CODE
IDENT. NO.
52681
DWG. NO.
SCALE:
SHEET
DRAWN
CHECKED
ENGINEER
TITLE
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
DECIMALS X
.05
XX
.01
XXX
.005
ANGLES ± 2 DEGREES
FILLETS AND RADII .003 - .005
HEX DIMENSIONS ARE:
≤
.5 + .000 / - .003
> .5 + .000 / - .005
REMOVE ALL BURRS
SHARP = R.000 - R.003
INTERNAL THREAD DEPTH MIN.
3425 WALDEN AVE. DEPEW, NY 14043
(716) 684-0002 E-MAIL: [email protected]
37476
CSA APPROVAL
685B0X00A1X AND
CS685YZZZ
INTERCONNECTION
2 OF 2
NONE
XXXX
.0005
JDM
7/17/17
JDM
7/17/17
GGS
7/17/17
SHLD.
COMM
RESET
SHLD.
4-20mA/15Vdc OUTPUT
NEG.
100mV/G
10G MAXIMUM
POS.
MT1
MT2
SHLD.
POS.
NEG.
RESET TO COMM
RAW VIBRATION OUTPUT
MOMENTARILY CONNECT
REMOTE RESET 5Vdc/1mA
SPST
5Adc 245Vac MAXIMUM
ALERT TRIAC
5Adc 245Vac MAXIMUM
MT2
VIBRATION SWITCH
PN 685B0X00A1X
GND
-AC
+AC
POWER SUPPLY
150mA MAXIMUM
85 to 245Vac 50/60Hz
ALARM TRIAC
SPST
NON-HAZARDOUS / SAFE AREA
OR DIV 2 / ZONE 2
CONDUIT/CABLE
POWER SUPPLY
SIGNAL CONDITIONER
MT1
HAZARDOUS AREA
DIV 2
VIBRATION SWITCH
PN CS685YZZZ
REVISIONS
REV
DESCRIPTION
DIN
- SEE SHEET 1-
37
47
6
PCB Piezotronics Inc. claims proprietary rights in
the information disclosed hereon. Neither it nor any
reproduction thereof will be disclosed to others
without the written consent of PCB Piezotronics Inc.
THE INSTALLER SHALL INSURE THAT THE TOP COVER INTERNAL GASKET AND CONDUIT
HUB THREADS ARE COATED WITH SUPPLIED SILICON GREASE TO MAINTAIN TYPE
4X/NEMA 4X INTEGRITY.
THE RELAY OUTPUTS MAY BE CONNECTED TO DIFFERENT PHASES ONLY FOR VOLTAGES
UP TO 125VAC. FOR VOLTAGES ABOVE 125VAC THE RELAYS SHALL BE CONNECTED
TO SAME PHASE CIRCUITS ONLY.
IF ONLY ONE CONDIT ENTRY IS USED, THE UNUSED ENTRY MUST BE SEALED WITH A FITTING
COMPLIANT TO HAZARDOUS RATINGS AS REQUIRED BY THE APPLICATION AND LOCAL
GOVERNING AGENCY.
INTERNAL GROUND SCREW MUST BE CONNECTED TO POWER SUPPLY GROUND WITH
WIRE SIZE EQUAL TO OR GREATER THAN 14 AWG.
ALL CONDUIT AND JUNCTION BOXES MUST MEET THE CLASS, DIVISION, GROUP, AND
INSTALLATION METHOD AS REQUIRED BY THE APPLICATION AND LOCAL
GOVERNING AGENCY.
SHIELDS TO BE EARTHED AT POWER SUPPLY END.
THE INSTALLER SHALL INSURE THAT THE VIBRATION SWITCH MOUNTING STRUCTURE IS AT
THE SAME GROUNDING POTENTIAL AS THE SUPPLY SOURCE GROUND. TOTAL EARTH
LOOP IMPEDANCE SHALL BE LESS THAN ONE OHM.
4.) FOR GUIDANCE ON CANADIAN INSTALLATION, REFER TO CEC PART I.
FOR GUIDANCE ON U.S. INSTALLATION, INSTALL IN ACCORDANCE WITH
NEC [ANSI/NFPA70] AND [ANSI/ISA RP12.6].
3.) CERTIFIED BY THE APPROPRIATE APPROVAL AUTHORITY FOR INSTALLATION IN THE
FOLLOWING AREAS:
CLASS 1, DIV 2, GROUPS A,B,C,D
CLASS 1, ZONE 2, GROUPS IIC T6
2.) WIRING (685B0X00A1X) & CS685YZZZ:
MULTICONDUCTOR
.5in [12.7mm] X 1000ft [305m] MAX.
1.) PART NUMBERS IS 685B0X00A1X WHERE X INDICATES RANGE, FREQUENCY RESPONSE,
AND NUMBER OF CONDUIT HUBS. 685B0X00D1X DENOTES INSTALLED MOUNTING PLATE.
10
9
8
7
6
5
11
10
10
11
7
8
11
5
11
8
7
11
5
11
9
6
NO CHANGES WITHOUT CSA APPROVAL
WARNING - EXPLOSION HAZARD
DO NOT DISCONNECT EQUIPTMENT
UNLESS POWER HAS BEEN SWITCHED
OFF OR THE AREA IS KNOWN TO BE
NON-HAZARDOUS
SCHEDULE DRAWING
NO MODIFICATIONS PERMITTED
WITHOUT REFERENCE TO THE
NOTIFIED BODY
AVERTISSEMENT - RISQUE D'EXPLOSION
NE PAS DÉCONNECTER L'ÉQUIPEMENT À MOINS
QUE LA PUISSANCE SOIT COMMUTE OFF OU LA
ZONE EST CONNUE POUR ÊTRE NON
DANGEREUX