Payne PA2P024 Скачать руководство пользователя страница 2

To assure proper functioning of the unit, flow of condenser air must not be obstructed from reaching the unit. Clearance of at least 48 in. is required
from top of unit and on sides except the power entry side (42 in. clearance) and the duct side (12 in. minimum clearance).

MAINTENANCE AND CARE FOR THE EQUIPMENT OWNER

Before proceeding with those things you might want to maintain yourself, please carefully consider the following:

WARNING: 1. TURN OFF ELECTRICAL POWER TO YOUR UNIT BEFORE SERVICING OR PERFORMING MAINTE-

NANCE.

2. When removing access panels or performing maintenance functions inside your unit, be aware of sharp sheet metal parts

and screws. Although special care is taken to reduce sharp edges to a minimum, be extremely careful when handling parts
or reaching into the unit.

A.

Air Filters

Air filter(s) should be checked at least every 3 or 4 weeks and changed or cleaned whenever it becomes dirty. Dirty filters produce excessive stress
on the blower motor and can cause the motor to overheat and shut down. Table 1 indicates the correct filter size for your unit. Refer to Fig. 2 to
access the filter(s).

To replace or inspect filter(s) (or accessory filter rack when supplied):

1. Remove the filter access panel using a 5/16-in. nut driver.

2. Remove the filter(s) by pulling the filter(s) out of the unit. If the filter(s) is dirty, clean or replace with new one.

When installing the new filter(s), note the direction of the airflow arrows on the filter frame.
If you have difficulty in locating your air filter(s), or if you have questions concerning proper filter maintenance, contact your dealer for
instructions. When replacing filters, always use the same size and type of filter that was supplied originally by the installer.

WARNING: Never operate your unit without filters in place. Failure to heed this warning may result in damage to the

blower motor and/or compressor. An accumulation of dust and lint on internal parts of your unit can cause loss of efficiency
and, in some cases, fire.

B.

Fans and Fan Motor

Periodically check the condition of fan wheels and housings and fan-motor shaft bearings. No lubrication of condenser- or evaporator-fan bearings
or motors is required or recommended.

Fig. 2—Filter Access Panel—Vertical Supply Shown

ACCESS PANEL

FILTER ACCESS
PANEL*

*For accessory filter rack.

Table 1—Indoor-Air Filter Data

UNIT SIZE

FILTER SIZE

PA1P-B018-030

20x20

PA1P-B036-042

20x24

PA1P-B048-060

24x30

PA2P024-030

20x20

PA2P036

20x24

PA2P042-060

24x30

—2—

Содержание PA2P024

Страница 1: ...ury or death TO START UNIT PROCEDURE 1 TURN ON THE ELECTRICAL POWER SUPPLY TO UNIT PROCEDURE 2 SELECT TEMPERATURE AND SET SYSTEM SWITCH TO DESIRED MODE TO SHUT UNIT OFF If unit is being shut down beca...

Страница 2: ...ct filter s or accessory filter rack when supplied 1 Remove the filter access panel using a 5 16 in nut driver 2 Remove the filter s by pulling the filter s out of the unit If the filter s is dirty cl...

Страница 3: ...ar should include the following 1 Inspection and if required cleaning of the condenser and evaporator coils 2 Inspection and if required cleaning of the evaporator drain pan 3 Inspection and cleaning...

Страница 4: ...space provided If the dealer knows exactly which unit you have he may be able to offer suggestions over the phone or save valuable time through knowledgeable preparation for the service call IN CASE O...

Страница 5: ...material and workmanship under normal use and maintenance for a period of one year from the date of original installation whether or not actual use begins on that date A new or remanufactured part at...

Страница 6: ...6...

Страница 7: ...of dealer 8 Dealer s installation policy 9 Friend s relative s recommendation 10 Contractor s dealer s recommendation 11 Other ____________________ 1 1 Age years Female 2 Male 2 years You 1 2 3 4 5 6...

Страница 8: ...1999 Payne Heating Cooling P O Box 70 Indianapolis IN 46206 8 OG PA1P 01 Catalog No 53PA 1P4...

Отзывы: