Pelican PM5-277 Скачать руководство пользователя страница 1

2

277VAC

Neutral

Wireless Control Module

 a 

wall mounted antenna to be 

placed in a location which can 

easily transmit and receive 

wireless signals.

Power Relay 

Module

 mounted and installed in a high voltage rated 

electrical box. Schedulable relays for switching On/Off 

electrical loads.

Installation Guide

1. Power Relay Module Installation

    CONTAINS FCC ID  

OA3MRF24J40MA

System Components

The power relay module can either be mounted inside an electrical sub panel with circuit breakers or 

in its own dedicated electrical box. Mounting tabs are provided on each end of the module. The 

module should be securely fastened to the inside of the electrical box using the mounting tabs and 

screws. Each relay on the module has a green light to indicate when it is active. There is also a 

single green status light located next to the low voltage terminal block indicating the status of 

communications with the wireless module.

Connect the 277VAC power wires between 

“L” and “N”. The input power is reduced to 

24VAC to provide isolated power to the relay 

control circuit and the wireless control 

module. A built-in auto-reset fuse limits 

current to 0.3 Amps to provide short circuit 

protection for the control interface.

3

1

Diagram 1

1 Power Options

There are (5) sets of relay connections.  

Each connection is independent and can 

operate at different voltages and currents. 

The dry contacts are rated to 

120VAC@15AMPS and 240/277VAC 

@10AMPS.  Each relay operates as a 

mechanical on/off switch and is intended to 

control the LINE side of the circuit.

The module is powered by 277VAC.

3 Control Interface

WARNING

!

DO NOT USE THE 24VAC OUTPUT 

TO POWER ANY OTHER DEVICES.

There are (8) screw terminals on the relay 

module. The terminals labeled R, C, and D 

are used to connect the relay module to the 

wireless control module. 18 to 24 gauge 

wire is recommended for this connection. 

Terminal functions are as followed: D – 

Data/Communication,  R – 24VAC supply 

power, C – Common Wire (Diagram 2).

W

POWER CONTROL MODULE / PM5-277

2 Dry Contact Relays

Failure to follow these instructions can damage 

the product or cause a hazardous condition. 

Disconnect power during the installation of this 

product. All wiring must conform to local codes 

and ordinances. We strongly recommend that any 

installation or servicing be performed by a 

qualified individual.

Relay 5

10AMP @ 277VAC

15AMP @ 120VAC

Relay 4

10AMP @ 277VAC

15AMP @ 120VAC

Relay 3

10AMP @ 277VAC

15AMP @ 120VAC

Relay 2

10AMP @ 277VAC

15AMP @ 120VAC

Relay 1

10AMP @ 277VAC

15AMP @ 120VAC

IND. CONT. EQ

5AB5

!

!

Содержание PM5-277

Страница 1: ...o provide short circuit protection for the control interface 3 1 Diagram 1 1 Power Options There are 5 sets of relay connections Each connection is independent and can operate at different voltages and currents The dry contacts are rated to 120VAC 15AMPS and 240 277VAC 10AMPS Each relay operates as a mechanical on off switch and is intended to control the LINE side of the circuit The module is pow...

Страница 2: ...minals to the same designated low voltage terminals on the Power Relay Module The Wireless Control Module s terminals are spring cage connected The wires should first be stripped to expose 1 4 of wire Each terminal has a release slot and a round hole Insert the exposed wire end into the round hole and it will be held in place by the internal spring cage To remove an already inserted wire use a sma...

Страница 3: ... relay will change between On and Off These manual inputs operate at 24VAC with very low current The pushbutton switches can be located up to 500 feet from the Power Relay Module 18 to 24 gauge wire should be used for these connections Optional Manual Override Function Momentary Switch In this configuration pressing the momentary switch will switch the dry contact relay labeled Y There is a LED li...

Страница 4: ...Please Visit www pelicanwireless com Power Control Module relays can be synchronized with the operation of your Pelican Thermostats For example a pump valve boiler cooling tower and or chiller connected to a relay can be energized based on actual thermostat demand For integration assistance please contact Pelican Technical Support by calling 888 512 0490 or email support pelicanwireless com Advanc...