5 Deinstallation
12
993203x3x-mub-en – V10
2018/02
4.2
Accessories: compression fitting (not included in the scope of delivery)
The connection to the heating installation can be carried out fast, pressure-proof and without
soldering when you use the optionally available compression fittings.
Not included in
the scope of delivery!
1.
Push the union nut ② and the cutting ring ③ onto the
copper pipe ①. The pipe must protrude at least 3 mm
from the cutting ring in order to ensure the force
transmission and the sealing.
2.
Insert the support sleeve ④ into the copper pipe.
3.
Insert the copper pipe with the plugged-on individual
parts (②, ③ and ④) all the way into the housing of
the compression fitting ⑤.
4.
First screw the uni
on nut ② manually.
5.
Tighten the union nut ② by rotating one full turn.
Secure the housing of the compression fitting ⑤
against distort in order to avoid damaging the
sealing ring.
5
Deinstallation
To remove the boiler charging set from the
mounting plate, push the clips sidewards with
a screwdriver. The boiler charging set can then
be pulled forwards (consider the tubing!).