ECP200 BASE 2/4
Page
15
USE AND MAINTENANCE MANUAL
Rev. 01-09
LIST OF LEVEL 1 VARIABLES (User level)
VARIABLES
MEANING
VALUE
DEFAULT
r0
Temperature difference
compared to main SETPOINT
0.2 - 10 °C
2°C
d0
Defrost interval
(hours)
0 - 24 hours
4 hours
d2
End-of-defrost setpoint
.
Defrost is not executed if the temperature read by the
defrost sensor is greater than
d2
(If the sensor is faulty defrosting is timed)
-35 - 45 °C
15°C
d3
Max defrost duration
(minutes)
1 - 60 min
25 min
d7
Drip duration
(minutes)
At the end of defrost the compressor and fans remain at
standstill for time
d7
, the defrost LED on the front panel
flashes.
0 - 10 min
0 min
F5
Fan pause
after defrost (minutes)
Allows fans to be kept at standstill for a time
F5
after
dripping. This time begins at the end of dripping. If no
dripping has been set the fan pause starts directly at the end
of defrost.
0 - 10 min
0 min
A1
Minimum temperature alarm
Allows user to define a minimum temperature for the room
being refrigerated. Below value
A1
an alarm trips: the alarm
LED flashes, displayed temperature flashes and the buzzer
sounds to indicate the problem.
- -45°C
A2
Maximum temperature alarm
Allows user to define a maximum temperature for the room
being refrigerated. Above value
A2
an alarm trips: the alarm
LED flashes, displayed temperature flashes and the buzzer
sounds to indicate the problem.
- +45°C
tEu
Evaporator sensor temperature display
Displays
evaporator
temperature
(displays nothing
if dE =1)
read only
5.8
CHAP. 5 - Parameter programming