The PCO MAG is installed in the ductwork of
the central air system to reduce odors and
airborne biological contaminants for improved
indoor air quality. The PCO MAG also reduces
microbial growth within the air system.
Installation Guide
Air Handler
2nd UV Lamp
2
Installation Notes
The PCO MAG is usually installed inside the central
air handling system. The unit should be oriented so
that the air flows past the
UV Light
first then into
the
Matrix Element
but a reversed installation is
permitted if mounting on the return-side of the coil.
If a second optional UV lamp is used (PCO MAG
Dual) select a location inside the air system that
will allow it to shine on the greatest surface area or
the area with the most evident microbial growth.
To install the secondary UV light use the
Optional
2nd Remote UV Light Installation Instructions
provided with PCO MAG Dual.
Typical installations include:
A
PCO MAG single in air handler
B
PCO MAG dual in air handler
C
PCO MAG in Package Unit
A
B
Package Unit
C
A
O
N
M
K
L
J
I
H
F
G
D
E
1
Parts List
Note: These parts are only included
with PCO MAG Dual.
*Note: only one lamp and power supply are included with PCO MAG.
B
C
D
E
TUVL-115P
TUVL-215P
3
Mount Lamp
Mount the
UV Lamp
to the
PCO
MAG
unit as shown using 2 quick
nuts
J
.
J
© 2016 Patriot UV - Manufactured by Triatomic Environmental, Inc. PAT-PCO-MAG-MAN 12.5.16
US patent #7,704,463
IMPORTANT!
• Only qualified technicians should install this product
• Install in accordance with relevant building codes
• Read instructions carefully including safety warnings
4
Air Handler Interior
Surface Installation
1.
Determine the optimal position for
placement of
PCO MAG
inside the air
system.
2.
Use a utility knife to cut a slit in the
insulation on the interior surface.
3.
Place the
magnetic mounting bracket
directly on the metal surface or remove the
magnet and hard-mount the bracket using
the
self-tapping screws
provided. Use foil
tape to close the cut in the insulation.
2.
3.
Important!
do not install the mounting
magnet within 12” of digital signal
devices as this may cause interference.
6
UV Lamp Connection
Make sure the flanges are aligned and then push
the connectors firmly together. A tight connection
ensures a proper water-resistant seal.
2.
1.
*Installation of this product by anyone other than licensed HVAC or electrical contractors voids warranty.
WARNING
PROTECT EYES FROM UV LIGHT
TURN OFF UNIT OR DISCONNECT
BEFORE SERVICING
5
Connecting to Power
IMPORTANT
Before connecting to power confirm which PCO MAG model is being installed. Turn off main
power source before installation. Model information is printed on the
Power Unit
cover.
IMPORTANT! Must be wired to constant power - do not connect to blower relay.
PCOMAG ER
PCOMAG
SI/DI
ST/DT
120-277 VAC
POWER SUPPLY
UV LAMP
4 PIN
CONNECTOR
L1 - BLACK
L2 or N - WHITE
GND - GREEN
Optional 2nd UV Lamp
24 VAC
POWER SUPPLY
UV LAMP
BLACK
4 PIN
CONNECTOR
RED
24 VAC TRANSFORMER
COMMON / BLUE
HOT / RED
CAUTION!
UV lamps contain small amounts of mercury - dispose of lamps in accordance with
local environmental regulations. For more information visit www.lamprecycle.org
Note:
Use of replacement UV lamps other than Patriot UV voids warranty
.
IMPORTANT!
Systems with high 24 VAC loads may require the installation of a separate 24 VAC
transformer to power the UV light.
Always use a separate 24 VAC transformer with “communicating” air systems and all
Patriot PCO Dual (PAT-PCO-DER) models.
Draws 16 VA, may need to do load calculation: Volts under load X Amps under load.
7
Lamp Replacement
The germicidal UV lamp in Patriot PCO needs to be
replaced periodically. TUVL-111P and TUVL115P lamps
should be replaced every year. TUVL-211P and TUVL-215P
should be replaced every 2 years.
Note: UV lamps will continue to emit visible light but lose
germicidal effectiveness over time. You can upgrade to a 2
year lamp with your existing Patriot PCO system.