Introduction   

The Model 683A1 ICP

®

 

Process Indicator/Controller is an

 

intelligent 4-digit modular panel meter with software 

features for monitoring, measurement, and control applications complete with 0.56

 LED in a 1/8 DIN 96x48 case. 

The 683A1 operates from a single power supply and will supply 24Vdc/4mA excitation for sensor power. The 
indicator/controller comes equipped with two 5 Amp Form A relays with independent setpoints and time delay. 
 

 

General Features

 



External transmitters, signal conditioners, or power supplies can be eliminated by direct connection of the 
sensor to the indicator/controller. 



Optional isolated 16-bit analog output. User or factory scalable to 4 to 20 mA across any desired digital 
span from ± one count to the full-scale range of 

 1999 to 9999 (12000 counts). 



24Vdc/4mA excitation to power sensor. 



Standard Internal DIP switch selectable vibration ranges include: 

Acceleration (g

s) 

Velocity (in/sec) 

Displacement (mils p-p) 

5.000 

0.500 

25.0 

10.00 

1.000 

50.0 

20.00 

2.000 

100.0 



Two 5 Amp Form A relays, additionally two 5 Amp Form A or 10 Amp Form C relays are available. 



Programmable Time Delay to 9999 seconds. 



Internal DIP switch selection for Peak or RMS display. 



User specified, factory installed, High and Low pass 2-pole filtering.

 



Analog output signal connection (RV) for conducting frequency analysis and machinery diagnostics.

 

Software Features 

Three-button front panel programming of: 



Scale Factor and Offset 



Decimal point setting. 



Four-level brightness control of digital display. 



Peak and valley view and reset. 



Four programmable setpoints. 



Adjustable delay-on-make and delay-on-break time for setpoints 1 and 2. 



Relay activation can be selected to occur above (HI) or below (LO) each setpoint. 

Содержание IMI SENSORS 683A1

Страница 1: ...e w ICP sensors Installation and Operating Manual For assistance with the operation of this product contact PCB Piezotronics Inc Toll free 800 959 4464 24 hour SensorLine 716 684 0001 Fax 716 684 3823...

Страница 2: ...ty regimen When in doubt about a calibration cycle a good rule of thumb is to recalibrate on an annual basis It is also good practice to recalibrate after exposure to any severe temperature extreme sh...

Страница 3: ...rchase Order should include authorization to proceed and return at current pricing which can be obtained from a factory customer service representative Contact Information International customers shou...

Страница 4: ...isclosure Table Pb Hg Cd Cr VI PBB PBDE O O O O O O PCB X O O O O O O O O O O O X O O O O O O O O O O O O O O O O O O O O O O O O O X O O O O O O O O O X O O O O O O O O O O O X O O O O O X O O O O O...

Страница 5: ...e O O X O O O Wires O O O O O O Cables X O O O O O Plastic O O O O O O Solder X O O O O O Copper Alloy Brass X O O O O O This table is prepared in accordance with the provisions of SJ T 11364 O Indica...

Страница 6: ...Model 683A1 ICP Process Indicator Controller Operating Guide with Enclosed Warranty Information 3425 Walden Avenue Depew New York 14043 2495 Phone 716 684 0003 Fax 716 684 3823 Toll Free Line 1 800 95...

Страница 7: ...Page 4 Controls and Indicators Page 5 Glossary of Programming Symbols Page 6 Software Logic Tree Page 7 Programming the 683A1 Page 8 Wiring and Installation Page 13 Configuring the 683A1 Page 17 Acce...

Страница 8: ...one count to the full scale range of 1999 to 9999 12000 counts 24Vdc 4mA excitation to power sensor Standard Internal DIP switch selectable vibration ranges include Acceleration g s Velocity in sec D...

Страница 9: ...lays negative Decimal Selection Front panel button selectable X X X X Positive Overrange Top segments of digital display flash Negative Overrange Bottom segment of digital display flash Relay Output T...

