III.6 Measurement of Balanced 3 Phase AC Power Quality
L1
L3
L1
L2
L3
+
600V
COM
V L1
L3
a. Set the rotary switch at the 3 Phase position
b. Connect the test leads to the voltage source in parallel with the load.
c. Clamp on one of the wire to the load. The current should flow from the
front of the tester to the side of the battery cover
d. Press
3φ
button for balanced
3φ
system measurement.
e. Press the FUNC button to select following displays