MODBUS REGISTER MAP
Address
R/W
Description
Notes
10001
R
Status - Heated Mode
Running in Heated mode
10002
R
Status - Heatless Mode
Running in Heatless mode
10003
R
Status - Switching to Heated
Switching from Heatless to Heated
10004
R
Status - Switching to Heatless
Switching from Heated to Heatless
10005
R
Status - Extended Drying Active
Variable drying time conditions met
10006
R
Status - Extended Dry Purge Active
Currently using extended dry purge
10007
R
Status - Stepping Allowed
Stepping is currently Allowed
10008
R
Status - Manual Stepping Active
Manual stepping is currently enabled
10009
R
Status - Run/Stop Status
Drying is currently running
10010
R
Status - Dryer is Parked
Dryer is in Standby
10011
R
Status - Heating Exhaust Limits Met
Heating exhaust conditions have been met
10012
R
Status - Cooling Exhaust Limits Met
Cooling exhaust conditions have been met
10013
R
Status - Shutdown
Currently shutdown due to alarm
10014
R
Status - Active alarm
There are current active alarms
10015
R
Status - Control Air
Control Air pressure is above its setting
10016
R
Status - Restarting Dryer
Dryer is currently restarting after an alarm
10017
R
Status - Repressurizing
Currently the dryer is repressurizing both tanks
10018
R
Status - Regenerating
Currently the dryer is regenerating in Heatless operation
10019
R
Status - Heating
Currently regenerating using heated air
10020
R
Status - Blower Cooling
Currently operating in the heating stage of regeneration
10021
R
Status - Ambient (Blower) Cooling
Currently using blower to provide ambient air for cooling
10022
R
Status - Stripping
Currently using dry purge air for cooling
10023
R
Status - Drying Side
0 = Left Tower Drying
1 = Right Tower Drying
10024
R
Status - Regeneration Side
1 = Left Tower Regenerating
0 = Right Tower Regenerating
10025
R
Status - Blowing Down
Regenerating tower is currently blowing down
10026
R
Status - Remote Shutdown
Remotely shutdown the dryer
10027
R
Status - Remote Standby
Remotely place the dryer in Standby
10028
R
Status - OK to Switch
Tank pressures are ok to switch towers or open exhaust valves
10033
R
Output - Alarm Relay
Relay is active
10034
R
Output - Repressurization Valve
Repressurization valve is open
10035
R
Output - Purge Stop Valve
Purge stop valve is closed
(Blower Models Only)
10036
R
Output - Dry Purge Valve
Dry Purge valve is open (Externally Heated Models Only)
10037
R
Output - Drain #1 Valve
Drain valve is open
10038
R
Output - Drain #2 Valve
Drain valve is open
10039
R
Output - Blower Contactor
Blower is running (Blower Models Only)
10040
R
Output - Purge Heater Contactor
Heater is active
10041
R
Output - Over Temp Contactor
Over-temp contactor is closed allowing heating
10042
R
Output - Purge Heater Contactor Bank 2
Heater Bank #2 is active (Only dryers with Multi-Bank Heaters)
10043
R
Output - Purge Heater Contactor Bank 3
Heater Bank #3 is active (Only dryers with Multi-Bank Heaters)
10044
R
Output - Purge Heater Contactor Bank 4
Heater Bank #4 is active (Only dryers with Multi-Bank Heaters)
10045
R
Output - Left Pre-Exhaust Valve
Left pre-exhaust valve is open
(Only dryers with pre-exhaust valves)
Содержание TWP/TWB201
Страница 1: ...1 Externally Heated Blower Purge Desiccant Dryers User Manual Models TWP TWB201 TWP TWB7501...
Страница 9: ...TWP TWB201 TWP TWB7501 9 TWP Desiccant Dryer Operation TWB Desiccant Dryer Operation...
Страница 10: ...TWP TWB201 TWP TWB7501 10 FLOW SCHEMATIC MODELS TWP201 301...
Страница 11: ...TWP TWB201 TWP TWB7501 11 FLOW SCHEMATIC MODELS TWP401 801...
Страница 12: ...TWP TWB201 TWP TWB7501 12 FLOW SCHEMATIC MODELS TWP1001 1201...
Страница 13: ...TWP TWB201 TWP TWB7501 13 FLOW SCHEMATIC MODELS TWP1501 7501...
Страница 14: ...TWP TWB201 TWP TWB7501 14 FLOW SCHEMATIC MODELS TWB201 801...
Страница 15: ...TWP TWB201 TWP TWB7501 15 FLOW SCHEMATIC MODELS TWB1001 1201...
Страница 16: ...TWP TWB201 TWP TWB7501 16 FLOW SCHEMATIC MODELS TWB1501 7501...
Страница 17: ...TWP TWB201 TWP TWB7501 17 TWP WIRING DIAGRAM STANDARD CONTROLLER...
Страница 18: ...TWP TWB201 TWP TWB7501 18 TWP WIRING DIAGRAM STANDARD CONTROLLER...
Страница 19: ...TWP TWB201 TWP TWB7501 19 TWP WIRING DIAGRAM STANDARD CONTROLLER...
Страница 20: ...TWP TWB201 TWP TWB7501 20 TWP WIRING DIAGRAM STANDARD CONTROLLER...
Страница 21: ...TWP TWB201 TWP TWB7501 21 TWB WIRING DIAGRAM STANDARD CONTROLLER...
Страница 22: ...TWP TWB201 TWP TWB7501 22 TWB WIRING DIAGRAM STANDARD CONTROLLER...
Страница 23: ...TWP TWB201 TWP TWB7501 23 TWB WIRING DIAGRAM STANDARD CONTROLLER...
Страница 24: ...TWP TWB201 TWP TWB7501 24 TWB WIRING DIAGRAM STANDARD CONTROLLER...
Страница 25: ...TWP TWB201 TWP TWB7501 25 PANEL LAYOUT STANDARD CONTROLLER...
Страница 42: ...TWP TWB201 TWP TWB7501 42 Service Screen...