![Partlow MIC 1161 Скачать руководство пользователя страница 45](http://html1.mh-extra.com/html/partlow/mic-1161/mic-1161_operators-manual_3811728045.webp)
45
MIC 1161 Manual
Alarms
Maximum Number:
Two "soft" alarms
Maximum # Outputs:
Up to 2 outputs can be used for alarm purposes
Comb. of Alarms:
Logical ORing or ANDing of alarms to an individual
hardware output is available.
PERFORMANCE
Reference Conditions
Ambient Temperature: 20
°
C
±
2
°
C
Relative Humidity:
60-70%
Supply Voltage:
90-264VAC 50Hz
±
1%
Source Resistance:
<10 ohm for T/C input
Lead Resistance:
<0.1 ohm/lead balanced (Pt100)
Common Mode
Rejection:
>120dB at 50/60Hz giving negligible effect at up to
264V 50/60Hz
Series Mode
Rejection:
>500% of span (at 50/60Hz) causes negligible effect
Operating Conditions
Ambient Temperature: 0 to 55
°
C
Ambient Temperature
Storage:
-20 to 80
°
C
Temperature Stability: 0.01% of span/
°
C change in ambient
Relative Humidity:
20 to 95% non-condensing
Supply Voltage:
90-264 VAC 50/60Hz
Source Resistance:
1000 ohm maximum (thermocouple)
Lead Resistance:
50 ohm/lead maximum balanced (Pt100)
Measurement Accuracy
DC Linear Inputs:
±
0.25% of span
±
1 LSD
RTD/
Thermocouple Inputs:
±
0.25% of span
±
1 LSD
Note: Reduced performace with Type B T/C
between 100-600
°
C (212-1112
°
F)
Linearization:
Better than
±
0.2
°
C any point, any 0.1
°
C range
(
±
0.05
°
C typical). Better than
±
0.5
°
C any point,
any 1
°
C range.
www.
GlobalTestSupply
.com
Find Quality Products Online at: