Follow these steps:
Step 1.
Attach the left and right rack mount rails (A) to the switch, and then secure the chassis in the
rails by screwing 2 flat head Phillips screws (D) in the designated points on each side (a total of 4
screws). See the figure below. To tighten the screws, use a torque of 1.5±0.2 Nm.
Figure 25: Attaching the Rails to the Chassis
Step 2.
Install 8 cage nuts (C) in the desired 1U slots of the rack: 4 cage nuts in the non-extractable
side and 4 cage nuts in the extractable side. Note that while each rack U (unit) consists of three holes,
the cage nut should be installed vertically with its ears engaging the top and bot- tom holes only. See
the figure below.
Figure 26: Installing the Cage Nuts