PEAK® IOM57 Input/Output Modules Installation Instructions
19
Technical specifications
Y65T31-0
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount, 8 in.
Primary Leads and Secondary Screw Terminals, Class 2
Note:
Additional Y6x-x Series transformers are also available. Refer to the
Series Y63,Y64, Y65, Y66, and Y69 Transformers Product Bulletin (LIT-125755)
for more
information.
AS-XFR050-0
Power transformer (Class 2, 24 VAC, 50 VA maximum output), no enclosure
MS-TBK4BUS-0
Replacement SA/FC bus terminal blocks, 4-Position, gray, bulk pack
Note:
This is the standard terminal block that is provided with the controller.
AP-TBK4SA-0
Replacement SA bus terminal blocks, 4-Position, brown, bulk pack
AP-TBK4FC-0
Replacement FC bus terminal blocks, 4-Position, blue, bulk pack
AP-TBK3PW-0
Replacement power terminal blocks, 3-Position, gray, bulk pack
PEAK IOM57 Series technical specifications (Part 1 of 2 )
Product code numbers
PK-IOM5711 Series Input/Output Module
PK-IOM5731 Series Input/Output Module
Supply voltage
24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply Class 2
(North America), Safety Extra-Low Voltage (SELV) (Europe)
Power consumption
14 VA maximum
Note:
VA rating does not include any power supplied to the peripheral devices connected
to binary outputs (BOs) or configurable outputs (COs).
Ambient conditions
Operating:
-40°C to 70°C (-40°F to 158°F); 10% to 90% RH noncondensing
Storage:
-40°C to 80°C (-40°F to 176°F); 5% to 95% RH noncondensing
Addressing
DIP switch set; valid controller device addresses 4–127 (Device addresses 0–3 and
128–255 are reserved and not valid controller addresses.)
Communications bus
BACnet® MS/TP, RS-485:
3-wire FC bus between the supervisory controller and other controllers
4-wire SA bus between controller, network sensors, and other SA devices, includes a lead
to source 15 VDC supply power from controller to bus devices.
Processor
RX631 Renesas® 32 bit Microcontroller
Memory
1.0 MB Flash Memory and 256 KB Random Access Memory (RAM)
Input and output capabilities
IOM5711:
16 - Universal inputs:
Defined as 0 VDC–10 VDC, 4 mA–20 mA, 0k–600k ohm, or Binary
Dry Contact
IOM5731:
8 - Analog outputs:
Defined as 0 to 10 VDC
8 - Relay outputs:
(Single-Pole, Double-Throw)
UL Listed
1/4 hp 120 VAC, 1/2 hp 240 VAC
360 VA Pilot Duty at 120/240 VAC (B300)
3 A Non-inductive 24 VAC–240 VAC
CE Marking:
6 (4) A N.O. or N.C. only, 240 VAC
Analog input/Analog output
resolution and accuracy
Input:
15-ENOB resolution
Output:
16-bit resolution, +/- 200 mV accuracy in 0 VDC–10 VDC applications
Terminations
Input/Output:
Fixed spade terminals
SA/FC bus and supply power:
4-wire and 3-wire pluggable screw terminal blocks
SA/FC bus port:
RJ-12 6-pin modular jacks
Table 10: Accessories ordering information (Part 2 of 2)
Product code number
Description