PeerlessBoilers WBV-03-060 Скачать руководство пользователя страница 20

18

MAINTENANCE

A. GENERAL

1. Check pipes adjacent to cold walls or in unheated

spaces. Insulate and tape them if necessary to be
sure they can't freeze up. Keeping the water moving
at all times will reduce the likelihood of freezing.

2. If there is considerable foreign matter in the boiler

water, the boiler should be shut down and allowed to
cool, then drained and thoroughly flushed out. Drain
the boiler at the drain cock. Pipe the drain cock to a
suitable drain or containment device (if antifreeze is
used). Flush the system to remove remaining matter.
If there is evidence that hard scale has formed on the
internal surfaces, the boiler should be cleaned by
chemical means as prescribed by a qualified water
treatment specialist.

3. There must be no signs of continuous wetness at the

chimney. If signs of continuous wetness are
observed, a qualified service agency must be
consulted to modify the vent configuration to prevent
the formation of condensate, which may damage the
vent pipe.

B. DAILY MAINTENANCE (WITH BOILER

OPERATING)

Daily boiler observation can be performed by the owner.
If any potential problems are found, a qualified installer
or service technician/agency must be notified.

1. Remove any combustible materials, gasoline and

other flammable liquids and substances that generate
flammable vapors from the area where the boiler is
contained. Make certain that the boiler area has
ample air for combustion and ventilation and that
there are no obstructions to the free flow of air to
and from the boiler.

2. Observe general boiler conditions (unusual noises,

vibrations, etc.)

3. Observe operating temperature and/or pressure

gauge on the boiler. Boiler pressure should never be
higher than 5 psi below the rating shown on the
safety relief valve. The valve rating can be found on
the top of the safety relief valve. Boiler temperature
should never be higher than 250°F.

4. Check for water leaks in boiler and system piping.

C. WEEKLY MAINTENANCE (WITH BOILER

OPERATING)

1. Flush float-type low-water cut-off (if used) to remove

sediment from the float bowl as stated in the
manufacturer's instructions.

D. MAINTENANCE OF SAFETY RELIEF

VALVE

1. Check function and maintain safety relief valve as

specified by manufacturer, typically every other
month or every month, per the instructions on the
tag on the safety relief valve.

E. MONTHLY MAINTENANCE (WITH BOILER

OPERATING)

1. Check boiler room floor drains for proper

functioning.

2. Test probe type low-water cut-off (if used) by using

the Push-to-Test Button.

3. Test limit by lowering the limit set point until the

burner shuts down. When proper operation is
confirmed, return the set point to original setting.

4. Follow additional instructions in the Burner Manual

for proving the burner component operation.

F.

MAINTENANCE – ANNUAL

TO CLEAN:

1. Remove top jacket panel and flue collector cover

plate, Item 11 (Figure 2.1).

2. To thoroughly clean the boiler it must be brushed

down from the top. The target wall is made of a soft
ceramic fiber. Care must be taken not to damage this
material during cleaning.

3. Remove any scale or soot from the combustion

chamber area by vacuum cleaning or any other
available means.

Do not use this appliance if any part has been under
water. Improper or dangerous operation may result.
Immediately call a qualified service technician to
inspect the boiler and to replace any part of the
control system and any control which has been
under water.

WARNING

Entire heating system, including boiler, burner and
venting system, must be inspected at least once a
year by a qualified heating professional. Boiler is to
be cleaned at least once a year.

NOTICE

Burner mounting plate must be opened gain access
to combustion chamber for the removal of dirt and
debris.

NOTICE

Disconnect all power to the burner before accessing
combustion chamber.

WARNING

Содержание WBV-03-060

Страница 1: ...WV Boilers Series Oil Installation Operation Maintenance Manual As an ENERGY STAR Partner PB Heat LLC has determined that this product meets the ENERGY STAR guidelines for energy efficiency Plastic Ja...

Страница 2: ...COVERPLATE 9 G CONTROLS 9 4 BURNER SETUP BOILER OPERATION 11 A BURNER INSTALLATION 11 B BURNER START UP AND ADJUSTMENT 11 C CHECK BOILER CONTROLS 11 D PURGE AIR FROM THE SYSTEM WATER BOILERS ONLY 12 5...

Страница 3: ...is equipped with an override which is provided primarily to permit the use of an external energy management system that serves the same function THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF T...

Страница 4: ...is boiler must be installed by a qualified contractor The boiler warranty can be voided if the boiler is not installed maintained and serviced correctly Figure 1 1 Appliance Installation Clearances Th...

Страница 5: ...system and installation must be in accordance with the current edition of the American National Standard ANSI NFPA 211 Chimneys Fireplaces Vents and Solid Fuel Burning Appliances or applicable provisi...

Страница 6: ...ler system operation in general You can also use this survey to locate system problems which will have to be corrected To obtain copies of these Surveys contact your PB Heat representative or download...

Страница 7: ...e installed as a rear flue outlet unit or a top flue outlet unit Packaged WBV 03 and WBV 04 boiler models are shipped as rear flue outlet and may be converted The WV 05 boiler model is only available...

Страница 8: ...er forced circulation However there is no minimum water flow rate for this boiler B SYSTEM COMPONENTS Figure 3 1 shows the symbol key for the piping diagrams in this section The following are brief de...

Страница 9: ...he boiler pressure relief valve is shipped separately for field installation On the WBV WV boiler this can be piped into the connection provided next to the boiler supply outlet connection or alternat...

Страница 10: ...8 WATER PIPING Figure 3 3 Recommended Water Piping...

Страница 11: ...he cooling coil in the airstream F TANKLESS HEATER OR COVERPLATE 1 If a tankless coil is used item 9 install as pictured On water boilers install in opening in front section 2 If not using a tankless...

Страница 12: ...10 Figure 3 7 Tankless Coil Piping Water Boiler WATER PIPING Figure 3 6 WBV WV Piped with a Chiller...

Страница 13: ...down the thermostat and moving the main boiler service switch to the off position 4 See burner manufacturer s manual for further information regarding the burner C CHECK BOILER CONTROLS 1 Limit and O...

Страница 14: ...purging Pumps will hold air in the eye of the impeller 2 Allow the system to reach 180 F and use manual vents if installed to remove any remaining air Watch the pressure gauge as the system approaches...

Страница 15: ...BURNER SPECIFICATIONS Boiler Model No Burner Model No Burner Series Nozzle Size Pump Pressure Start Up Settings Turbulator Air Damper WBV 03 060 F3 Series 40 0 50 90 B 145 PSI 0 0 2 9 WBV 03 085 F5 S...

Страница 16: ...ective devices shall not be wired in a grounded line B WIRING 1 See Section 4 for mounting burner 2 For complete information on servicing and adjustment of controls refer to the attached control speci...

Страница 17: ...15 ELECTRICAL Figure 4 1 Water Boilers Beckett 7600A Limit Control Figure 4 1a Beckett AquaSmart 7600A Limit Control Wiring Details...

Страница 18: ...16 Figure 4 2 Water Boilers Hydrolevel 3250 Limit Control ELECTRICAL Figure 4 2a Hydrolevel HydroStat 3250 Limit Control Wiring Details...

Страница 19: ...de adequate ventilation Wear a NIOSH MSHA approved respirator Wear long sleeved loose fitting clothing and gloves to prevent skin contact Wear eye goggles Minimize airborne dust prior to handling and...

Страница 20: ...fety relief valve Boiler temperature should never be higher than 250 F 4 Check for water leaks in boiler and system piping C WEEKLY MAINTENANCE WITH BOILER OPERATING 1 Flush float type low water cut o...

Страница 21: ...n the city water inlet valve to assure required system pressure usually about 12 psi Close the inlet valve if it is necessary to open the inlet water valve frequently a substantial leak may be the cau...

Страница 22: ...oiler Dimensions Water Boiler Boiler Model Number Jacket Depth A Jacket Width B Jacket Height C Rear of Jacket to c l of Vent D Vent Size Diameter E WBV 03 085 110 18 3 8 23 5 8 39 1 4 7 6 WBV 04 125...

Страница 23: ...ating Capacity and Annual Fuel Utilization Efficiency AFUE ratings are based on U S Government tests with 13 CO2 and 0 02 w c draft over fire Before purchasing this appliance read important informatio...

Страница 24: ...arts are available from your local PB Heat LLC distributor or from Parts To Your Door at 1 610 916 5380 www partstoyourdoor com Note Remember to include the boiler model number and serial number when...

Страница 25: ...less Coil WV 05 Water 90534 10 Flue Collector Plate Blanket Seal 90999 11 Flue Collector Cover Plate WBV 03 90565 Flue Collector Cover Plate WBV 04 90566 11A Top Outlet Flue Collector Plate WV 05 9056...

Страница 26: ...Operation Maintenance Manual TO THE INSTALLER This manual is the property of the owner and must be affixed near the boiler for future reference TO THE OWNER This boiler should be inspected annually by...

Отзывы: