background image

 

3.1.2.2  Safety instructions – Installation 

  Comply with the general locally applicable building, fire, safety and installation 

regulations of the relevant local authorities, the regulations of the water and electric 

utilities and all other official regulations. 

  Pull the unit’s plug from the mains socket to separate the unit from the power supply. 

If the unit does not have a plug, use a switch according to EN 60335-1 (with 

separation of all three poles and 3 mm clearance, over-voltage category III). 

  Always disconnect the unit from the power supply prior to commencing maintenance 

or repair activities. If the unit is operated while open, there is hazard of injury. 

  Make sure that the FOCUS unit cannot switch on unintentionally. 

  To eliminate the risk of coming into contact with the running fans, the air ducts must 

be fastened to the unit before the power supply is connected, observing a minimum 

length of 900 mm. 

  Therefore, always apply measures to prevent electrostatic discharges when working 

on the electronics. Wear an antistatic wrist band, for example. Static energy can 

cause damage to electronic components. 

  The entire installation must comply with the applicable (safety) regulations from the 

following sources: 

- local EU standard for safety features for low voltage systems; 

-  Mounting/installation manual of the manufacturer (see the back cover of the 

instruction manual for the contact data of Zehnder). 

  A socket with grounding at a distance of 1 meter or no more than the length of the 

included mains cable must be present. 

  For safety reasons do not use an extension cable. 

  Installation conditions 

The following conditions must be considered when deciding whether a unit should be installed in a specific area to 

ensure the correct installation of the unit. 

  Ensure that the temperatures in the installation area are in the permissible range year-round. The information 

regarding the permissible temperature can be found in the “Technical specification” table. 

  When choosing an installation location, it is recommended that you avoid areas with a high average level of 

humidity (ambient conditions for indoor climate control system must not continuously exceed 70% RH at 22 °C). 

  The unit must not be installed in rooms subject to explosion hazards. 

  Inside wet rooms, the unit may only be installed outside of protection zones 1 and 2 in accordance with DIN 

57100/VDE 100 Part 701. 

  Connect the unit to a power source with 230 V/50 Hz. 

  Check whether the electrical installation is suitable for the maximum  output of the unit. The values for the 

electrical input power can be found in the “Technical specification” chapter. 

  Check that the installation area of the unit meets the requirements in the “Installation requirements” chapter. 

Chapter for operators and qualified personnel 

  Product description 

The FOCUS unit is a ventilation unit with heat recovery for healthy, well-balanced and energy-saving comfort 

ventilation. A comfort ventilation system extracts foul-smelling waste air from areas such as kitchens, bathrooms and 

toilets and conveys an identical quantity of fresh air into living rooms, bedrooms and children's rooms. A highly 

efficient cross-counterflow heat exchanger made from plastic is used for waste heat recovery. An optional summer 

box module can be used instead of the heat exchanger for thermal separation of the two airflows. The housing is 

made from sheet metal with an anthracite powder coating. The high-quality polypropylene inner lining ensures the 

necessary thermal insulation and unit soundproofing. 

The FOCUS unit has two maintenance-free 230 VAC centrifugal fans with an integrated power supply unit and 

electronic commutation. The fans run at a steady volume flow to keep the air volume constant at any selected fan 

speed. The air volume is not affected even if the filters become soiled. 

The unit contains filters according to EN ISO 16890 of the filter class ISO Coarse for the outdoor air and the extract 

air. These consist of a synthetic non-woven filter medium with a polypropylene frame. As an option, filters of filter 

class ePM1 can be used for the outdoor air. The filters are accessed via the front panel. 

Содержание FOCUS 200 Base

Страница 1: ...Translation of the original instruction manual Heat Recovery Unit FOCUS 200 Base...

Страница 2: ...this manual in part or as a whole The information contained in these documents is the property of Zehnder Group Any form of publication whether in whole or in part requires the written approval of Zeh...

Страница 3: ...ions 11 External control signal 0 10 V 11 Boost ventilation mode with external boost ventilation key 12 Maintenance by the user 12 Replacing the unit filters 12 Resetting the filter running time 15 Wh...

Страница 4: ...chnical description 28 Air connection design versions 28 Technical specification 28 Dimensions 30 FOCUS 200 Base terminal scheme 31 6 Appendices 32 Checklist A Maintenance work for users 32 Checklist...

Страница 5: ...the various design variants of the FOCUS heat recovery unit Possible accessories are only described to the extent necessary for appropriate operation of the unit Please refer to the respective instruc...

Страница 6: ...if the safety feature is triggered In case of open flue fireplaces for solid fuels the ventilation system must be switched off if the safety feature is triggered The ventilation units for controlled v...

Страница 7: ...nt Symbol Meaning Important note Caution Risk of affecting the operation of the ventilation system or damaging the unit Caution Risk of personal injury Safety regulations 3 1 2 1 Safety instructions g...

Страница 8: ...osing an installation location it is recommended that you avoid areas with a high average level of humidity ambient conditions for indoor climate control system must not continuously exceed 70 RH at 2...

Страница 9: ...product and in case of questions for service The type label is located on the same side of the unit as the air connections and must remain permanently attached to the product Frost protection The FOCU...

Страница 10: ...operating functions Description Explanation Intensity scale Rotary knob positioning Operating mode Ventilation with constant air volume flow according to the intensity scale Position 1st scaling segm...

Страница 11: ...reset filter running time key allows you to reset the filter running time To restart the filter running time press and hold this key for 3 s If the filter running time is reset before the end of 180...

Страница 12: ...hs As part of this process please inspect the other filters in the ventilation system and replace them if necessary The filter mats on the extract air valves e g bathroom kitchen WC should be replaced...

Страница 13: ...and heat exchanger out of the EPP housing To do this grip the strap at one end and pull while using your other hand to support the unit Fig 5 Pulling out the EPP foam cover of the filters and heat ex...

Страница 14: ...rding to the type label filters with filter class ISO ePM1 must be inserted into the filter compartment of the outdoor air connector The outdoor air connector is indicated by the symbol on the air con...

Страница 15: ...of at the end of their useful life in accordance with the applicable regulations in your country 5 Chapter for qualified persons Installation requirements The following requirements must be assured f...

Страница 16: ...heck that the wall construction has the necessary load bearing capacity net weight of the FOCUS unit is 25 kg and that the fastening sheet can be mounted securely In case of unsuitable walls we recomm...

Страница 17: ...S unit onto the fastening sheet by inserting the lugs B into the slots E in the lock seam at the top of the rear cover Fig 12 Hooking the unit into the fastening sheet Fitting on Floor stand optional...

Страница 18: ...ow place the short base part at right angles to the long base part at a staggered height Fig 14 Assembling the base parts 2 Working in the direction of the arrow push the lugs A of the short base part...

Страница 19: ...mb vertical and stable Then fix it in this height position with the lock nuts of the adjustable feet Fig 18 Aligning the floor stand 6 Place the FOCUS unit on the floor stand so that the lugs of the f...

Страница 20: ...haust air fan when it thaws causing damage to the blades Fig 20 Drainage arrangement for outdoor and exhaust air tubes If an attenuator is fitted at the exhaust air connector it must be routed upwards...

Страница 21: ...when The unit is commissioned The siphon starts making slurping gurgling noises We generally recommend using a dry siphon No functional restrictions if it dries out no need for a 2nd siphon Electrical...

Страница 22: ...necting cable to the flat connector plug As shown in Fig 24 a J Y St Y 2x2x0 6 cable is recommended as the connecting cable between the control panel and the FOCUS unit The maximum permitted cable len...

Страница 23: ...nel connecting terminal Wire of boost ventilation key cable X 07 Wire 1 X 08 Wire 2 GND Table 7 Terminal assignment of boost ventilation key connection Connecting external sensors A sensor controlled...

Страница 24: ...total outdoor air volume flow This nominal air volume flow must correspond to a rotary knob position according to the illustration of the control unit Fig 25 Diagram 1 fan speeds parametrisation Fig 2...

Страница 25: ...ceed two years Use checklist B to document the maintenance work completed Inspection and cleaning of the heat exchanger In doing so proceed as follows 1 Disconnect the FOCUS unit from the mains power...

Страница 26: ...g out the EPP foam cover 5 Holding them by the strap pull the filters E out of the filter compartments Fig 30 Pulling out the filters 6 Holding it by the strap F pull the heat exchanger G out of the E...

Страница 27: ...heat exchanger to dry fully before reinstalling it Instructions for proper disinfection can be found at www core life 8 Install the heat exchanger Take care when installing the heat exchanger On the...

Страница 28: ...limit value Blinks 4x per second Temperature downstream of pre heater 3K below limit value LED 3 Lights up Pre heater heating up Table 10 Overview of how working conditions are displayed Technical des...

Страница 29: ...tance of 3 m unit emission according to DIN EN ISO 3743 1 30 dB A at 155 m h 100 Pa 24 dB A at 200 m h 100 Pa Table 13 Operation data p characteristic curve Note The numerical values shown in the p ch...

Страница 30: ...30 Dimensions Fig 33 Dimensional drawing...

Страница 31: ...31 FOCUS 200 Base terminal scheme Fig 34 Terminal assignment terminal plan...

Страница 32: ...cycle 90 days Quarter Year I II III IV 20 20 20 20 20 20 20 20 20 20 2nd Extract air supplementary filter clean the filters in extract air valves filter replacement cycle approx 2 months Quarter Year...

Страница 33: ...ns and clamping assemblies secure yes no Are the regulating and control units functional yes no 3 Ventilation tube heat insulation Has cleaning if necessary been carried out Testing OK For cleaning wh...

Страница 34: ...n as planned Cleaning option provided yes no yes no yes no 5 Extract air duct Cleaning option provided yes no 6 Extractor fan Cleaning option provided yes no 7 Control regulation system Operational ye...

Страница 35: ...days used very dirty Supply air Fan speed No Room name Project data Measurement data m h m s m h m s Extract air Fan speed No Room name Project data Measurement data m h m s m h m s Pel W The listed...

Страница 36: ...36 PDE Manual_Focus 200 Base_V1 1 V1122 DE Subject to change...

Отзывы: