Product Manual: PELAIR SERIES PORTABLE AIR CONDITIONER

 - Revision 05 - Date: 12-01-2008

Page 17

3.  Start-Up and Operation:

a.   

First:

 Turn on the unit with the power switch located between the hand cart and the backside of the air handler on 

the lower left side.

      

Second:

 Set the desired operating temperature using the hand held Temperature Controller. 

b.

   

Temperature Controller Operation:

  The Temperature Controller is an electronic low voltage (24VAC) microproc-

essor. The 8 foot long thermocouple probe extending from the top of the display enclosure is water proof but the 

enclosure itself is not. Note that a wet thermocouple will give you a false reading of the surrounding air. Place the 

thermocouple at the desired location being cooled making sure that the black end is suspended in the air and is not 

in contact with any surfaces. The controller reads the temperature at the thermocouple. The set point is the setting 

at which the compressor will turn shut down and the differential setting is the degrees from set point at which the 

controller will recycle the compressor.  This setting will also determine the compressor cycle rate.

 

Example:  If the set point is set at 70° and the differential is set at 5°, the compressor will turn shut down at 75° 

and recycle at 70 °.

 

Compressor Cycle Rate:

   During normal operation the cycle rate of the compressor should not exceed five (5) 

cycles per hour (12min) but not fewer than three (3) per hour (20min).  *

Running 

the compressor continuously can cause the evaporative coil to freeze up in 

humid conditions.

c.

   Do not repeatedly cycle the air conditioners power switch.  Proper cycling of the compressor is attained via the set-

ting of the temperature controller.  Repeated powering on and powering off of the unit can cause the system to short 

cycle and result in damage to the components.  If the air conditioner is powered off or unplugged for any reason, wait 

three (3) to four (4) minute before restarting the unit.

5.2 - Start-Up & Operating Procedures (continued)

4.  Programming The Temperature Controller:

Step 1:

  To start programming, press the 

SET

 key once to access the Fahrenheit/Celsius mode. The display will show 

either 

F

 for degrees Fahrenheit of 

C

 for degrees Celsius. Press either the up or down arrow key to toggle 

between the 

F

 or 

C

 designation.

Step 2:

  Press the 

SET

 key again to access the set point. The LCD will display the current set point and the 

S1 

annun-

ciator will be blinking to indicate that the controller is in the set point mode. Then press either the up key to 

increase or the down key to decrease the set point for the desired temperature. 

Step 3:

  Pressing the 

SET

 key again accesses the differential temperature mode. The LCD will display the current 

differential and the 

DIF1

 annunciator will be blinking. Press either the up key to increase of the down key to 

decrease the differential to the desired setting.

Step 4:

  Press the 

SET

 key again to access the cooling or heating mode. The LCD will display either 

C1

 or 

H1

.  Set 

the 

C1

 cooling mode by using either the up key or down key to toggle to the cooling mode.  Press the 

SET

 

key once more & programming is complete.

Temperature Control Lockout Switch

        

The hand held Temperature Control is provided with a lockout switch to prevent tampering by unauthorized person-

nel. When placed in the 

LOCK

 position, the keypad is disabled and no changes to the settings can be made. When 

in the 

UNLOCK

 position, the keypad will function normally.  To access the lockout switch, disconnect the power 

supply and open the controller enclosure. The switch is located on the inside of the cover. All control settings are 

retained in Nonvolatile memory. Re-programming is not necessary if power is interrupted or between usage.  

Controller Circuit Board

     

    The Controller Circuit Board is located on the bottom inside back wall of the main frame. 

Only a trained tech-

nician should service this circuit board. 

Access the board by removing the left hand lower side panel 

and/or the front lower panel. All functions of the air conditioner are monitored by the microprocessor on the circuit 

 

 

 

 

 

 

 

 

Содержание 122393-002

Страница 1: ...al PELAIR Series Portable Air Conditioners T A Pelsue Company 2500 South Tejon Street Englewood Colorado USA 80110 Tel 800 525 8460 or 303 936 7432 Fax 303 934 5581 Internet www pelsue com Email sales pelsue com ISO 9001 Certified ...

Страница 2: ... 122420 001 Product Manual PELAIR SERIES PORTABLE AIR CONDITIONER Revision 05 Date 12 01 2008 Page 2 ...

