Parker IQAN-MC31 Скачать руководство пользователя страница 18

 16

Addressing/terminating

     

Instruction book, IQAN- MC31

Addressing/terminating

IQAN-MC31 use of an ID-Tag

In IQANdesign 3.0 and higher software, more than one IQAN master module can be 
used together in a multi-master system. The master modules are each given a unique 
address by using an ID-Tag. The value of the ID-Tag identifies the master and will 
enable a single project application to be loaded into more than one master module over 
the CAN bus. The functionality needed for each master is loaded based on the ID-tag 
address. 

Identification of an IQAN-MC31 by address

For normal operation of an IQAN-MC31 in a single master system, the ID-Tag is still 
used. When no ID-Tag is installed the MC31 or if the ADDR pins are jumpered on 
power up, the MC31 will start in safe mode. 
The connection of an ID-Tag between ADDR-H and ADDR-L will assign an address to 
the IQAN-MC31 master module. The desired functionality based on address is built 
into the project file using IQANdesign software. For more information, please refer to 
the IQANdesign user manual. 
It is the combination of 

address

 and

 type

 that gives each master module a unique 

identification. The maximum number of MC31 addresses is 8, denoted as addresses 0, 
1, 2, 3, 4, 5, 6, 7 respectively. 
In order to assign any IQAN-MC31 an address , an 

ID-Tag

 will have to be connected to 

the positions ADDR-H and ADDR-L.

Connecting of Id-Tag.

Terminating

To eliminate interference in the communications through the CAN bus, the CAN bus 
must be terminated. By default, the MC31 is terminated internally on all of its CAN 
buses. When an IQANdesign application is loaded, it can set individual buses to be 
non-terminated.

To give an IQAN-MC31 a unique address, you may use an addressing ID-tag, or an ID-
tag having a combined address and terminating function. The ’T’ values of ID-tags are 
ignored, i.e. an ID-tag 3T is equivalent to ID-tag 3.

If the module is located at the end of the CAN-bus, then leave the bus default 
terminated in the MC31.

N

OTICE

The CAN-bus should not be terminated at the MC31 using an external regular 
terminating resistor, due to the fact that terminating is made from within the MC31 
module by default.

ID-Tag

ADDR-L

ADDR-H

IQAN-MC31

Содержание IQAN-MC31

Страница 1: ...IQAN MC31 Instruction book Publ no HY33 8411 IB UK Edition 2016 07 05...

Страница 2: ...nectors C1 C4 11 Supply voltage 15 Addressing terminating 16 Diagnostic interfaces 17 Reference voltage VREF 18 Voltage inputs 19 Digital inputs 22 Frequency inputs 24 Proportional outputs 25 Connecti...

Страница 3: ...is common to the term hazardous situation that a person is exposed to a hazard As a way of pointing out important information for the machine designer that in some way relates to safety This includes...

Страница 4: ...ation contains product information in a compact format for details on the information found in those documents consult this manual The IQAN module documentation system Compact Documentation Main Docum...

Страница 5: ...ctions on the system must be disconnected from other equipment The negative cable must always be disconnected from the battery before disconnecting the positive cable The ground wire of the welder sha...

Страница 6: ...ics may only be carried out by trained personnel who are well acquainted with the control system the machine and its safety regulations Before you start Read section Start up Additional information fo...

Страница 7: ...n there is a need of higher performance in a sub circuit or when there is an OEM supplied overall machine master This product is designed for the outdoor environment and comes with an IP6K9K protectio...

Страница 8: ...ferent modes Either Current mode current closed loop or PWM mode voltage open loop signals can be selected and the parameters configured using IQAN software See below In order to increase the performa...

Страница 9: ...unit has four 4 CAN buses CAN A thru CAN D The buses may be configured using IQAN software to be ICP ICP IQAN CAN Protocol SAE J1939 or Generic user defined CAN protocol e g CANopen Communication The...

Страница 10: ...8 Markings Approvals 3 Product description Instruction book IQAN MC31 Markings Approvals...

Страница 11: ...r an application defined error value for the module inputs and the module outputs will be off The error will be presented on the master display module if there is one and with a related blink code on...

Страница 12: ...act is avoided e g impact from falling objects or the module being used as a step Locate the module so that air can circulate to eliminate excess heat Ensure that no external heat e g from the engine...

Страница 13: ...GH in dominant state CAN B L 5 CAN low voltage bus line will be LOW in dominant state CAN B H 6 CAN high voltage bus line will be HIGH in dominant state ADDR L 7 IdTag interface Low side to address ta...

Страница 14: ...e for external sensors Return 0V VREF A 2 Voltage reference for external sensors Sourcing 5V VIN A 3 I Voltage signal input VIN B 4 I Voltage signal input VIN C 5 I Voltage signal input VIN D 6 I Volt...

Страница 15: ...nce for external sensors Sourcing 5V DIN A 3 I DIN FIN DFIN PCN DPCN signal input DIN B 4 I DIN FIN DFIN PCN DPCN signal input DIN C 5 I DIN FIN DFIN PCN DPCN signal input DIN D 6 I DIN FIN DFIN PCN D...

Страница 16: ...ver low side CRET A 3 O COUT power driver low side COUT B 4 O COUT power driver high side CRET B 5 O COUT power driver low side CRET B 6 O COUT power driver low side COUT C 7 O COUT power driver high...

Страница 17: ...r should be as close to the battery as possible for safety IQAN expansion modules do not have RTC WARNING Risk of injury To reduce the risk for uncontrolled supply of an IQAN master module i e a short...

Страница 18: ...ore information please refer to the IQANdesign user manual It is the combination of address and type that gives each master module a unique identification The maximum number of MC31 addresses is 8 den...

Страница 19: ...to use this feature Contact Parker for information about supported CAN interfaces A termination resistor is usually required at the CAN interface on the PC Parker part number 5030082 or 5030182 or an...

Страница 20: ...ors and potentiometers VREF positions NOTICE It is strongly recommended to use the module s VREF and VREF to all sensors and potentiometers that are connected to the module inputs This will reduce bad...

Страница 21: ...on NOTICE The negative terminal of the sensor must not be connected to the chassis Maximum load for VREF position see Appendix A Connecting other 3 wire sensors The same type of connection shown for p...

Страница 22: ...d be connected to VREF and VIN DIN respectively for 5V signal The current consumption for the input is negligible NOTICE Maximum load for VREF position see Appendix A EXAMPLE Connect the negative term...

Страница 23: ...ed to connect system voltage BAT to the input through a switch in order to reserve 5Vdc VREF for sensors and potentiometers EXAMPLE Connect the positive and negative terminals of the switch to supply...

Страница 24: ...ing switches to the digital inputs DIN that share pins with CRET extra precautions should be taken WARNING The DIN that share pins with the CRET positions of the proportional outputs have a possibilit...

Страница 25: ...4 Vdc systems The DIN signal will not be detected by the module Remember that these flexible I O pins must be configured in pairs of the same type EXAMPLE Connect the supply of the switch to BAT throu...

Страница 26: ...e terminal to the VREF respectively The sensor signal is connected to the FIN position If the current consumption for the sensor exeeds the maximum load for the VREF the sensor could be connected to t...

Страница 27: ...e frequency which can be changed using IQAN software For the possible frequencies see Appendix A Connecting loads to proportional outputs Connecting a load e g one proportional valve section to the cu...

Страница 28: ...ut and ground as close to the load as possible This protects the output against high voltage transients For example use diode 1N5408 3A 1000V Depending on the load other clamping diodes might be used...

Страница 29: ...ents For example use diode 1N5408 3A 1000V Depending on the load other clamping diodes might be used instead WARNING Loads on DOUT with Low Side switch DOUT LS must always be controlled on the high si...

Страница 30: ...might be used instead DOUT output diagnostics The diagnostic DOUT is capable of detecting internal faults as well as wiring faults The fault will be identified as one of the following status values in...

Страница 31: ...a tively the emergency stop may also shut off the diesel engine or a dump valve and with that depressurize the hydraulic system Prepare for system start WARNING Make sure no one is in dangerous proxim...

Страница 32: ...the IQAN module will indicate error status through the red blinking LED This gives an immediate diagnosis as to the nature of the error that has occurred The location of the LED indicators on the IQA...

Страница 33: ...he application will not be loaded This is a special start up mode that is used for master modules and puts the unit in a safe state without starting any application When safe mode is desired a jumper...

Страница 34: ...ate Heat operation Heat storage Cold Change of temperature IEC 60529 2001 IP67 DIN 40050 Part 9 1993 IP6K9K IEC 60068 2 52 1996 Kb 72 h IEC 60068 2 30 2005 Db 55 C 95 RH 6 cycles IEC 60068 2 78 2001 C...

Страница 35: ...25 mV C 40 to 85 C Maximum load current 140 mA on each VREF Protection overload SCB SCG Diagnostics over under voltage Under over voltage threshold 150 mV from nominal value Signal input VIN Number of...

Страница 36: ...V 0 3 V Input impedance 6 8 kohm in parallel with 10 nF Sample rate same as system cycle time TSC Maximum continuous voltage 32V Diagnostics Defined in application Signal input PCNT DPCNT Number of PC...

Страница 37: ...BAT 14V and FDITH 200 Hz 5 ohm 10 mH 5 ohm 20 mH 10 ohm 30 mH 20 ohm 60 mH Maximum allowable load inductance 1 0 A load 1 5 A load 2 0 A load 500 mH 200 mH 50 mH Protection SCB SCG Diagnostics Operati...

Страница 38: ...typ 0 41 V 1 5 A load Leakage current in OFF state DOUT A to C high side DOUT D to E high side DOUT F to H low side DOUT I to J low side 100 A 100 A 2 mA 100 A Maximum allowable load inductance DOUT...

Страница 39: ...ease safety WARNING Don t use the machine if an error message or error code is activated LED indicator showing different MC31 modes Status Flash yellow Normal operation Application not loaded No appli...

Страница 40: ...he IQAN MC31 module Appendix C Instruction book IQAN MC3 Appendix C Dimensioning of the IQAN MC31 module 6 12 18 6 12 18 6 12 18 6 12 18 1 7 13 1 7 13 1 7 13 1 7 13 A B C D C4 C3 C2 C1 IQAN MC3 230 21...

Страница 41: ...nge without notice Parker Hannifin Electronic Controls Division SE 435 35 M lnlycke Sweden Tel 46 31 750 44 00 Fax 46 31 750 44 21 www parker com Parker Hannifin Electronic Controls Division 1651 N Ma...

Отзывы: