AcTIVATION Of ThE LOAD ON AuTOMATIc MODE:
uSER PROGRAMMING:

Push the button 

 and keep it depressed until the display shows 

MINIMUM     COS-FI
0.70@ 

with the buttons 

 and 

 set the cos-fi value so that below this parameter the load 

will be disabled for dry running; 

i.e. Enable the motor output on manual mode, make the load turn with no load (dry run-

ning) read the cos-fi data detected (i.e. 0.65) And enter the value with an additional 0.05 on 

the screen  previously displayed

MINIMUM     COS-FI
0.70@ 

Push the 

 button and on the display the 

MAXIMUM CURRENT
5.0A             

, appears, with the 

 and 

 buttons set the value of the current so that if this parameter is exceeded 

the load will be disabled for overcurrent; 

i.e. Enable motor output on manual mode, read the data of the current with load detected 

(i.e. 5.0A) (see that it matches with the data on the motor plate) and enter the value with an 

additional 10-15%, on the screen previously displayed

MAXIMUM CURRENT 
5.7A            

Push the 

 button and 

  RESET    N. 1       
  TIME       5 MIN 

, is displayed with the 

 and 

 buttons set the reset time that allows the system to restart automatically after being 

stopped for the first time by the dry running motor alarm; 

Push the 

 button and   

  RESET    N. 2       
  TIME       10 MIN 

, is displayed with the 

 and 

 buttons set the reset time that allows the system to restart automatically after being 

stopped for the second consecutive time by the dry running motor alarm; 

Push the 

 button and   

  RESET    N. 3       
  TIME       15 MIN 

, is displayed with the 

 and 

 buttons set the reset time that allows the system to restart automatically after being 

stopped for the third consecutive time by the dry running motor alarm; 

Содержание EVOLUTION Mono

Страница 1: ...erona Italy Tel 39 045 6136311 Fax 39 045 7614663 e mail sales pedrollo com www pedrollo com MADE IN ITALY EVOLUTION Quadro elettrico per un motore con controllo del cos Control panel with cos control...

Страница 2: ...haracteristics Pag 6 5 Installation Pag 6 6 Front panel Pag 7 7 Functions and programming Pag 8 8 Alarms Pag 11 9 EVOLUTION SINGLE PHASE wiring diagrams Pag 12 10 EVOLUTION THREE PHASE wiring diagrams...

Страница 3: ...f death and to indica te an hazardous situation which may result in severe injuries or damage of goods Caution is required WARNING The instructions provided with this sign must be followed to avoid ma...

Страница 4: ...applications that are not listed below please contact our after sales service Should you need to get in touch with our technical service or to order spare parts please speci fy the identification cod...

Страница 5: ...ION electrical panel is to be cleaned and stored in a safe place away from weather hazards and from accidental risk of falling if it is to be kept out of service for a long period DANGER Do not use wa...

Страница 6: ...ut com no nc resistive load Main switch interlocking door Running capacitor can be added optional Enclosure in ABS IP55 Ambient temperature 5 40 C Relative humidity 50 at 40 C not condensed 5 Installa...

Страница 7: ...ont panel electric pump EVOLUTION 1 v 1 0 Multifunction visualization and programming display Green led for load activated Multifunction pushbutton Arrow up pushbutton Arrow down pushbutton Ok pushbut...

Страница 8: ...power supply voltage detected 0 0A corrent absorbed by the load connected 1 0 power factor cos fi of the load connected Man EVOLUTION on manual mode Aut EVOLUTION on automatic mode LOAD ACTIVATION ON...

Страница 9: ...utput on manual mode read the data of the current with load detected i e 5 0A see that it matches with the data on the motor plate and enter the value with an additional 10 15 on the screen previously...

Страница 10: ...ndless cyclical restart the drytek dry running protection system enables restart according to the pro gramming time set an resets the restarting cycels each time that the system detects the presence o...

Страница 11: ...LOW The voltage of the electrical power system detected is too low The display flashes and the alarm output is enabled clean nc c na contacts The system is to be reset manually by pushing the pushbut...

Страница 12: ...10 EVOLUTION SINGLE PHASE wiring diagrams...

Страница 13: ...11 EVOLUTION THREE PHASE wiring diagrams...

Страница 14: ...ns by personnel in charge Incidental causes acts of God i e fires flooding water or lightening Faulty products must be returned free of charge to PEDROLLO S p A who reserves the indi sputable opinion...

Страница 15: ...with the provisions of the community directives and relevant modifications Machinery 98 37 EEC European Directive 2006 95 EC Electromagnetic compatibility 89 336 EEC and following modifications and c...

Отзывы: