MicroTrans
EQ
Operation & Maintenance Manual
Paragon Controls Incorporated
21
Revision Level 012
8.6.3. AutoZero
Test
Interval
For troubleshooting or testing the AutoZero function, the AutoZero Test Interval Menu allows the user
to select an Auto Zero test frequency of once a minute to once every 30 minutes in 1 minute increments.
Use the UP/DOWN keys to select the interval value. If AutoZero Test Interval is turned ON for more
than 60 minutes, it will automatically default to OFF and the AutoZero Interval (see Section 8.6.2) will
be reactivated.
Field
Setup
Menu
Flow Correction
AZ Status
AZ Test Interval
AutoZero
AZ Interval
(OFF)
Temp Comp.
AZ Test Interval
Interval
Display Filter
(1)Min
8.7. TEMPERATURE
COMPENSATION
The Temperature Compensation option compensates the flow and velocity signal for density changes
caused by variations in the process air temperature. The following menus for configuration of
Temperature Compensation are only available if the Temperature Compensation option is purchased.
Additionally, an input signal from an external temperature transmitter or the building automation system
is required; see Section 3.2 for proper temperature transmitter connection and Section 4.2 for
temperature input signal configuration.
8.7.1. Temperature
Units
The Temperature Units Menu allows the user to select the appropriate temperature units for the job.
Field
Setup
Menu
Flow Correction
Temperature Units
Units
AutoZero
Temperature Values
(ºF / ºC)
Temp Comp.
Temperature Input
Display Filter
Fixed Value
(ºF)