PAGE 12
SENSO
RS AN
D INS
TRUME
N
TATI
O
N F
O
R MAC
HINE
CON
DITI
ON M
ON
IT
ORIN
G
STEP J Set Setpoint 3 (SP3)
(No [doM] or [dob])
1)
Using the
and
buttons, adjust the display to the desired SP3 value.
2)
Press the
button. Display toggles between [hYST] and the previous [hYST]
setting.
STEP K Set the Hysteresis Setting for Setpoint 3
1)
Using the
and
buttons, adjust the display to the desired hysteresis [hYST]
value.
2)
Press the
button. Display toggles between [SP4] and the previous [SP4]
setting.
STEP L Set Setpoint 4 (SP4)
(No [doM] or [dob])
1)
Using the
and
buttons, adjust the display to the desired SP4 value.
2)
Press the
button. Display toggles between [hYST] and 0.
STEP M Set the Hysteresis Setting for Setpoint 4
1)
Using the
and
buttons, adjust the display to the desired hysteresis [hYST]
value.
2)
Press the
button. Display toggles between [rLYS] and the previous relay
setting.
STEP N Set Relay Activation mode [rLYS]
(h) High the relay energizes when the setpoint is exceeded. (L) Low the relay
energizes below the setpoint. The setpoint is indicated from left to right SP1, SP2, SP3,
SP4.
1)
Using the
and
buttons, adjust the reading on the display to the desired
relay settings: [LLLL], [LhLh], [hLhL], [hhhh].
If only 2 relays installed [Lh--], [hL--], [hh--], [LL--].
2)
Press the
button. The meter exits the setpoint mode and returns to the
operational display.
The Setpoint Relay programming mode is now complete.