10
Parker Hannifin Corporation
TFP 5715-734UK.indd 24.06.22
2-Way Servo Proportional Valves
Series TFP
Operation Manual
The connecting cable has to comply to the follow-
ing specification:
Cable type
control cable, flexible,
7 conductors, overall braid
shield
Cross section
min. AWG16
Outer dimension
8...12 mm
Cable length
max. 50 m
For cable lengths > 50 m consult Parker.
The connection cable is coupled to the female
connector by solder joints.
Skinning lengths for the connecting cable:
Electrical Connection
The electrical connection of the valve takes place
by one common cable, which is coupled to the
integrated electronic driver by a central connector
assembly.
The connection requires a 6 + PE female connector
EN 175201-804.
Female connector (ordering no. 5004072)
A female connector with metal housing is
required! Plastic made models may create
function problems due to insufficient EMC-
characteristics.
Do not disconnect cable socket under tension!
Pressure Fluids
The following rules applies for the operation with
various pressure fluids:
This information serves for orientation and
does not substitute user tests among the
particular operating conditions. Particularly no
liabiliy for media compatibility may be derived
out of it.
Mineral oil: usable without restriction.
HFC: Choose seal option code N.
HFA
Oil-in-water emulsion
HFB
Water-in-oil emulsion
HFD
Unhydrous fluids (Phosphor-Ester)
For operation with the following pressure fluids
please consult Parker:
For detailed information concerning pressure
fluids note VDMA-document 24317 as well as
DIN 51524 & 51502.
Special gaskets may be available depending on
the utilized fluid.
In case of doubt please consult Parker.
Limits of Use
The valve may be operated within the determined
limits only. Please refer to the “technical data“
section as well as to the “characteristic curves“ in
the Parker catalogue MSG11-3500/UK "Hydraulic
Valves Industrial Standard".
Follow the environmental conditions! Unal-
lowable temperatures, shock load, aggresive
chemicals exposure, radiation exposure,
illegal electromagnetic emissions may result
in operating trouble and may lead to failure!
Follow the operating limits listed in the “speci-
fications“ table!