2  

A19ANC/A19ANF/A19APC Installation Instructions 

Optional Constructions 

Sensing Elements 

See Product Selection Chart for 
standard capillary lengths. Other 
lengths are available. Contact a 
Johnson Controls 
representative. 

Bulb Well 

Copper bulb wells with 1/2 in. 
NPT brass connectors are sold 
separately. See Product 
Selection Chart for ordering 
information. For special 
applications requiring a 
connector made with a different 
metal, contact a Johnson 
Controls representative for 
availability. 

Installation 

!

 WARNING: 

Risk of 

electrical shock. 

Disconnect power supply 
before wiring connections 
are made to avoid possible 
electrical shock. 

!

 CAUTION: 

Risk of 

equipment damage. 

Disconnect power supply 
before wiring connections 
are made to avoid damage 
to the equipment. 

Note:

 Use terminal screws 

furnished (8-32 

 1/4 in. binder 

head). Do not substitute screws 
of a different size. Make all 
wiring connections using copper 
conductors only, and in 
accordance with the local, 
national, and regional 
regulations. 

Indoors, mount the thermostat in 
any position by means of three 
mounting feet. When the 
thermostat will be exposed 
directly to the outdoor weather, 
mount the thermostat with the 
electrical conduit, capillary 
fittings, and drain hole facing 
downward as illustrated in Fig. 1. 

Ambient rating (not bulb 
maximums) 140

F (60

C). 

Fig. 3 

– Bulb well dimensions 

IMPORTANT: Do not dent or 

deform the sensing bulb of 
this control. A dent or 
deformation will change the 
calibration and cause the 
control to cycle at a 
temperature lower than the 
dial setting. 

Where the capillary is exposed 
and subject to possible 
mechanical damage some 
means of protection should be 
provided. The capillary outlet is 
designed to permit the capillary 
to be run through 1/2 in. thin wall 
or flexible conduit. Remove the 
capillary outlet seal nut. (See 
Fig. 4.) Push the bulb and 
capillary through a conduit 
coupling or suitable hose fitting 
and on through the conduit or 
hose. By tightening the coupling 
to the 1/2 in. female capillary 
outlet fitting, the seal around the 
capillary will be maintained and 
the conduit or hose will be rigidly 
attached to the enclosure. 

Adjustments 

!

 WARNING: 

Risk of 

electrical shock. 

To avoid 

the risk of electrical shock, 
disconnect the power 
supply before making any 
adjustments to avoid 
possible electrical shock. 

 

Product Selection Chart

 

Product 
Number 

Range 

F (

C) 

Differential 
F

 (C

Maximum Allowable 
Temp 

F (

C) 

Capillary Length 
Ft. (m) 

Bulb Size 

Bulb Well 
(if required) 

A19ANC-1 

0 to 150 
(-18 to 66) 


(2.8) 

190 
(88) 

10 
(3) 

0.290 x 2 ½” 

WEL11A-601R 

A19ANC-2 

100 to 250 
(38 to 121) 


(3.3) 

290 
(143) 

10 
(3) 

0.290 x 2 ½” 

WEL11A-601R 

A19ANC-3 

200 to 350 
(93 to 177) 


(2.8) 

390 
(199) 

10 
(3) 

0.366 x 2 ¼” 

WEL16A-601R 

A19ANF-3 

20 to 90 
(-6.7 to 32) 


(1.1) 

130 
(54) 

10 
(3) 

0.366 x 2 5/8” 

WEL16A-601R 

A19APC-1 

20 to 90 
(-6.7 to 32) 

3.5 to 14 
(1.9 to 7.8) 

140 
(60) 


(1.8) 

0.375 x 5” 

WEL14A-603R 

 

Содержание A19ANF

Страница 1: ...mostats have an enclosed SPDT switch The red terminal is common Fig 1 Interior of an A19ANC thermostat Red Common Blue h Yellow Red to Blue Opens on Temperature Increase Red to Yellow Closes on Temperature Increase Fig 2 Designations and Switch Action The red to blue terminals open on a temperature increase See Fig 2 Simultaneously the circuit between red and yellow closes The thermostats have an ...

Страница 2: ...0 C Fig 3 Bulb well dimensions IMPORTANT Do not dent or deform the sensing bulb of this control A dent or deformation will change the calibration and cause the control to cycle at a temperature lower than the dial setting Where the capillary is exposed and subject to possible mechanical damage some means of protection should be provided The capillary outlet is designed to permit the capillary to b...

Страница 3: ... the control Turn the dial so the pointer indicates the stop setting Move the stop located behind the dial plate against the stop bracket Tighten screws to lock the stop in position High cutout stop can be set between 55F 31C above the bottom of the range and the top of the range Example The high temperature stop can be set between 255 to 350 F 124 to 277 C on a control with a range of 200 to 350 ...

Страница 4: ...act JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA www penncontrols com Johnson Controls and PENN are registered trademarks of Johnson Controls in the United States of America and or other countries All other trademarks used her...

Отзывы: