P-K SOLIS™
Gas Fired Boiler
Technical Service 1.877.728.5351
Revised: March 15, 2021
Released: March 15, 2021
Patterson-Kelley 2021
All Rights Reserved.
2701000090 P-K SOLIS NURO Installation and
Owners Manual (Rev A).docx
Page 61
23. Re-Install the burner access plate.
a. Ensure the burner access plate gasket is in place before installing the plate
b. Ensure the gasket is aligned properly with the reliefs on the plate.
c. Gradually tighten the eight (8) M6 nuts using an 11mm socket or wrench in the order
shown in Step 22 (c) to a torque of 7.4 ft.-lbs.
24.
Reinstall the ignition electrode assembly (if previously removed).
25.
Reinstall the flame/ionization rod assembly (if previously removed).
26.
Reinstall the wires/cables to the ignition electrode and flame/ionization rod.
27.
Double check the tightness of all bolted joints.
The burner access plate gasket must be installed correctly. Failure to comply could result in severe personal
injury, death, or substantial property damage
.
PRECAUTIONS ASSOCIATED WITH HANDLING REFRACTORY LINING MATERIAL
•
This Patterson-Kelley product contains a Combustion Area lined with
REFRACTORY
CERAMIC FIBERS (RCFs)
similar to many other devices produced in this industry.
•
RCFs have been identified by the
International Agency for Research on Cancer (IARC)
as possibly being carcinogenic to Humans.
•
AVOID breathing particles or dust from
RCFs
and avoid contact with Skin or Eyes.
•
The
National Institute for Occupational Safety and Health (NIOSH)
recommends the use
of a respirator meeting current standards, to avoid inhalation of dust. Also recommended is
loose fitting, long sleeved clothing, eye protection and gloves whenever handling
RCFs
.
Current
NIOSH
Recommendations are listed on their website at
http://www.cdc.gov/niosh/homepage.html
, which should be viewed before the handling or
removal of Refractory Lining Materials on this or any similar device.
•
Using a SPRAY BOTTLE, saturate with WATER; but not dripping, the combustion chamber
lining to prevent dust from becoming airborne.
•
Place removed
RCFs
into a plastic bag for disposal with normal trash.
•
Wash exposed clothing (if not disposable), TWICE and DRY separately from other laundry.