Technical Characteristics
PSUP Mains module
26
192-120147N9 PSUP Manual 2019-06
PSUP30D6 Mains connection
Device type PSUP30
230V
400V
480V
Supply voltage
230VAC ±10%
50-60Hz
400VAC ±10%
50-60Hz
480VAC ±10%
50-60Hz
Rated voltage
3AC 230V
3AC 400V
3AC 480V
Input current
50Arms
50Arms
42Arms
Output Voltage
325VDC ±10%
565VDC ±10%
680VDC ±10%
Output power
17kW
30kW
30kW
Pulse power (<5s)
34kW
60kW
60kW
Heat dissipation
140W
140W
140W
Maximum fuse rating per
device
2 special purpose fuses in
line are required
Cable protection measure:
MCB (K characteristic) with a rating of 63A / 4xxVAC
(depending on the input voltage)
Recommendation: (ABB) S203U-K63 (440VAC)
Device protection measure:
Circuit breakers 125A / 700VAC per supply leg in
accordance with UL category JFHR2
Requirement: Bussmann 170M1368 or 170M1568D
Control voltage 24 VDC PSUP
Device type
PSUP
Voltage range
21 - 27VDC
Ripple
0.5Vpp
Requirement according to safe extra
low voltage (SELV)
yes (class 2 mains module)
Current drain PSUP
PSUP10: 0.2A
PSUP20 / PSUP30: 0.3A
UL approval for mains modules PSUP
Conform to UL:
in accordance with UL508C
Certified
E-File_No.:
E142140
The UL approval is documented by a
“UL” logo on the device (type
specification plate).
UL approval PSUP30 in preparation!
Insulation requirements
Enclosure rating
Protection class in accordance with EN 60664-1
Protection against human contact
with dangerous voltages
In accordance with EN 61800-5-1
Overvoltage category
Voltage category III in accordance with
EN 60664-1
Degree of contamination
Degree of contamination 2 in accordance with
EN 60664-1 and EN 61800-5-1