ECP300 EXPERT
Pag. 30
USE AND MAINTENANCE MANUAL
Rev. 01-12
SWITCHING ON ECP300 EXPERT PANEL
After wiring the electronic controller correctly, power up at 400 V AC; the display panel will
immediately emit a beep and all the LEDs will come on simultaneously for a few seconds.
COMPRESSOR ACTIVATION/DEACTIVATION CONDITIONS
The
ECP300 EXPERT
controller activates the compressor when cold room temperature
exceeds differential (r0); it deactivates the compressor when cold room temperature is
lower than the setting.
Nel caso venga selezionata la funzione Pump-down fare riferimento al capitolo 5.14 per le
condizioni di attivazione/disattivazione compressore.
MANUAL DEFROSTING
To defrost just press the dedicated key (see section 5.2) to activate the elements relay.
Defrosting will not take place if the end-of-defrost temperature setting (d2) is lower than the
temperature detected by the evaporator sensor. Defrosting ends when the end-of-defrost
temperature (d2) or maximum defrost time (d3) is reached.
5.11
5.12
5.13
CHAP. 5 - Data programming