19
en
Maximum speed of the primary pump
Main menu / Store loading / Prim. max. speed
Adjustment channel Description
Adjustment range /
selection
Factory
setting
Prim. max. speed
Maximum speed of the primary pump 1.5 … 100 %
100 %
With the parameter Prim. max. speed the maximum speed of the primary pump
can be adjusted.
Note:
The adjustable value represents the speed of the corresponding pump.
Maximum speed (100 %) is reached at 80 to 90 % of the PWM signal duty
cycle. The minimum value (1.5 %) is reached at 10 to 20 % of the PWM
signal duty cycle.
The power of the PWM signal is indicated in the status menu.
Maximum speed of the secondary pump
Main menu / Store loading / Sec. max. speed
Adjustment channel Description
Adjustment range /
selection
Factory
setting
Sec. max. speed
Maximum speed of the secondary pump 1.5 … 100 %
80 %
With the parameter Sec. max. speed the maximum speed of the primary pump
can be adjusted.
Note:
The adjustable values of both channels represent the speed of the cor-
responding pump.
Maximum speed (100 %) is reached at 80 to 90 % of the PWM signal duty
cycle. The minimum value (1.5 %) is reached at 10 to 20 % of the PWM
signal duty cycle.
The duty cycle of the corresponding PWM signal is indicated in the status
menu.
Minimum hot water set temperature
Main menu / Store loading / Set min
Adjustment channel Description
Adjustment range /
selection
Factory
setting
Set min
Minimum hot water set temperature
20 … 75 °C
20 °C
This parameter determines the minimum limitation for the adjustment of the hot
water set temperature T-HW set.