Payne PA3P042 Скачать руководство пользователя страница 11

11

START--UP

CHECK FOR REFRIGERANT LEAKS
Proceed as follows to locate and repair a refrigerant leak and to
charge the unit:

1. Locate leak and make sure that refrigerant system pressure

has been relieved and reclaimed from both high-- and

low--pressure ports.

2. Repair leak following accepted practices.

NOTE

: Install a filter drier whenever the system has been opened

for repair.

3. Add a small charge of R--22 refrigerant vapor to system and

leak--test unit.

4. Recover refrigerant from system and evacuate to 500

microns if no additional leaks are found.

5. Charge unit with R--22 refrigerant, using a volumetric

charging cylinder or accurate scale. Refer to unit rating plate

for required charge. Be sure to add extra refrigerant to
compensate for internal volume of filter drier.

START--UP

COOLING

SECTION

AND

MAKE

ADJUSTMENTS
Complete the required procedures given in the Pre--Start--Up
section before starting the unit. Do not jumper any safety devices

when operating the unit. Do not operate the unit when the outdoor
temperature is below 40

°

F (4

°

C) (unless accessory low--ambient kit

is installed). Do not rapid cycle the compressor. Allow 5 minutes

between “on” cycles to prevent compressor damage.
CHECKING COOLING CONTROL OPERATION
Start and check the unit for proper cooling control operation as
follows:

1. Place room thermostat SYSTEM switch in OFF position.

Observe that blower motor starts when FAN switch is placed

in ON position and shuts down after 30 second fan time
delay expires when FAN switch is placed in AUTO position.

2. Place SYSTEM switch in COOL position and FAN switch

in AUTO position. Set cooling control below room
temperature. Observe that compressor, condenser fan, and

evaporator blower motors start. Observe that compressor
and outdoor fan shut down when control setting is satisfied

and that indoor blower shuts down after 30 second fan time
delay expires.

IMPORTANT

: Three--phase, scroll compressors are direction

oriented. Unit must be checked to ensure proper compressor
3--phase power lead orientation. If not corrected within 5 minutes,
the internal protector will shut off the compressor. The 3--phase
power leads to the unit must be reversed to correct rotation. When
turning backwards, the difference between compressor suction and
discharge pressures may be dramatically lower than normal.

CHECKING AND ADJUSTING REFRIGERANT CHARGE
The refrigerant system is fully charged with R--22 refrigerant and

is tested and factory sealed.

NOTE

: Adjustment of the refrigerant charge is not required unless

the unit is suspected of not having the proper R--22 charge.
A superheat charging chart is attached to the outside of the service

access panel. The chart includes the required suction line
temperature at given suction line pressures and outdoor ambient

temperatures.

An accurate superheat, thermocouple-- or thermistor--type
thermometer, and a gauge manifold are required when using the

superheat charging method for evaluating the unit charge. Do not
use mercury or small dial--type thermometers because they are not

adequate for this type of measurement.

NOTE

: Allow system to operate for a minimum of 10 minutes

before checking or adjusting refrigerant charge.

IMPORTANT

: When evaluating the refrigerant charge, an

indicated adjustment to the specified factory charge must always be
very minimal. If a substantial adjustment is indicated, an abnormal
condition exists somewhere in the cooling system, such as
insufficient airflow across either coil or both coils.

Proceed as follows:

1. Remove caps from low-- and high--pressure service fittings.
2. Using hoses with valve core depressors, attach low-- and

high--pressure gauge hoses to low-- and high--pressure

service fittings, respectively.

3. Start unit and let run until system pressures stabilize.
4. Measure and record the following:

a. Outdoor ambient--air temperature (

°

F (

°

C) db).

b. Suction--tube temperature (

°

F(

°

C) ) at low--side service

fitting.

c. Suction (low--side) pressure (psig).

5. Using Cooling Charging Charts compare outdoor--air

temperature (

°

F (

°

C) db) with the suction line pressure (psig)

to determine desired system operating suction line

temperature (See Fig. 16).