Страница 3: ...a continuing reputation for excellence in the production of fine products for a broad spectrum of industry throughout the world Now in our second generation of family direction continued commitment to innovation and quality makes Pelsue a leading source of equipment for many types of confined spaces We specialize in safety retrieval fall arrest ventilation cable placing splicing and maintenance na...

Страница 4: ...1 Quality Policy 1 2 Pelsue Product Warranty 2 0 Introduction Product Information 7 2 1 Serial Number 3 0 Configuration Assembly 8 3 1 Decal Location 3 2 Wiring Diagram 4 0 Safety 12 4 1 Safety Alert Symbol 4 2 General Safety Information 5 0 Product Operation 14 5 1 Product Description Capabilities 5 2 Start Up Operating Procedures 5 3 Transporting 6 0 Troubleshooting 20 ...

Страница 5: ...er satisfaction is one of the differentiators that sets you apart from the pack and yields a competitive advantage Therefore we will support total customer satisfaction by implementing the ISO 9001 Quality System and providing the necessary atmosphere and training to nurture this concept throughout our organization We will make every business decisionas though the quality of the part or service pr...

Страница 6: ...ll not be covered by this warranty Unless otherwise agreed the T A Pelsue Company shall repair or replace the defective components within 30 calendar days of notice of failure T A Pelsue Company s obligation hereunder shall be limited to the repair or replacement of the product or component as set forth above and shall not include any liability whatsoever for damages caused by such failure includi...

Страница 7: ...ODEL PELAIR15V B 1 0F 1 04 O Portable Drawings Portable 122910 SLDDRW N A N A 05 22 04 SIZE 0 010 PORTABLE THIS DOCUMENT AND THE DATA DISCLOSED HEREIN OR HEREWITH IS NOT REVISION LATEST D HAM FRACTIONS DECIMALS ANGLES 1 16 X XX 0 03 2 X XXX CHECKED RELEASED 15 ON HAND CART 11 14 17 18 ON BACk OR AIR HANDLER REVISIONS zONE REV DESCRIPTION DATE ALL 00 ISSUED FOR FABRICATION 03 29 05 D ALL 01 ITEM 17...

Страница 8: ... PELAIR15V 122421 002 Model PELAIR30V 122393 002 Replacement Parts Identification Table Refer to Figure 3 0 3 1a and 3 1b Item Part Number Number Description 1 122334 002 Sub Assembly 2 Wheel Hand Cart 2 120951 001 Air Filter Element Fiberglass w Chipboard Frame 11 3 4 x 11 3 4 x 3 4 3 120951 002 Air Filter Element Fiberglass w Chipboard Frame 16 x 25 x 1 4 122423 001 PELAIR15V Power Cord Assembly...

Страница 9: ...LATED PURCHASED 8 6 100604 010 REVISIONS zONE REV DESCRIPTION DATE B Y ALL 00 ISSUED FOR FABRICATION 03 29 05 D HAM ALL 01 ITEM 17 WAS ITEM 21 QTY 1 WAS 2 SHOWED BRADLEY LOOP COMPRESSOR SUPPORT DELETED ITEM 12 13 18 19 20 RESTRUCTURED PART S AND B O M 09 20 05 D HAM ALL 02 MODELED IN SOLIDWORkS UPDATED DRAWINGS AND B O M 11 07 08 A CHAU SIDE VIEW SCALE 1 6 BACk VIEW SCALE 1 6 Table 3 1a Pelair Ser...

Страница 10: ...EJON STREET ONE WITHOUT THE PERMISSION OF THE T A PELSUE COMPANY 122419 O Portable Drawings PORTABLE N A D CHAU 120VAC 60HZ POWER INPUT SCALE D HAM REVISON 02 01 05 DO NOT SCALE DRAWING THIS DOCUMENT AND THE DATA DISCLOSED HEREIN OR HEREWITH IS NOT 0 010 TOLERANCES ARE UNLESS OTHERWISE SPECIFIED 122419 001 N A N A ENG FRACTIONS DECIMALS ANGLES 1 16 X XX 0 03 2 X XXX CHECKED DUKE ZONE REV DESCRIPTI...

Страница 11: ... 122420 001 Product Manual PELAIR SERIES PORTABLE AIR CONDITIONER Revision 05 Date 12 01 2008 Page 11 Figure 3 2b PELAIR30V Wiring Diagram 220VAC 60Hz 3 2 Wiring Diagram continued ...

Страница 12: ...round electricity This manual will take you step by step through the workings and capabilities of the PELAIR Portable Air Con ditioner and will alert you to all good safety and operating practices while using the system Remember you are the key to safety Good safety practices not only protect you but also the people around you Make these practices a working part of your safety program Do not risk ...

Страница 13: ... through a GFCI equipped receptacle or circuit breaker rated at 20 Amps and dedicated for the use of the air conditioner only 6 When used as ventilation for manholes confined spaces take precautions to keep ventilation hoses and extension cords out of the walkways in order to eliminate tripping hazards and the possibility of them becoming dislodged for the air conditioner unit 7 Prior to operation...

Страница 14: ...cifications Performance 5 1 Product Description Capabilities The following section will address the capabilities and the general operation of the Pelsue PELAIR Portable Air Condi tioner The instructions contained within this section should be adhered to each and every time the product is used Any person tasked with installing or operating this piece of equipment should be familiar with these proce...

Страница 15: ...ing use The Pre Operation Visual Inspection is not limited to but must include the following items a Check that the grille on the outlet panel is present and free from obstructions b Remove any objects around the immediate area that could be sucked onto the inlet panel or the lower portion of the left hand panel where the compressor cooling fan is located c Ensure that electrical components such a...

Страница 16: ...the intake grille by placing the hose adapter lip over the top edge of the intake grille and then securing the adapter bottom to the inlet grill utilizing the two draw latches on the adapter plate Place the intake hose end with the buckle over the adapter ring and cinch the strap around the inlet ring The free end of the intake hose can then be placed in the shelter preferably at ground level and ...

Страница 17: ...restarting the unit 5 2 Start Up Operating Procedures continued 4 Programming The Temperature Controller Step 1 To start programming press the SET key once to access the Fahrenheit Celsius mode The display will show either F for degrees Fahrenheit of C for degrees Celsius Press either the up or down arrow key to toggle between the F or C designation Step 2 Press the SET key again to access the set...

Страница 18: ...Shut Down Codes Operational errors are reported by the flashing light in the Power Switch and in the Control Status LED The flashes are approximately 1 2 second per flash and are followed by a 4 second pause between error flash cycles Freeze Stat 1 flash High Pressure Switch 2 flashes Low Pressure Switch 3 flashes Blower Blower Fuse 4 flashes Condenser Fan 1 Relay Fuse 5 flashes Condenser Fan 2 Re...

Страница 19: ...ds on the round hand rails at the curve Place on foot on the footrest down by the axle and pull back until the weight of the air conditioner is balanced on the wheels The unit can now be rolled forward or backwards Note it is best to pull the unit over any large obstacles There is a grab handle at the front of the unit for lifting over obstructions Always try to keep the air conditioner in the ver...

Страница 20: ...feel cold enough in cool mode A Thermostat set incorrectly A Reset temp Control See Section 5 2 Steps 1 4 B Intake outlet hose ends to close to one another B Move hoses further apart C Air intake is blocked C Clear intake vent replace filter D Condenser coil filter is clogged D Replace filter 3 Compressor turns on and off rapidly A Outside Temperature is extremely hot A Shade the unit B Extension ...

Страница 21: ... 122420 001 Product Manual PELAIR SERIES PORTABLE AIR CONDITIONER Revision 05 Date 12 01 2008 Page 21 NOTES ...

Страница 22: ... 122420 001 Product Manual PELAIR SERIES PORTABLE AIR CONDITIONER Revision 05 Date 12 01 2008 Page 22 NOTES ...

Страница 23: ... 122420 001 Product Manual PELAIR SERIES PORTABLE AIR CONDITIONER Revision 05 Date 12 01 2008 Page 23 ...

Страница 24: ...ISO 9001 Certified T A Pelsue Company 2500 South Tejon Street Englewood Colorado USA 80110 Toll free 800 525 8460 or 303 936 7432 Fax 303 934 5581 Internet www pelsue com Email sales pelsue com ...

Отзывы: