Technical Data

Specifications

Temperature Control Range

50° to 90° F  (10° to 32° C)

Operating Temperature Range

0° to 120° F  (-18° to 49° C)

Storage Temperature Range

-20° to 130° F  (-29° to 55° C)

Electrical Input Frequency

50/60 Hz +/- 10%

Input Power

24 V

AC

 (20-30 V

AC)

 

and/or

 2 AA alkaline 

batteries 

(Installing batteries recommended)

Output Terminal W - Heating

20-30 V

AC

  0.02-1.0 A

Output Terminal Y - Cooling

20-30 V

AC

  0.02-1.0 A

Output Terminal G - Fan

20-30 V

AC

  0.02-0.6 A

Output Terminal A - Economizer

20-30 V

AC

  0.02-1.0 A

Dehumidifi cation Sensor

0 - 100% RH

Dehumidifi cation Range

25%  - 99% RH

Termination Connections

Wallplate w/ terminal blocks

Memory Card

SD (Secure Digital)

Specifications

Total load not to exceed 2.5 A

Mounting

Direct mount; 2" x 4" horizontal 
or vertical, or 4" x 4"

LCD Viewable Size

8 inch2  -  2.5" W x 3.2" H
51.8 cm2  - 6.4 cm W x 8.1 cm H

Physical Dimensions

5.7”W x 4.3"H x 1.3"D

Dimensions

Model

Part No. Description

T8532-IAQ

70337

Performance PRO 3 Heat/2 

Cool staging, programmable w/ 

Humidifi cation/Dehumidifi cation 

control

T8532-001

69922

Performance PRO 3 Heat / 2 

Cool staging, programmable.

T8522-001

70333

Performance PRO 2 Heat

/2 Cool staging, programmable.

70271 

70271

Wallplate. Performance PRO 

common wallplate: applicable to 

all series models.

69308

69308

Indoor remote sensor

70327

70327

Outdoor remote sensor

SB200-001

68375

Occupancy sensor - time based

SK200-001

68381

Occupancy sensor - guest room

CONVENTIONAL

        HEAT PUMP             B/O  AUX

C   W1  W2  G      A    E   Y1  Y2  RH   RC  SC  S1   S2  S3

CONVENTIONAL

       HEAT PUMP             B/O  AUX

C   W1  W2  G      A    E   Y1  Y2  RH   RC  SC  S1   S2  S3

Performance PRO Wallplate 

& Terminal Connections

DS-T8000 - 9/10  © PECO, Inc.  2010

Models  &  Accessories

Terminals

Conventional

Heat Pump

C

W2

G

E

Unswitched side 24 V

AC

Stage 2 Heat

Fan Relay

Stage 1 Heat

Stage 3 Heat

Sensor Common

W1

A

SC

Unswitched side 24 V

AC

RC

Power to Cooling switched side

Power to Cooling switched side

Y2

Stage 2 Cool or Dehumidify

Compressor Stage 2

Heat / Cool or Dehumidify

Y1

Stage 1 Cool

Compressor Stage 1 

Heat / Cool 

Indoor remote sensor

S1

Indoor remote sensor

Setback input

S2

Setback input

Emergency

Sensor Common

RH

Power to Heating switched side

Power to Heating switched side

Fan Relay

Outside remote sensor

S3

Outside remote sensor

Economizer, Damper Control

or Humidify

B/O

AUX

Reversing valve

Auxiliary (Stage 3 Heat)

Economizer, Damper Control

or Humidify

4.3”

(10.9 

cm

)

5.7”

(14.5 

cm

)

1.3”

(3.3 

cm

)

Memory

Card

T8000 Thermostat

RoHS

 Compliant