22
AcTIVATION Of ThE LOAD ON AuTOMATIc MODE:
uSER PROGRAMMING:
Push the button
and keep it depressed until the display shows
MINIMUM COS-FI
0.70@
with the buttons
and
set the cos-fi value so that below this parameter the load
will be disabled for dry running;
i.e. Enable the motor output on manual mode, make the load turn with no load (dry run-
ning) read the cos-fi data detected (i.e. 0.65) And enter the value with an additional 0.05 on
the screen previously displayed
MINIMUM COS-FI
0.70@
Push the
button and on the display the
MAXIMUM CURRENT
5.0A
, appears, with the
and
buttons set the value of the current so that if this parameter is exceeded
the load will be disabled for overcurrent;
i.e. Enable motor output on manual mode, read the data of the current with load detected
(i.e. 5.0A) (see that it matches with the data on the motor plate) and enter the value with an
additional 10-15%, on the screen previously displayed
MAXIMUM CURRENT
5.7A
Push the
button and
RESET N. 1
TIME 5 MIN
, is displayed with the
and
buttons set the reset time that allows the system to restart automatically after being
stopped for the first time by the dry running motor alarm;
Push the
button and
RESET N. 2
TIME 10 MIN
, is displayed with the
and
buttons set the reset time that allows the system to restart automatically after being
stopped for the second consecutive time by the dry running motor alarm;
Push the
button and
RESET N. 3
TIME 15 MIN
, is displayed with the
and
buttons set the reset time that allows the system to restart automatically after being
stopped for the third consecutive time by the dry running motor alarm;