SPECIFICATIONS
Heating Capacity and Efficiency
30040
42060
48080
60080
60100
66120
Input
High Heat
(BTUH)
40,000
60,000
80,000
80,000
100,000
120,000
Low Heat
(BTUH)
26,000
39,000
52,000
52,000
65,000
78,000
Output
High Heat
(BTUH)
39,000
58,000
78,000
78,000
97,000
117,000
Low Heat
(BTUH)
25,000
38,000
50,000
51,000
63,000
76,000
Efficiency
AFUE % (ICS)
96.0
96.0
96.0
96.0
96.0
96.0
Certified Temperature
Rise Range ºF (ºC)
High Heat
40 - 70
(22 - 39)
40 - 70
(22 - 39)
40 - 70
(22 - 39)
40 - 70
(22 - 39)
40 - 70
(22 - 39)
40 - 70
(22 - 39)
Low Heat
30 - 60
(17 - 33)
30 - 60
(17 - 33)
30 - 60
(17 - 33)
30 - 60
(17 - 33)
30 - 60
(17 - 33)
30 - 60
(17 - 33)
Airflow Capacity and Blower Data
30040
42060
48080
60080
60100
66120
Rated External Static
Pressure (in. w.c.)
Heating
0.10
0.12
0.15
0.15
0.20
0.20
Cooling
0.5
0.5
0.5
0.5
0.5
0.5
Airflow Delivery @ Rated ESP (CFM)
High Heat
815
1135
1505
1555
1865
2375
Low Heat
660
860
1160
1200
1435
1675
Cooling
905
1475
1610
2005
2005
2115
Cooling Capacity (tons)
400 CFM/ton
2
3.5
4
5
5
5
350 CFM/ton
2.5
4
4.5
5.5
5.5
6
Direct-Drive Motor Type
Electronically Commutated Motor (ECM)
Direct-Drive Motor HP
1/2
3/4
3/4
1
1
1
Motor Full Load Amps
6.8
8.4
8.4
10.9
10.9
10.9
RPM Range
600 - 1200
Speed Selections
Variable (PWM)
Blower Wheel Dia x Width
in.
11 x 7
11 x 8
11 x 8
11 x 10
11 x 10
11 x 11
Air Filtration System
Field Supplied
Filter Used for Certified Watt Data*
KGAWF**06UFR
Electrical Data
30040
42060
48080
60080
60100
66120
Input Voltage
Volts-Hertz-Phase
115-60-1
Operating Voltage Range
Min-Max
104 - 127
Maximum Input Amps
Amps
7.5
9.2
9.2
11.7
11.8
11.8
Unit Ampacity
Amps
10.3
12.4
12.4
15.5
15.6
15.6
Minimum Wire Size
AWG
14
14
14
12
12
12
Maximum Wire Length
@ Minimum Wire Size
Feet
36
29
29
37
36
36
(M)
(11.0)
(8.8)
(8.8)
(11.3)
(11.0)
(11.0)
Maximum Fuse/Ckt Bkr
(Time-Delay Type Recommended)
Amps
15
15
15
20
20
20
Transformer Capacity (24vac output)
40 VA
External Control Power Available
Heating
24.3 VA
Cooling
34.6 VA
Controls
30040
42060
48080
60080
60100
66120
Gas Connection Size
1/2" - NPT
Burners (Monoport)
2
3
4
4
5
6
Gas Valve (Redundant)
Manufacturer
White Rogers
Minimum Inlet Gas pressure (in. wc)
4.5
Maximum Inlet Gas pressure (in. wc)
13.6
Gas Conversion Kit - Natural to Propane
KGANP5201VSP
Gas Conversion Kit - Propane to Natural
KGAPN4401VSP
Manufactured (Mobile) Home Kit
not approved for MH use
Ignition Device
Silicon Nitride
Limit Control
165
180
170
200
180
160
Heating Blower Control (Heating Off-Delay)
Adjustable: 90, 120, 150, 180 seconds
Cooling Blower Control (Time Delay Relay)
90 seconds
Communication System
Non-communicating
Thermostat Connections
R, W/W1, W2 Y/Y2, Y1, G, Com 24V, DHUM
Accessory Connections
EAC (115vac); HUM (24vac); 1-stg AC (via Y/Y2)
* See Accessory List for part numbers available.
PG96V