Parker EME
Compax3 device description
192-120113 N08 C3I12T11 - December 2010
45
Maximum capacity in the axis system:
PSUP10: 2400 µF
PSUP20 & PSUP30: 5000 µF
Reference value for the required capacity in an axis system
100 µF per kW of the temporal medium value of the total power (transmi
power dissipation) in the axis system
Example: PSUP20 (1175 µF) with one axis controller (440 µF)
Total power 15 kW, 100 µF/kW => 1500 µF required in the axis system.
Axis system: 1615 µF are sufficient.
Protective seals
Caution!
The user is responsible for protective covers and/or additional safety measures in
order to prevent damages to persons and electric accidents.
3.5.4.
Control voltage 24VDC PSUP (mains module)
Connector X9
Pin
Designation
Line cross sections:
minimum: 0.5mm
2
with conductor sleeve
maximum: 6mm
2
with conductor sleeve
(AWG: 20 ... 10)
1
+24 V
2
GND24V
Control voltage 24 VDC PSUP
Device type
PSUP
Voltage range
21 - 27VDC
Ripple
0.5Vpp
Requirement according to safe extra
low voltage (SELV)
yes (class 2 mains module)
Current drain PSUP
PSUP10: 0.2A
PSUP20 / PSUP30: 0.3A
Electric current drain Compax3M
C3M050D6: 0.85
3M100D6: 0.85A
C3M150D6: 0.85A
C3M300D6: 1.0 A
+ Total load of the digital o current for
the motor holding brake