Страница 1: ...FT 1003 Air Volume Velocity Transducer Operation Maintenance Manual Engineered for accuracy applicability durability and simplicity...
Страница 2: ......
Страница 3: ...n Level 002 TABLE OF CONTENTS TABLE OF CONTENTS i 1 INTRODUCTION 1 1 1 DESCRIPTION 1 1 1 1 Installation Setup 1 2 CALIBRATION 2 2 1 DPT ZERO CALIBRATION 2 2 2 OUTPUT SPAN CALIBRATION 2 2 2 1 0 5vdc Ou...
Страница 4: ...in a change in capacitance which is then detected and processed electronically into an output signal linear to the velocity pressure The electronic signal is then sent to the square root extractor mu...
Страница 5: ...set to voltage mode monitor between TP1 GND and TP2 DPT Step 4 With no pressure applied adjust DPT ZERO potentiometer for a reading of 0 0 001vdc Step 5 Reinstall the black rubber plug 2 2 OUTPUT SPA...
Страница 6: ...1 Verify Supply Voltage level See Section 1 1 1 2 Verify correct wire connections 3 Verify correct pressure connections 4 Verify input pressure differential with a manometer 5 Contact Factory Service...
Страница 7: ......
Страница 8: ...Paragon Controls Incorporated P O Box 99 Forestville CA 95436 http www paragoncontrols com Phone 707 579 1424 Revision Level 002...