6. Compare actual suction--tube temperature with desired

suction--tube temperature. Using a tolerance of

±

3

°

F, add

refrigerant if actual temperature is more than 3

°

F higher than

proper suction--tube temperature, or remove refrigerant if

actual temperature is more than 3

°

F lower than required

suction--tube temperature.

NOTE

: If the problem causing the inaccurate readings is a

refrigerant leak, refer to Check for Refrigerant Leaks section.
INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS

NOTE

: For cooling operation, the recommended airflow is 350 to

450 cfm for each 12,000 Btuh of rated cooling capacity.
Table 3 shows cooling airflows at various external static pressures.
Refer to this table to determine the airflow for the system being

installed.

NOTE

: Be sure that all supply-- and return--air grilles are open, free

from obstructions, and adjusted properly.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Disconnect electrical power to the unit and install lockout tag

before changing blower speed.

!

WARNING

PA

3P

Содержание PA3P042

Страница 1: ...ter Piston 18 TROUBLESHOOTING 18 START UP CHECKLIST 18 A05120 Fig 1 Unit PA3P SAFETY CONSIDERATIONS Installation and servicing of this equipment can be hazardous due to mechanical and electrical compo...

Страница 2: ...that the fan discharge does not recirculate to the outdoor coil Do not locate the unit in either a corner or under an overhead obstruction The minimum clearance under a partial overhang such as a nor...

Страница 3: ...UIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTR...

Страница 4: ...S INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTRY SIDE 42 00 10...

Страница 5: ...port CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM PA3P024 036 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126...

Страница 6: ...l UNIT FALLING HAZARD Failure to follow this warning could result in personal injury or death Never stand beneath rigged units or lift over people WARNING INSTALLATION The lifting rigging bracket is e...

Страница 7: ...Be sure to check the drain tube for leaks Prime trap at the beginning of the cooling season start up 1 25mm MIN 2 50mm MIN TRAP OUTLET C99013 Fig 8 Condensate Trap Step 7 Install Duct Connections Thed...

Страница 8: ...sion of vibration The transition may be screwed or bolted to duct flanges Use suitable gaskets to ensure weather tight and airtight seal 4 All units must have field supplied filters or accessory filte...

Страница 9: ...the line side of the contactor 4 Connect field L1 to black wire on connection 11 of the compressor contactor 5 Connect field wire L2 toyellow wireon connection13 ofthe compressor contactor 6 Connect...

Страница 10: ...al box if refrigerant leak is suspected around compressor terminals 3 Never attempt to repair soldered connection while refrigerant system is under pressure 4 Do not use torch to remove any component...

Страница 11: ...gerant charge is not required unless the unit is suspected of not having the proper R 22 charge A superheat charging chart is attached to the outside of the service access panel The chart includes the...

Страница 12: ...511 496 478 460 439 CFM 1526 1482 1437 1398 1344 1281 1205 1125 1029 High Watts 765 746 730 709 690 664 642 624 600 CFM 1860 1805 1751 1685 1620 1541 1468 1370 1265 50SD048 Low Watts 627 617 607 584 5...

Страница 13: ...13 A07034 Fig 13 Wiring Diagram 208 230 1 60 PA3P...

Страница 14: ...14 A07035 Fig 14 Wiring Diagram 208 230 3 60 PA3P...

Страница 15: ...15 A07037 Fig 15 Wiring Diagram 460 3 60 PA3P...

Страница 16: ...onnect contactor coil C through unit wire Y and time delay relay TDR through unit wire G across the 24 v secondary of transformer TRAN The normally open contacts of energized contactor C close and com...

Страница 17: ...onomy andcontinuing efficiency clean accumulated dirt and grease from the blower wheel and motor annually ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or deat...

Страница 18: ...ssemble the connection properly and securely After inspecting the electrical controls and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper...

Страница 19: ...e cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Faulty...

Страница 20: ...ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE __________________________________ COMPRESSOR AMPS_________________________________ INDOOR EVAPORATOR FAN AMPS___________ TEMPERAT...

Отзывы: