background image

Zone Thermostats

 – The thermostats wiring will for single stage 

can be four or five wire. The fifth wire being the C-Common terminal 
for 24 Volt powered thermostats. There are 5 terminals on the 
PCMMP3 for each thermostat, marked Y-G-R-W-C. This wiring is 
shown on Wiring Diagram 1 for single stage thermostats.     
 

HVAC Equipment

 – The HVAC equipment will follow Wiring 

Diagram 2 for Single Stage Systems. The PCMMP3 can also control 
Heating Only and Cooling Only as well as both Heating and Cooling.   
 

Transformer

 – A separate 24 Volt AC, 40VA Transformer is 

recommended to power the control panel and dampers. Often the 
transformer on the HVAC unit only has enough power for its own 
controls. Therefore it is recommended a separate transformer be 
used to power this panel and the dampers wired to it.   
 

Transformer Wiring 

24V TRA

N

S

C
R

C
R

T24 -24V 40VA

TRANSFORMER

 

Zone Thermostat Wiring 

G

Y

R

W

C

ZONE T

H

ERMOS

T

A

T

G

Y
R

W

C

70°

ZONE THERMOSTAT

 

Plug-In Damper Wiring 

To Additional Dampers

Up to 10 Per Zone, if used.

Zone Damper

Connector on 

Zone Panel

NOTE:

It does NOT matter which jack on damper    
goes to the panel or additional dampers.  

PLUG-IN ZONE DAMPER 

25 Foot Modular Cord

(Provided with each damper)

 

HVAC Equipment  Wiring 

Y  COMPRESSOR RELAY

G         FAN RELAY

W      HEAT RELAY

R   24V. TRANSFORMER   C

FURNACE CONTROLS

OUTDOOR CONDENSING UNIT

Y

G

W

R

EQUIPMENT

 

 

 

Zone Plenum Sensor 

The Zone Mix-Air Sensor, Model PCZPS, is a remote sensor that is 
located in the supply air duct to sense the leaving air temperature of 
the HVAC Unit. The PCZPS is a high limit protection for the heating 
and a low limit protection for the cooling. When zoning, the airflow 
through the HVAC Unit is critical. The LAS protects the equipment in 
low air flow situations as well as when by-pass air is being directed 
back into the return air duct.   
 
The heating limit is fixed at 180

n

F. The cooling limit is fixed at 40

n

F.  

When the PCZPS senses heating above its set point, or cooling 
below its set point, the PCMMP3 will drop both stages of heating or 
cooling. The PCZPS must sense a 10

n

F fall for heating or rise for 

cooling before re-activating the first stages of heating or cooling. If 
two stage heating or cooling is being used the second stage timer 
will start again once the first stage is re-activated.  

 

The PCZPS requires 2 wires from the sensor to the LAT terminals 
on the PCMMP3 panel. The PCZPS probe can also be adjusted for 
length by loosening the end nut and sliding the probe thru the 
mounting plate in order for the probe to pass through any duct 
insulation. 

 

Leaving Air Sensor

(Mounted in Supply Air before Zone Dampers)

Model ZPS

LAS Terminals
On Zone Panel

 

NOTE:  If the PCZPS is not used, the NO SENSOR jumper 
located just above the LAT terminals must be on the pins. 
 

After installing the PCZPS, use the chart supplied with the PCZPS to 
check the Ohm reading for the appropriate duct temperature.    

 

TROUBLESHOOTING

The PCMMP3 is a very simple control to troubleshoot, especially 
with the LED indicators. The only other device needed is a simple 
Volt/Ohm meter.   
 
Almost all problems can be traced to an external component or 
wiring to the PCMMP3. While the PCMMP3 has been designed to 
operate under extreme voltage conditions and is fuse protected, like 
any computer the micro-processor can hang up and not operate 
properly. For these instances a BOOT button has been installed that 
re-boots the micro-processor just like your computer. Pressing this 
button for a few seconds and then release it will allow the micro-
processor to re-boot and in most all cases eliminate the problem. If 
not the following procedure can help isolate the problem.   
 

    

 

If the BOOT Button does not resolve the problem, turn off the power 
to the panel for several seconds until the LEDs got out and then turn 
the power back on to see if the panel resets. In many instances this 
resolves the problem.   
 
The first check is for 24VAC Power to the panel. When there is 
power the Green Power LED will be lit. If not check the transformer 
and the power supply to it.   
 
 
 
 
 
 

BOOT 

4

Содержание PCMMP3

Страница 1: ...Model PCMMP3 PCMMP3 ZONING SYSTEM 3 Zones For Plug In Damper Motors 1 ...

Страница 2: ...ower transformer are wired When installing the PCMMP3 panel it is important to pick a central location where it is most convenient to bring all the wires Most often this is near the furnace or air handler and closest to power the HVAC unit controls and the zone dampers when typically located at or near the plenum The PCMMP3 case and cover are made of sturdy ABS plastic and can be mounted to any fl...

Страница 3: ... Equipment Set Up The PCMMP3 is factory set for conventional fossil fuel oil or gas single stage heating and cooling The panel only needs to be configured when using with a conventional electric furnace or hydro air system in order to bring the fan on with a call for heat By using the FIH Fan On In Heat jumper located on the upper right corner of the board this allows the Fan to be activated with ...

Страница 4: ...ting above its set point or cooling below its set point the PCMMP3 will drop both stages of heating or cooling The PCZPS must sense a 10nF fall for heating or rise for cooling before re activating the first stages of heating or cooling If two stage heating or cooling is being used the second stage timer will start again once the first stage is re activated The PCZPS requires 2 wires from the senso...

Страница 5: ...e powered is restored and the thermostat is disconnected the call should drop from the zone If not replace panel Damper Motor Checkout Procedure In order to determine the operation of the damper motors the panel motor plug can be checked to determine if power is being supplied from the panel If there is power at the motor plug the problem may be a broken wire or poor connection in the cord or the ...

Страница 6: ... BOOT Button Resets the microprocessor NO SENSOR Must be ON when not using Leaving Air Sensor and OFF when sensor is wired FIPG FIH TEST BOOT ON LOW LIMIT 24V TRANS C R C R T24 24V 40VA TRANSFORMER Y COMPRESSOR RELAY G FAN RELAY W HEAT RELAY R 24V TRANSFORMER C FURNACE CONTROLS OUTDOOR CONDENSING UNIT Y G W R EQUIPMENT G Y R W C ZONE THERMOSTAT G Y R W C 70 ZONE THERMOSTAT G Y R W C ZONE THERMOSTA...

Отзывы: