WARNING

WARNING

Align Flanges

A

 PCO MAG Unit

B

 PCO MAG 11 UV Lamp 1 Year*

C

 PCO MAG 11 UV Lamp 2 Year*

D

 PCO MAG 15 UV Lamp 1 Year*

E

 PCO MAG 15 UV Lamp 2 Year*

F

 ER Power Supply*

G

 ST/DT Power Supply*

H

 SI/DI Power Supply*

I

 Self-tapping Screws

J

 Quick Nut (plastic)

K

 Spade Connector

L

 Tap-in Connector

M

 “Z” Mounting Bracket

N

 Sight Glass

O

 Warning Sticker

The PCO MAG is installed in the ductwork of 

the central air system to reduce odors and 

airborne biological contaminants for improved 

indoor air quality. The PCO MAG also reduces 

microbial growth within the air system.

Installation Guide

Air Handler

2nd UV Lamp

2

 Installation Notes

The PCO MAG is usually installed inside the central 

air handling system. The unit should be oriented so 

that the air flows past the 

UV Light

 first then into 

the 

Matrix Element 

but a reversed installation is 

permitted if mounting on the return-side of the coil.

 

If a second optional UV lamp is used (PCO MAG 

Dual) select a location inside the air system that 

will allow it to shine on the greatest surface area or 

the area with the most evident microbial growth. 

To install the secondary UV light use the 

Optional 

2nd Remote UV Light Installation Instructions

 

provided with PCO MAG Dual. 

Typical installations include:

A

 PCO MAG single in air handler

B

 PCO MAG dual in air handler

C

 PCO MAG in Package Unit

A

B

Package Unit

C

A

O

N

M

K

L

J

I

H

F

G

D

E

1

 Parts List

Note: These parts are only included 

with PCO MAG Dual.

*Note: only one lamp and power supply are included with PCO MAG.

B

C

D

E

TUVL-115P

TUVL-215P

3

 Mount Lamp

Mount the 

UV Lamp

 to the 

PCO 

MAG

 unit as shown using 2 quick 

nuts 

J

 .

J

© 2016 Patriot UV   -   Manufactured by Triatomic Environmental, Inc.     PAT-PCO-MAG-MAN 12.5.16

US patent #7,704,463

IMPORTANT!

•  Only qualified technicians should install this product

•  Install in accordance with relevant building codes

•  Read instructions carefully including safety warnings

4

 Air Handler Interior   

      Surface Installation
1. 

Determine the optimal position for 

placement of 

PCO MAG 

inside the air 

system.

2.

 Use a utility knife to cut a slit in the 

insulation on the interior surface.

3.

 Place the 

magnetic mounting bracket

 

directly on the metal surface or remove the 

magnet and hard-mount the bracket using 

the 

self-tapping screws

 provided. Use foil 

tape to close the cut in the insulation.

2. 

3. 

Important!

 do not install the mounting 

magnet within 12” of digital signal 

devices as this may cause interference.

6

 UV Lamp Connection

Make sure the flanges are aligned and then push 

the connectors firmly together. A tight connection 

ensures a proper water-resistant seal.

2. 

1. 

*Installation of this product by anyone other than licensed HVAC or electrical contractors voids warranty.

WARNING

PROTECT EYES FROM UV LIGHT

TURN OFF UNIT OR DISCONNECT

BEFORE SERVICING

5

 Connecting to Power

IMPORTANT

Before connecting to power confirm which PCO MAG model is being installed. Turn off main 

power source before installation. Model information is printed on the 

Power Unit

 cover.

IMPORTANT! Must be wired to constant power - do not connect to blower relay.

PCOMAG ER

PCOMAG

SI/DI

ST/DT

120-277 VAC

POWER SUPPLY

UV LAMP

4 PIN

CONNECTOR

L1 - BLACK
L2 or N - WHITE

GND - GREEN

Optional 2nd UV Lamp

24 VAC

POWER SUPPLY

UV LAMP

BLACK

4 PIN

CONNECTOR

RED

24 VAC TRANSFORMER

COMMON / BLUE

HOT / RED

CAUTION!

UV lamps contain small amounts of mercury - dispose of lamps in accordance with 

local environmental regulations. For more information visit www.lamprecycle.org

Note: 

Use of replacement UV lamps other than Patriot UV voids warranty

.

IMPORTANT! 

Systems with high 24 VAC loads may require the installation of a separate 24 VAC 

transformer to power the UV light.

Always use a separate 24 VAC transformer with “communicating” air systems and all 

Patriot PCO Dual (PAT-PCO-DER) models.

Draws 16 VA, may need to do load calculation: Volts under load X Amps under load.

7

  Lamp Replacement

The germicidal UV lamp in Patriot PCO needs to be 

replaced periodically. TUVL-111P and TUVL115P lamps 

should be replaced every year. TUVL-211P and TUVL-215P 

should be replaced every 2 years. 

Note: UV lamps will continue to emit visible light but lose 

germicidal effectiveness over time. You can upgrade to a 2 

year lamp with your existing Patriot PCO system.

B

TUVL-111P

C

TUVL-211P

D

TUVL-115P

TUVL-215P

E

Replacement lamps for  

PAT-PCO-MAG15

Replacement lamps for  

PAT-PCO-MAG11

PATRIOT PCO MAG