140°F (-32–60°C)

Ambient Storage Conditions

-40–140°F (-40–60°C)

Shipping Weight

1.2 lb (0.54 kg)

Compliance

UL Listed; File E6688, CCN XAPX (US) and XAPX7 (Canada)
UL Listed as Type 4X

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these 
specifications, consult Johnson Controls Application Engineering at (800) 275-5676. Johnson Controls shall not be liable for damages resulting 
from misapplication or misuse of its products.

Содержание A19QSC

Страница 1: ...be designed into the control system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfuncti...

Страница 2: ...allation Instructions 2 Dimensions Figure 1 Dimensions for A19QSC Temperature Controls with NEMA 4X Enclosures in mm MENU 2 87 73 3x 1 2 Conduit Knockout 2 18 55 2 81 71 4x 20 5 Mtg Hole 6 10 154 0 06...

Страница 3: ...operty MISE EN GARDE Risque de dommages environnementaux et d g ts mat riels Enrouler et fixer l exc dent de tubes capillaires de mani re viter tout contact avec des objets coupants ou des surfaces ab...

Страница 4: ...e the cover and tighten the screws WARNING Risk of Electric Shock Disconnect the power supply before making electrical connections Contact with components carrying hazardous voltage can cause electric...

Страница 5: ...ooling Load L1 L2 Dial R Y to closes on temperature increase A19 Temperature Control FIG cl_app Figure 4 Typical Wiring for Combination Heating and Cooling Applications R B Y Heating Load L2 Dial A19...

Страница 6: ...tion When the temperature at the sensing element rises to the setpoint dial setting the switch between R and Y closes and the switch between R and B opens on SPDT models See Figure 2 Figure 3 and Figu...

Страница 7: ...ed herein are the property of their respective owners Copyright 2018 by Johnson Controls All rights reserved www penncontrols com European Single Point of Contact NA SA Single Point of Contact APAC Si...

Отзывы: