background image

IMPORTANT SAFETY PRECAUTIONS 

 

Control assembly and the tools and lifting equipment 
used in installation are heavy and may easily cause 
personal injury if dropped or carelessly handled. The 
normal precautions and safety rules associated with the 
installation or repair of machinery, in regard to manual 
lifting, use of power equipment, and handling of tools, 
must be observed in the installation of this controller. 
 
Petroleum-base cleaning solvents are flammable. 

 

Smoking by personnel, open flame, or other activity 
which could ignite vapors in the vicinity of these solvents 
is extremely hazardous and must not be permitted. 
 
Do not work under a suspended object unless there is a 
positive support under it to stop is fall in event of sling or 
hoist failure. 
 
 
 
 
 
 

UPON RECEIPT OF CONTROL EQUIPMENT: 

Check 

carefully to see that all of the equipment has been 
received. Report immediately any shortages or damages 
to the transportation company handling the shipment, 
noting the extent of the damage or shortage on the 
freight bill and bill of lading. 
 
Do not leave the unit exposed to weather or construction 
hazards. The controller may become mechanically 
damaged. This controller is a well designed and carefully  
 
 
 
 
 
 
 
 

WARNING

 Do not work under a suspended object 

unless  there  is a positive support under it to stop its fall 
in event of sling or hoist failure. Disregard of this warning 
could result in grave personal injury.  
 

ELECTRODE HOUSING:

 If furnished in two or more 

sections, screw the 1-1/2” pipe (Electrode Housing) 
together with couplings provided. Screw the bulb 
assembly (20) (21) (22) (23) to the bottom of the 1-1/2” 
electrode Housing. Be sure to use a good pipe thread 
compound to insure a watertight connection. 
 
To protect and facilitate installation, roll the flexible bulb 
into a compact bundle about its vertical axis and  
 
 
 

4848247 

Before attempting examination, handling or repair, be 
certain that the electrical power supply is shut off. An 
electrical shock from contact with live wires or cards can 
be fatal. 
 
Before opening the conduit box of an electric motor, a 
switch cover, starter or panel door, be certain that the 
power supply is shut off. An electrical shock from contact 
with live leads can be fatal. 
 
Before attempting repairs to installation, disconnect 
power supply. Controls are automatic. This prevents 
accidental running of pump motor. Starting motor during 
repair activities could damage pump and may cause 
personal injury. 
 
 
 
 
 
 

INTRODUCTION

 
Manufactured unit. It should be given the same attention 
accorded to any precision machine. 
 
The satisfactory operation of this controller depends to a 
large extent upon proper installation. These in-structions 
cannot answer every question that may  arise as each 
installation will be different. The installer and the 
operator of this equipment must use  good judgment to 
adapt these procedures to the installation. 
 
 
 
 
 
 
 
 

INSTALLATION

temporarily encircle the roll with tape to secure. 

 

Carefully lower the Electrode Housing assembly, bulb 
first, through the opening in the cover over the basin until 
the mounting flange rests on the basin cover. Remove 
tape. 
 

MOUNTING FLANGE:

   The Sealtrode Series P Pump 

Controller is furnished with one of two styles of mounting 
flanges:  standard for mounting on metal basin covers, 
and style F for concrete mounting, both illustrated on 
page 5.  
 
The Mounting Flange (15) has been preset at the factory 
for the correct basin depth and should require no further 
adjustment. Refer to page 5 for factory settings.   

Содержание Sealtrode P Series

Страница 1: ...y does not cover parts repaired outside the Seller s factory without prior written approval Seller makes no warranty as to starting equipment electrical apparatus or other material not of its manufacture since the same are usually covered by warranties of the respective manufacturers thereof Manufacturer and may also result in bodily injury as well as property damage This book is intended to be a ...

Страница 2: ...use a good pipe thread compound to insure a watertight connection To protect and facilitate installation roll the flexible bulb into a compact bundle about its vertical axis and 4848247 2 Before attempting examination handling or repair be certain that the electrical power supply is shut off An electrical shock from contact with live wires or cards can be fatal Before opening the conduit box of an...

Страница 3: ...4 AWG wire with 600 volts rated insulation and 3 64 inch minimum insulation wall thickness to connect the letter coded wires to the indicated terminals in the control box Be sure electric current is the same as that stamped on the control box nameplate Wire per wiring diagram supplied with control panel If diagram is lost or misplaced copies may be obtained from your local Peerless Pump representa...

Страница 4: ...filled and the pumps do not cut off remove and empty the bulb and refill as outlined on page 3 under the heading Filling Flexible Bulb LOCATING TROUBLE IF THE PUMP FAILS TO START 1 Make sure sodium bicarbonate has been added to water 2 Check the electrical service making sure the current characteristics are the same as that stamped on the control box nameplate 3 Check to see if the control wiring ...

Страница 5: ...DT 4848247 5 ...

Страница 6: ...unted in enclosure for 1 phase motors only All mounted and pre wired in NEMA 1 general purpose or NEMA 4 watertight dead front enclosure 4848247 6 TYPE L and TYPE VCS PUMPS Fusible Disconnect Switch DY60FD Circuit Breaker DY60CB SERIES P DUPLEX COMBINATION SEALTRODE FLOATLESS CONTROLLER consists of A Electrode and terminal housing assembly including galvanized steel electrode housing NEMA 1 thru 4...

Страница 7: ...or High Water Alarm Contacts Alarm Annunciation by others High Water Alarm with Annunciation Silencing Relay and Push Button Red High Water Alarm Light Enclosure Mounted Y 56 A U Y 56 A Simplex 2 X Y 57 A UH Y 57 A H Simplex 3 X X Y 57 AU A Y 57 A A Simplex 3 X Y 57 AU D Y 57 A D Duplex 3 X X Y 57 AU DH Y 57A DH Duplex 4 X X Y 57 AU DA Y 57 A DA Duplex 4 X Y 58 AU Y 58 A Duplex 3 X X Y 58 AU H Y 5...

Страница 8: ...over Slotted Screw Upper Gasket 3 4 Pipe Plug 3 4 Tee 3 4 Nipple Ground Terminal Compression Fitting Phillips Head Screw Lower Gasket O Ring Reducer Coupling Compression Set Screw Sq Hd Mounting Flange Gasket Mtg Flg Electrode Hsg Suspension Wires Electrodes Bulb Adapter Hose Clamp Band Protector Bulb Housing Body Vent Cap 27 These parts make up the Terminal Housing 4848247 Rev 2 2 05 ...

Отзывы: