SUPERVISOR PARAMETERS
13
ATT+ 140-340
MODBUS BASED (0)
ANALOG / INTEGER VARIABLES (HOLDING REGISTER)
BMS
Address
Description
Default
"Read/
Write"
Variable name
40001
Adsorber Inlet Temperature
0
R
ADInletTemp
40002
Purge Air Temperature
0
R
PurgeAirTemp
40003
Dew Point Temperature
0
R
DewpointTempDisplay
40008
Set Dew Point Fitted
-40
R/W
SetPDP
40016
Thermal Mass Temperature
0
R
ThermalMassTemp
40050
Pressure Column 1
0
R
Pressure_Col1
40051
Pressure Column 2
0
R
Pressure_Col2
40052
Discharge Refrigerant Temperature
0
R
DischRefrTemp
40067
Optional (Ambient Temperature )
0
R
AmbientProbe
40129
90
R/W
SetAt70
40130
10
R/W
RitTc
40145
146
R/W
SetAt
40148
5
R/W
Set_i
40149
0
R
TimerFaseAdsorbtionCol1
40150
0
R
TimerFaseAdsorbtionCol2
40151
0
R
TimerFaseHeatingCol1
40152
0
R
TimerFaseHeatingCol2
40153
0
R
TimerFaseCoolingCol1
40154
0
R
TimerFaseCoolingCol2
40156
59
R/W
SetHt40
40157
30
R/W
SetCt40
40171
150
R/W
SetTHeat
40179
Software Release
0
R
SW_Release
40180
Software Date Year
0
R
SW_Date_Year
40181
Software Date Month
0
R
SW_Date_Month
40182
Software Date Day
0
R
SW_Date_Day
40187
8
R/W
UnitModel
40188
Operating Software
2
R
OperatingSoftware
40199
Moisture Drain ON
5
R/W
ParMoistureDrainModeTon
40200
Moisture Drain OFF
120
R/W
ParMoistureDrainModeToff
40202
Modbus Address
1
R/W
BMS_ADDRESS
40203
Baud Rate
3
R/W
BaudRate
40204
Money Type
0
R/W
MoneyType
40206
0
R/W
SelezioneDeltaKwh
40212
Delay Change Filter Year
0
R
UltimoCambioFiltroAnno
40213
Delay Change Filter Month
1
R
UltimoCambioFiltroMese
40214
Delay Change Filter Day
1
R
UltimoCambioFiltroGiorno
40218
Optional (Set ambient Temperature )
13.0
R/W
SetTambiente
40219
Optional (Diff ambient Temperature )
2.0
R/W
DiffTambiente
40220
Ooptional (Delay summer Day)
0
R/W
DeleyEstateGiorni
40221
Ooptional (Delay summer Hour)
0
R/W
DelayEstateOre
40222
Ooptional (Delay summer Day)
1
R/W
DelayEstateGiorni
40223
Optional (Offset Dew Point )
0
R/W
OffsetDewPoint
40224
Optional (set Dew point )
10
R/W
SetPointDewpoint
40226
Optional (Diff Dew point )
0
R/W
DiffDewPoint
40229
Working Pressure
0
R
WorkingPressure
40241
Mode Moisture Drain
1
R/W
ParMoistureDrainMode
40289
0
R
NewSetPDP
MODBUS CONFIGURATION
BUAD
RATE
PRO
Parity
Stop
Bit
Data
Bits
Holding
register
Offset
digital
0 = 1200
1 = 1200
2 = 4800
3 = 9600
4 = 19200
0 = MDBUS
NONE
1
8
40000
0