Screen 3 ( 5-9 )
5-10 Transient Capture ( Dips, Swells, Outage )
1)If intend to make the Transient Capture measurement it
should set the transient voltage level ( high level, low
level ) at first , the setting procedures, please refere to
chapter 4-5-9 and chapter 4-5-10.
2)Press " Transient Key " ( 3-32, Fig. 1 ) will enter to
Transient Capture screen, insert the SD memory card
then press the " REC Button " ( 3-9, Fig. 1 ) will make
the measuremnt, refer as the Screen 1
3)Definition :
a. SWELL :
Vrms > ( Vref + ( Vref * SDVP% ) )
b. DIP
Vrms < ( Vref - ( Vref * SDVP% ) )
c. OUTAGE
Vrms < 30 V to 40 V.
60