Страница 10: ...etting mode Up Button When in the operational display pressing the button alone allows you to view and reset the Peak and Valley Highest and Lowest Readings When in calibration mode or the setpoint se...

Страница 11: ...can be increased by pressing and releasing the button or decreased by pressing and releasing the button When two buttons are shown side by side and enclosed by a dotted line they must be pressed at t...

Страница 12: ...is an intelligent meter with a hierarchical software structure designed for easy programming and operation as shown below in the software logic tree After the meter has been powered up the four digits...

Страница 13: ...ggles between cAL and out STEP B Select Between Calibration of Input or Output Note If the analog output option is not present Step B is skipped and the program goes directly from Step A to Step C 1 P...

Страница 14: ...onnect a multimeter to pins 16 and 17 on the output module See Rear Panel Pinouts on Page 8 Using the and buttons adjust the analog output to the desired low value as shown on the multimeter display c...

Страница 15: ...toggles between Anhi and the previous Anhi setting STEP G Setting the Digital Span Point for Analog High Output 1 Using the and buttons adjust the display to the desired digital value which sets the p...

Страница 16: ...y time has elapsed before the relay will make contact energize 2 Press the button Display toggles between dob and the previous dob setting STEP D Set the SP1 Delay on Break dob Delay Time Setting 1 Us...

Страница 17: ...value 2 Press the button Display toggles between hYST and 0 STEP M Set the Hysteresis Setting for Setpoint 4 1 Using the and buttons adjust the display to the desired hysteresis hYST value 2 Press th...

Страница 18: ...l connectors for all input and output connections The power supply connections pins 14 and 15 have a unique plug and socket outline to prevent cross connection The main board and input signal conditio...

Страница 19: ...ion To Maintain Conformance I O Shields must be connected to Pin 3 on the Panel Meter and all Supplied Accessories must be wired as shown Power Supply Option 2 1 2 3 4 5 8 9 10 11 14 15 ICP SENSOR SIM...

Страница 20: ...vate the LOCK or DIM functions from the rear of the meter the respective pins have to be connected to the COMMON pin This pin is connected to the internal power supply ground Pin 20 HOLD By connecting...

Страница 21: ...PAGE 16 SENSORS AND INSTRUMENTATION FOR MACHINE CONDITION MONITORING Case Dimensions and Panel Cutout...

Страница 22: ...removing the back cover and sliding the ICP Interface PC Board out of the Panel Meter Controller Once removed the DIP switch should be configured per one of the conditions in the following table Range...

Страница 23: ...forms a seal between the base and the panel The cam hinge prevents the cover from closing when opened until pushed closed The cover has a tapered recess that when closed forms a capillary seal with a...

Страница 24: ...olycarbonate case and is held firmly in place by spring type non return clips Once the metal case has been fitted to the polycarbonate case it cannot be removed With the metal case in place the meter...

Страница 25: ...ischarge ESD can damage electrical devices Similar to a capacitor a cable can hold a charge caused by triboelectric transfer such as that which occurs in the following Laying on and moving across a ru...

Страница 26: ...mp Form A Relays SPST Frequency Response 0 3Hz to 10kHz Standard 1 3Hz to 1kHz 2 10Hz to 10kHz 3 10Hz to 1kHz Accessories 0 None 1 96x48mm Clear Lockable Front Cover NEMA 4X Splash Proof 2 Metal Surro...

Страница 27: ...ior to servicing at no charge Before returning the unit please consult a factory IMI applications engineer concerning the situation as certain problems can often be corrected with simple on site proce...

Страница 28: ...price refunded IMI offers to all customers at no charge 24 hour phone support This service makes product or application support available to our customers day or night seven days a week When unforese...

Страница 29: ...5VAC 95 370VDC 85 265VAC 95 370VDC Current Consumption Typical 2 5W 2 5W Current Consumption Max 3 5W 3 5W Excitation Voltage 1VDC 24VDC 24VDC Constant Current Excitation 1mA 4mA 4mA Physical Size Dep...

Страница 30: ......

Отзывы: