Compax3
device description
C3I12T11
46
192-120113 N08 C3I12T11 - December 2010
3.5.5.
Mains supply PSUP (mains module) X41
By cyclically switching on and off the power voltage, the input current
limitation can be overloaded, which may cause damage to the device.
Wait at least one minute between two switching on processes!
Operation of the PSUP30 only with mains filter!
Connector X41
Pin Designation
PE
Earth conductor
L3
Phase 3
L2
Phase 2
L1
Phase 1
Mains connection PSUP10D6
Device type PSUP10
230V
400V
480V
Supply voltage
230VAC ±10%
50-60Hz
400VAC ±10%
50-60Hz
480VAC ±10%
50-60Hz
Rated voltage
3AC 230V
3AC 400V
3AC 480V
Input current
22Arms
22Arms
18Arms
Output voltage
325VDC ±10%
565VDC ±10%
680VDC ±10%
Output power
6kW
10 kW
10 kW
Pulse power (<5s)
12kW
20kW
20kW
Power dissipation
60W
60W
60W
Maximum fuse rating per
device (=short circuit rating)
Measure for line and device protection:
MCB miniature circuit breaker (K characteristic) 25A in
accordance with UL category DIVQ
Recommendation: (ABB) S203UP-K 25(480VAC)
Mains connection PSUP20D6
Device type PSUP20
230V
400V
480V
Supply voltage
230VAC ±10%
50-60Hz
400VAC ±10%
50-60Hz
480VAC ±10%
50-60Hz
Rated voltage
3AC 230V
3AC 400V
3AC 480V
Input current
44Arms
44Arms
35Arms
Output voltage
325VDC ±10%
565VDC ±10%
680VDC ±10%
Output power
12kW
20kW
20kW
Pulse power (<5s)
24kW
40kW
40kW
Power dissipation
120W
120W
120W
Maximum fuse rating per
device (=short circuit rating)
2 circuit breakers in line are
required
Cable protection measure:
MCB (K characteristic) with a rating of 50A / 4xxVAC
(depending on the input voltage)
Recommendation: (ABB) S203U-K50 (440VAC)
Device protection measure:
Circuit breakers 80A / 700VAC per supply leg in
accordance with UL category JFHR2
Requirement: Bussmann 170M1366 or 170M1566D
Device protection