Automation & Controls
Division of PECO, Inc.
Portland, OR 97282
800-874-8547
or
503-233-6401
www.pecomanufacturing.com
Performance PRO
™
T8000 Series
T8000
Series
Gas
Electric
Oil
Heat Pump
Technical Data
Specifications
Temperature Control Range
50° to 90° F (10° to 32° C)
Operating Temperature Range
0° to 120° F (-18° to 49° C)
Storage Temperature Range
-20° to 130° F (-29° to 55° C)
Electrical Input Frequency
50/60 Hz +/- 10%
Input Power
24 V
AC
(20-30 V
AC)
and/or
2 AA alkaline
batteries
(Installing batteries recommended)
Output Terminal W - Heating
20-30 V
AC
0.02-1.0 A
Output Terminal Y - Cooling
20-30 V
AC
0.02-1.0 A
Output Terminal G - Fan
20-30 V
AC
0.02-0.6 A
Output Terminal A - Economizer
20-30 V
AC
0.02-1.0 A
Dehumidifi cation Sensor
0 - 100% RH
Dehumidifi cation Range
25% - 99% RH
Termination Connections
Wallplate w/ terminal blocks
Memory Card
SD (Secure Digital)
Specifications
Total load not to exceed 2.5 A
Mounting
Direct mount; 2" x 4" horizontal
or vertical, or 4" x 4"
LCD Viewable Size
8 inch2 - 2.5" W x 3.2" H
51.8 cm2 - 6.4 cm W x 8.1 cm H
Physical Dimensions
5.7”W x 4.3"H x 1.3"D
Dimensions
Model
Part No. Description
T8532-IAQ
70337
Performance PRO 3 Heat/2
Cool staging, programmable w/
Humidifi cation/Dehumidifi cation
control
T8532-001
69922
Performance PRO 3 Heat / 2
Cool staging, programmable.
T8522-001
70333
Performance PRO 2 Heat
/2 Cool staging, programmable.
70271
70271
Wallplate. Performance PRO
common wallplate: applicable to
all series models.
69308
69308
Indoor remote sensor
70327
70327
Outdoor remote sensor
SB200-001
68375
Occupancy sensor - time based
SK200-001
68381
Occupancy sensor - guest room
CONVENTIONAL
HEAT PUMP B/O AUX
C W1 W2 G A E Y1 Y2 RH RC SC S1 S2 S3
CONVENTIONAL
HEAT PUMP B/O AUX
C W1 W2 G A E Y1 Y2 RH RC SC S1 S2 S3
Performance PRO Wallplate
& Terminal Connections
DS-T8000 - 9/10 © PECO, Inc. 2010
Models & Accessories
Terminals
Conventional
Heat Pump
C
W2
G
E
Unswitched side 24 V
AC
Stage 2 Heat
Fan Relay
Stage 1 Heat
Stage 3 Heat
Sensor Common
W1
A
SC
Unswitched side 24 V
AC
RC
Power to Cooling switched side
Power to Cooling switched side
Y2
Stage 2 Cool or Dehumidify
Compressor Stage 2
Heat / Cool or Dehumidify
Y1
Stage 1 Cool
Compressor Stage 1
Heat / Cool
Indoor remote sensor
S1
Indoor remote sensor
Setback input
S2
Setback input
Emergency
Sensor Common
RH
Power to Heating switched side
Power to Heating switched side
Fan Relay
Outside remote sensor
S3
Outside remote sensor
Economizer, Damper Control
or Humidify
B/O
AUX
Reversing valve
Auxiliary (Stage 3 Heat)
Economizer, Damper Control
or Humidify
4.3”
(10.9
cm
)
5.7”
(14.5
cm
)
1.3”
(3.3
cm
)
Memory
Card
T8000 Thermostat
RoHS
Compliant