Addr. of Modbus register
Data stored in memory with the 0x0020 command
41001-41002
Cells capacity
41003
Cells sensitivity
41004
Weight division value
41005-41006
Tare of the system
41007-41008
System capacity
41101
Weight filter
41102
Weight stability
41103-41104
Auto-zero setpoint
41105
Zero tracking
41106
Zero band in divisions
41201
Operation mode Set 1
41202-41203
Hysteresis Set 1
41204
Timer Set 1
41205
Delay Set 1
41206
Operation mode Set 2
41207-41208
Hysteresis Set 2
41209
Timer Set 2
41210
Delay Set 2
41401-41402
Analog full scale
41403
Analog mode
41404
Analog range
TABELLA F - WEIGHT SETPOINT OPERATION CODING
bit
Setpoint operation mode
0…1
0 = Net weight, 1 = Gross weight, 2 = Peak
2
0 = N.O. 1 = N:C.
3
0 = Positive values 1 = Negative values
4
0 = Always controlled 1 = Only with stable weight
EXAMPLE: CALIBRATION FUNCTION VIA MODBUS
To perform the calibration of full scale (that require the weight value in the sample set in the data register),
the value in the data register must be present when the command register is programmed. For example:
Calibrate the full scale using a sample weight of 2000 kg.
Write 2000 in the data register.
Write 0x0011 in the command register.
Use the multiple registers write function and write the registers of data register and command register
in a single command.