background image

TRIP SWITCH APPENDIX 

 

These products are fitted with thermal circuit breaker/power switches with indicator as a 

fail safe

 and should not be 

used to determine excessive current drawer.  

These are not an 

RCD

 and do not function in the same way.

 

 

USERS OF THESE PDU'S SHOULD PRE-DETERMINE THE MAXIMUM SAFE LOAD AS INDICATED ON THE BACK OF THE UNIT. 

 

PLEASE NOTE:

 An RCD is a safety switch that protects people from electrical shock; a circuit breaker protects the wiring 

and electrical components attached to the unit. 
 
In normal operation there will be peaks in the current draw and these switches allow for this, but will switch if the 
overload is continuous. 
 

Technical Specification 
Calibration: 

Will continuously carry 100% of rating. 

May trip between 101% and 134%,  
(they must trip at 135% of rating within one hour at +25°C 
See Chart) 

Dielectric Strength:

 1,500VAC (60 seconds). 

Insulation Resistance: 100 megohms. 

Maximum Operating Voltage:

 250VAC, 50/60 Hz. 

 
These switches have the following certification approvals:  
UL 1077 , VDE 0642/EN60934, CCC & CE compliant. 
 

 

Penn Elcom Ltd excepts no responsibility or liability for any equipment connected to this unit 

 

 

 

Отзывы: